Specifications Table for EDLA09-14DW1

EDLA09DAW1 EDLA11DAW1 EDLA14DAW1
Heating capacity Nom. kW 9.37 (1), 9.00 (2) 10.6 (1), 9.82 (2) 12.0 (1), 12.5 (2)
Power input Heating Power input-=-Heating-=-Nom.-=-kW @ kW 1.91 (1), 2.43 (2) 2.18 (1), 2.68 (2) 2.46 (1), 3.42 (2)
COP 4.91 (1), 3.71 (2) 4.83 (1), 3.66 (2) 4.87 (1), 3.64 (2)
Dimensions Unit Dimensions-=-Unit-=-Height-=-mm @ mm 870 870 870
    Width mm 1380 1380 1380
    Depth mm 460 460 460
Weight Unit kg 147 147 147
Fan Air flow rate Heating High m³/min 48.0 55.8 70.4
Operation range Heating Water side Min. °C 9 (6) 9 (6) 9 (6)
      Max. °C 60 (6) 60 (6) 60 (6)
  Domestic hot water Ambient Min. °CDB -25 -25 -25
      Max. °CDB 35 35 35
    Water side Min. °C 25 25 25
      Max. °C 55 (6) 55 (6) 55 (6)
Refrigerant Type   R-32 R-32 R-32
  GWP   675 675 675
  Charge kg 3.80 3.80 3.80
  Charge tCO2Eq 2.57 2.57 2.57
Space heating Average climate water outlet 55°C General Space heating-=-Average climate water outlet 55°C-=-General-=-SCOP @   3.39 3.32 3.37
      Seasonal space heating eff. class   A++ A++ A++
  Average climate water outlet 35°C General Space heating-=-Average climate water outlet 35°C-=-General-=-SCOP @   4.72 4.64 4.62
      Seasonal space heating eff. class   A+++ A+++ A+++
Energy Efficiency Range Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F
Compressor component Main power supply Phase   3N~ 3N~ 3N~
    Voltage V 400 400 400
Power supply Name   W1 W1 W1
  Phase   3~ 3~ 3~
  Frequency Hz 50 50 50
  Voltage V 400 400 400
Notes (1) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
  (2) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (2) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (2) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
  (3) - For more details, see operation range drawing (3) - For more details, see operation range drawing (3) - For more details, see operation range drawing
  (4) - Depends on operation mode, refer to installation manual. (4) - Depends on operation mode, refer to installation manual. (4) - Depends on operation mode, refer to installation manual.