ABQ100CV1 / AZQS100B7V1B ABQ125CV1 / AZQS125B7V1B ABQ140CV1 / AZQS140B7V1B
Poff (Off mode) W 0.0    
Cooling Psb (Standby mode cooling) W 9.0    
  Cooling-=-Cooling cdc degradation cooling 0.25    
Seasonal efficiency (according to EN14825) Cooling Pdesign kW 9.50    
    Annual energy consumption kWh 716    
    Seasonal efficiency (according to EN14825)-=-Cooling-=-Seasonal efficiency according to en14825 cooling energy label 4.65    
    D Condition (20°C - 27/19) Pdc kW 4.20    
      power input kW 0.58    
      Seasonal efficiency (according to EN14825)-=-Cooling-=-D Condition (20°C - 27/19)-=-Eerd 7.35    
    C Condition (25°C - 27/19) power input kW 0.76    
      Pdc kW 4.50    
      Seasonal efficiency (according to EN14825)-=-Cooling-=-C Condition (25°C - 27/19)-=-Eerd 5.94    
    A Condition (35°C - 27/19) power input kW 3.63    
      Pdc kW 9.50    
      Seasonal efficiency (according to EN14825)-=-Cooling-=-A Condition (35°C - 27/19)-=-Eerd 2.62    
    B Condition (30°C - 27/19) Pdc kW 7.00    
      power input kW 1.86    
      Seasonal efficiency (according to EN14825)-=-Cooling-=-B Condition (30°C - 27/19)-=-Eerd 3.78    
  Heating (Average climate) Annual energy consumption kWh 2,498    
    Pdesign kW 6.78    
    Required back up heating cap at design conditions kW 3.89    
    Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-Seasonal efficiency according to en14825 heating average climate scop A    
    TBivalent Pdh (declared heating cap) kW 6.00    
      Power input kW 2.20    
      Tbiv (bivalent temperature) °C -7    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TBivalent-=-Copd declared cop 2.73    
    C Condition (7°C) Pdh (declared heating cap) kW 3.00    
      Power input kW 0.56    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-C Condition (7°C)-=-Copd declared cop 5.43    
    TOL Tol (temperature operating limit) °C -15    
      Pdh (declared heating cap) kW 7.70    
      Power input kW 4.33    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TOL-=-Copd declared cop 1.78    
    A Condition (-7°C) Pdh (declared heating cap) kW 6.00    
      Power input kW 2.20    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-A Condition (-7°C)-=-Copd declared cop 2.73    
    D Condition (12°C) Pdh (declared heating cap) kW 3.50    
      Power input kW 0.55    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-D Condition (12°C)-=-Copd declared cop 6.45    
    B Condition (2°C) Power input kW 1.05    
      Pdh (declared heating cap) kW 3.70    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-B Condition (2°C)-=-Copd declared cop 3.55    
Cooling capacity Nom. kW 9.5 12.1 13.0
Pck (Crankcase heater mode) W 0.0    
Nominal efficiency Annual energy consumption kWh 1,813 2,153 (0.000) 2,159
  Energy label Heating D   B
  Nominal efficiency-=-Cop 2.62   3.01
Heating Psb (Standby mode heating) W 9.0    
  Heating-=-Heating cdh degradation heating 0.25    
Heating capacity Nom. kW 10.8 13.5 15.5
Pto (Thermostat off) W 109.0    
Power input Cooling Nom. kW 3.63 4.31 4.32
  Heating Nom. kW 3.16 3.96 4.55
Cold season included yes    
Notes Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load   Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load
Nominal efficiency EER     2.81  
  COP     3.41  
  Energy labeling Directive Cooling     C  
    Heating     B  
Notes   EER/COP according to Eurovent 2012, for use outside EU only  
    Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load