Specifications Table for ADEA-A

ADEA35A2VEB ADEA50A2VEB ADEA60A2VEB ADEA71A2VEB ADEA100A2VEB ADEA125A2VEB
Cooling capacity Total capacity Nom. kW           14.00
Heating capacity Total capacity Nom. kW           13.50
Casing Colour   Not painted (galvanised) Not painted (galvanised) Not painted (galvanised) Not painted (galvanised) Not painted (galvanised) Not painted (galvanised)
  Material   Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate
Dimensions Unit Height mm 245 245 245 245 245 245
    Width mm 700 700 1,000 1,000 1,400 1,400
    Depth mm 800 800 800 800 800 800
Weight Unit kg 28.0 28.0 35.0 35.0 46.0 46.0
Fan External static pressure High Pa 150 150 150 150 150 150
    Nom. Pa 30 30 30 30 40 50
Sound power level Cooling dBA 60 60 56 56 58 62
Sound pressure level Cooling High dBA 35 35 30 30 34 37
    Medium dBA 32 32 28 28 32 35
    Low dBA 29 29 25 25 30 32
  Heating High dBA 37 37 31 31 36 38
    Medium dBA 34 34 28 28 33 35
    Low dBA 29 29 25 25 30 32
Piping connections Liquid OD mm 6.35 6.35 6.35 9.52 9.52 9.52
  Gas OD mm 9.52 12.70 12.70 15.90 15.90 15.90
  Drain   VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26)
Drain-up height mm 625 625 625 625 625 625
Control systems Infrared remote control   BRC4C65, BRC4C66 BRC4C65, BRC4C66 BRC4C65, BRC4C66 BRC4C65, BRC4C66 BRC4C65, BRC4C66 BRC4C65, BRC4C66
  Wired remote control   BRC1D528, BRC1E53A7, BRC1E53B7, BRC1E53C7 BRC1D528, BRC1E53A7, BRC1E53B7, BRC1E53C7 BRC1D528, BRC1E53A7, BRC1E53B7, BRC1E53C7 BRC1D528, BRC1E53A7, BRC1E53B7, BRC1E53C7 BRC1D528, BRC1E53A7, BRC1E53B7, BRC1E53C7 BRC1D528, BRC1E53A7, BRC1E53B7, BRC1E53C7
Standard Accessories Operation manual 1 1 1 1 1 1
  Installation manual 1 1 1 1 1 1
  Drain hose 1 1 1 1 1 1
  Metal clamp for drain hose 1 1 1 1 1 1
  Washer for hanger bracket 8 8 8 8 8 8
  Screws 40 40 40 40 40 40
  Insulation for fitting 2 2 2 2 2 2
  Sealing pads 5 5 5 5 5 5
  Clamps 4 4 4 4 4 4
Power supply Phase   1~ 1~ 1~ 1~ 1~ 1~
  Frequency Hz 50 50 50 50 50 50
  Voltage V 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220
Notes (1) - Sound power level is an absolute value that a sound source generates. (1) - Sound power level is an absolute value that a sound source generates. (1) - Sound power level is an absolute value that a sound source generates. (1) - Sound power level is an absolute value that a sound source generates. (1) - Sound power level is an absolute value that a sound source generates. (1) - Sound power level is an absolute value that a sound source generates.
  (2) - See separate drawing for electrical data (2) - See separate drawing for electrical data (2) - See separate drawing for electrical data (2) - See separate drawing for electrical data (2) - See separate drawing for electrical data (2) - See separate drawing for electrical data