EBHQ006BBV3 EBHQ008BBV3
Heating capacity Min. kW 4.36 (2), 3.87 (4) 4.36 (2), 3.87 (4)
  Nom. kW 6.00 (2), 5.58 (4) 8.85 (2), 8.15 (4)
  Max. kW 7.45 (2), 6.68 (4) 9.58 (2), 8.76 (4)
Cooling capacity Min. kW 4.82 (1), 3.67 (3) 4.82 (1), 3.67 (3)
  Nom. kW 7.00 (1), 5.12 (3) 8.37 (1), 6.08 (3)
  Max. kW 7.20 (1), 5.12 (3) 8.91 (1), 7.10 (3)
Power input Cooling Nom. kW 2.20 (1), 2.16 (3) 2.97 (1), 2.75 (3)
  Heating Nom. kW 1.41 (2), 1.79 (4) 2.21 (2), 2.72 (4)
COP 4.26 (2), 3.11 (4) 4.00 (2), 3.00 (4)
EER 3.18 (1), 2.37 (3) 2.82 (1), 2.21 (3)
Casing Colour   Ivory white Ivory white
  Material   Painted galvanized steel plate Painted galvanized steel plate
Dimensions Unit Height mm 805 805
    Width mm 1,190 1,190
    Depth mm 360 360
  Packed unit Height mm 915 915
    Width mm 1,265 1,265
    Depth mm 442 442
Weight Unit kg 95 95
  Packed unit kg 104 104
  Operation weight kg 99 99
Packing Material   Carton + Wood + EPS Carton + Wood + EPS
  Weight kg 8 8
Heat exchanger Length mm 845 845
  Rows Quantity   2 2
  Fin pitch mm 1.8 1.8
  Stages Quantity   32 32
  Tube type   ø8 Hi-XA ø8 Hi-XA
  Fin Type   WF fin WF fin
    Treatment   Anti-corrosion treatment (PE) Anti-corrosion treatment (PE)
Fan Type   Propeller fan Propeller fan
  Quantity   1 1
  Discharge direction   Horizontal Horizontal
Fan motor Quantity   1 1
  Output W 53 53
Compressor Quantity   1 1
  Model   2YC63BXD#C 2YC63BXD#C
  Type   Hermetically sealed swing compressor Hermetically sealed swing compressor
  Output W 1,920 1,920
  Starting method   Inverter driven Inverter driven
Operation range Heating Ambient Min. °CWB -15 -15
      Max. °CWB 25 25
    Water side Min. °C 15 (7) 15 (7)
      Max. °C 50 (7) 50 (7)
  Cooling Ambient Min. °CDB 10 10
      Max. °CDB 43 43
    Water side Min. °C 5 5
      Max. °C 22 22
  Domestic hot water Ambient Min. °CDB -15 -15
      Max. °CDB 35 35
    Water side Min. °C 25 25
      Max. °C 80 80
Sound power level Heating Nom. dBA 61 62
  Cooling Nom. dBA 63 63
Sound pressure level Heating Nom. dBA 48 (6) 49 (6)
  Cooling Nom. dBA 48 (6) 50 (6)
Refrigerant Type   R-410A R-410A
  GWP   2,087.5 2,087.5
  Charge kg 1.7 1.7
  Charge TCO2Eq 3.5 3.5
  Control   Expansion valve (electronic type) Expansion valve (electronic type)
  Circuits Quantity   1 1
Refrigerant oil Type   FVC50K FVC50K
  Charged volume l 0.75 0.75
Defrost method Reversed cycle Reversed cycle
Defrost control Sensor for outdoor heat exchanger temperature Sensor for outdoor heat exchanger temperature
Capacity control Method   Inverter controlled Inverter controlled
Safety devices Item 01   Fan motor thermal protection Fan motor thermal protection
    02   Fuse Fuse
    03   Safety valve Safety valve
    04   Flowswitch Flowswitch
    05   Clixon expansion vessel heater Clixon expansion vessel heater
Pump Type   Water cooled Water cooled
  Quantity   1 1
  Model   RS 25/7 3 PL 130 3 RS 25/7 3 PL 130 3
  Nr of speeds   3 3
  Nominal ESP unit Heating kPa 46.1 (2), 47.9 (4) 35.1 (2), 35.6 (4)
    Cooling kPa 49.7 (3), 41.5 (1) 45.8 (3), 34.3 (1)
  Power input W 130 130
Water side Heat exchanger Type   Brazed plate Brazed plate
  Quantity   1 1
  Water volume l 0.67 0.67
  Water flow rate Heating Nom. l/min 17.2 (2), 16.0 (4) 25.4 (2), 23.4 (4)
    Cooling Nom. l/min 14.7 (3), 20.1 (1) 17.4 (3), 24.0 (1)
    Min. l/min 12 12
  Insulation material   Foamed polyurethane Foamed polyurethane
Expansion vessel Volume l 6 6
  Max. water pressure bar 3 3
  Pre pressure bar 1.0 1.0
  Heater W 50 50
Water filter Diameter perforations mm 1.0 1.0
  Material   Brass Brass
Water circuit Piping connections diameter inch G 1" (male) G 1" (male)
  Piping inch 5/4" 5/4"
  Piping length Max. OU - Tank m 10 10
  Level difference Max. m 5 5
  Safety valve bar 3 3
  Manometer   Yes Yes
  Drain valve / fill valve   Yes Yes
  Shut off valve   Yes Yes
  Air purge valve   Yes Yes
  Total water volume l 5.5 (8) 5.5 (8)
  Minimum water volume in the system l 10 (9) 10 (9)
Compressor component Main power supply Name   V3 V3
    Phase   1~ 1~
    Frequency Hz 50 50
    Voltage V 230 230
  Current Maximum running current Heating A 18 18
      Cooling A 16.25 16.25
    Starting current Heating A 11 11
      Cooling A 11 11
Voltage range Min. % -10 -10
  Max. % 10 10
Current Zmax Text Ω 0.42 0.42
  Recommended fuses A 20 20
Notes Tamb 35°C - LWE 18°C (DT=5°C) Tamb 35°C - LWE 18°C (DT=5°C)
  DB/WB 7°C/6°C - LWC 35°C (DT=5°C) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)
  Tamb 35°C - LWE 7°C (DT=5°C) Tamb 35°C - LWE 7°C (DT=5°C)
  DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
  Pump power input is included in heating and cooling power input Pump power input is included in heating and cooling power input
  The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information.
  15°C-25°C: BUH only, no heat pump operation = during commissioning 15°C-25°C: BUH only, no heat pump operation = during commissioning
  Including piping + PHE; excluding expansion vessel Including piping + PHE; excluding expansion vessel
  Excluding water volume in the unit. In most applications this minimum water volume will have a satisfying result. In critical processes or in rooms with a high heat load though, extra water volume might be required. Refer to operation range for more info. Excluding water volume in the unit. In most applications this minimum water volume will have a satisfying result. In critical processes or in rooms with a high heat load though, extra water volume might be required. Refer to operation range for more info.
  The 3-way valve should be mounted as close as possible to the outdoor unit The 3-way valve should be mounted as close as possible to the outdoor unit
  Power supply compressor compartment is for compressor, fan, pump and controller Power supply compressor compartment is for compressor, fan, pump and controller
  Minimum Ssc value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase Minimum Ssc value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase
  In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (system impedance) ≤ Zmax In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (system impedance) ≤ Zmax
  EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A
  Wiring connections: cf. connection diagram for full wiring overview; Select diameter and type according to local regulations; For more details on voltage range and current cf. EBHQ installation manual Wiring connections: cf. connection diagram for full wiring overview; Select diameter and type according to local regulations; For more details on voltage range and current cf. EBHQ installation manual
  See separate drawing for operation range See separate drawing for operation range
  Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases
  PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC