EHSXB04P30BA / ERLQ004CAV3 EHSXB08P30BA / ERLQ006CAV3 EHSXB08P50BA / ERLQ006CAV3 EHSXB08P30BA / ERLQ008CAV3 EHSXB08P50BA / ERLQ008CAV3 EHSXB16P50BA / ERLQ011CAV3 EHSXB16P50BA / ERLQ014CAV3 EHSXB16P50BA / ERLQ016CAV3
Indoor unit EHSXB04P30BA EHSXB08P30BA EHSXB08P50BA EHSXB08P30BA EHSXB08P50BA EHSXB16P50BA EHSXB16P50BA  
Heating capacity Min. kW 1.80 (1), 1.81 (2) 1.80 (1), 1.81 (2) 1.80 (1), 1.81 (2) 1.80 (1), 1.81 (2) 1.80 (1), 1.81 (2)      
  Nom. kW 4.26 (3), 3.47 (4), 4.53 (1), 3.98 (2) 5.14 (3), 4.60 (4), 6.06 (1), 5.78 (2) 5.14 (3), 4.60 (4), 6.06 (1), 5.78 (2) 5.53 (3), 5.51 (4), 7.78 (1), 7.27 (2) 5.53 (3), 5.51 (4), 7.78 (1), 7.27 (2) 5.95 (1), 7.74 (2), 11.80 (3), 10.40 (4) 14.81 (1), 13.73 (2), 8.28 (3), 9.57 (4) 15.34 (1), 14.86 (2), 8.04 (3), 10.05 (4)
  Max. kW 4.90 (1), 5.12 (2) 8.35 (1), 7.95 (2) 8.35 (1), 7.95 (2) 10.02 (1), 9.53 (2) 10.02 (1), 9.53 (2) 11.38 (3), 11.00 (4) 14.55 (5), 13.59 (6) 16.10 (5), 15.22 (6)
Cooling capacity Min. kW 2.0 (5), 2.1 (6) 2.5 (5), 2.6 (6) 2.5 (5), 2.6 (6) 2.5 (5), 2.6 (6) 2.5 (5), 2.6 (6) 2.5 (5), 2.6 (6) 2.5 (1), 2.6 (2)  
  Nom. kW 4.4 (5), 4.0 (6) 5.2 (5), 4.6 (6) 5.2 (5), 4.6 (6) 5.2 (5), 4.6 (6) 5.2 (5), 4.6 (6) 15.1 (5), 11.7 (6) 16.1 (1), 12.6 (2) 16.8 (1), 13.1 (2)
  Max. kW 5.9 (5), 4.5 (6) 7.3 (5), 5.5 (6) 7.3 (5), 5.5 (6) 8.4 (5), 6.4 (6) 8.4 (5), 6.4 (6) 15.1 (5), 11.7 (6) 16.1 (1), 12.6 (2) 16.8 (1), 13.1 (2)
Power input Heating Nom. kW 0.87 (5), 1.04 (6), 1.49 (3), 0.85 (4) 1.30 (5), 1.58 (6), 1.88 (3), 1.26 (4) 1.30 (5), 1.58 (6), 1.88 (3), 1.26 (4) 1.69 (5), 2.04 (6), 1.98 (3), 1.56 (4) 1.69 (5), 2.04 (6), 1.98 (3), 1.56 (4) 2.57 (5), 3.13 (6), 2.43 (1), 2.35 (2) 3.42 (1), 4.07 (2), 3.17 (3), 2.93 (4) 3.42 (1), 4.07 (2), 3.17 (3), 2.93 (4)
    Max. kW 1.12 (5), 1.44 (6) 1.99 (5), 2.32 (6) 1.99 (5), 2.32 (6) 2.54 (5), 2.96 (6) 2.54 (5), 2.96 (6) 2.64 (5), 3.25 (6) 3.43 (1), 4.22 (2) 3.83 (1), 4.71 (2)
  Cooling Nom. kW 1.05 (5), 1.41 (6) 1.43 (5), 1.85 (6) 1.43 (5), 1.85 (6) 1.43 (5), 1.85 (6) 1.43 (5), 1.85 (6) 4.55 (5), 4.30 (6) 5.44 (1), 5.10 (2) 6.18 (1), 5.72 (2)
    Max. kW 1.86 (5), 2.04 (6) 2.27 (5), 2.51 (6) 2.27 (5), 2.51 (6) 2.89 (5), 3.20 (6) 2.89 (5), 3.20 (6) 4.53 (5), 4.31 (6) 5.42 (1), 5.09 (2) 6.15 (1), 5.74 (2)
COP 5.23 (5), 3.84 (6), 2.85 (3), 4.07 (4) 4.65 (5), 3.66 (6), 2.73 (3), 3.64 (4) 4.65 (5), 3.66 (6), 2.73 (3), 3.64 (4) 4.60 (5), 3.57 (6), 2.78 (3), 3.54 (4) 4.60 (5), 3.57 (6), 2.78 (3), 3.54 (4) 4.38 (5), 3.32 (6), 2.45 (1), 3.29 (2) 4.27 (1), 3.34 (2), 2.58 (3), 3.22 (4)  
EER 4.21 (5), 2.85 (6) 3.65 (5), 2.51 (6) 3.65 (5), 2.51 (6) 3.65 (5), 2.51 (6) 3.65 (5), 2.51 (6) 3.32 (5), 2.72 (6) 2.96 (1), 2.47 (2)  
Water side Heat exchanger Water flow rate Cooling Nom. l/min               48.1 (7), 37.5 (8)
    Heating Nom. l/min               44.0 (9), 42.6 (10)
General LW(A) Sound power level (according to EN14825) Indoor dB(A)               39
LW(A) Sound power level (according to EN14825) Outdoor dB(A)               66
Space heating general Other Pck (Crankcase heater mode) kW               0.000
    Poff (Off mode) kW               0.050
    Psb (Standby mode) kW               0.050
    Pto (Thermostat off) kW               0.105
  Integrated supplementary heater Psup kW               9.0
Domestic hot water heating General Declared load profile   L L XL L XL XL XL  
  Average climate AEC (Annual electricity consumption) kWh               2,158
    Ƞwh (water heating efficiency) %               84
    Qelec (Daily electricity consumption) kWh               9.681
    Water heating energy efficiency class   A A A A A A A  
  Cold climate AEC (Annual electricity consumption) kWh               2,394
    Ƞwh (water heating efficiency) %               76
    Qelec (Daily electricity consumption) kWh               10.755
  Warm climate AEC (Annual electricity consumption) kWh               1,921
    Ƞwh (water heating efficiency) %               95
    Qelec (Daily electricity consumption) kWh               8.600
Space heating Average climate water outlet 55°C General Annual energy consumption kWh               8,978
      Ƞs (Seasonal space heating efficiency) %               127
      Prated at -10°C kW               14
      Seasonal space heating eff. class   A++ A++ A++ A++ A++ A++ A++  
    A Condition (-7°CDB/-8°CWB) Pdh kW               12.6
      PERd %               74.0
    B Condition (2°CDB/1°CWB) Pdh kW               7.8
      PERd %               127.6
    C Condition (7°CDB/6°CWB) Pdh kW               4.9
      PERd %               178.8
    D Condition (12°CDB/11°CWB) Pdh kW               5.4
      PERd %               260.8
    Tol (temperature operating limit) Pdh kW               11.2
      PERd %               62.8
      TOL °C               -10
      WTOL °C               55
    Rated heat output supplementary capacity Psup (at Tdesign -10°C) kW               3.0
    Tbiv (bivalent temperature) Pdh kW               12.6
      PERd %               73.6
      Tbiv °C               -7
  Cold climate water outlet 55°C General Annual energy consumption kWh               10,405
      Ƞs (Seasonal space heating efficiency) %               101
      Prated at -22°C kW               11
    A Condition (-7°CDB/-8°CWB) Pdh kW               6.6
      PERd %               82.0
    B Condition (2°CDB/1°CWB) Pdh kW               4.0
      PERd %               127.6
    C Condition (7°CDB/6°CWB) Pdh kW               5.2
      PERd %               220.0
    D Condition (12°CDB/11°CWB) Pdh kW               6.1
      PERd %               302.4
    Tol (temperature operating limit) Pdh kW               6.8
      PERd %               43.2
      TOL °C               -20
      WTOL °C               55
    G Condition (-15°CDB/-) Pdh kW               8.9
      PERd %               56.8
    Tbiv (bivalent temperature) Pdh kW               8.9
      PERd %               56.8
      Tbiv °C               -15
    Rated heat output supplementary capacity Psup (at Tdesign -22°C) kW               4.9
  Warm climate water outlet 55°C General Annual energy consumption kWh               3,429
      Ƞs (Seasonal space heating efficiency) %               154
      Prated at 2°C kW               10
    B Condition (2°CDB/1°CWB) Pdh kW               10.3
      PERd %               71.2
    C Condition (7°CDB/6°CWB) Pdh kW               6.6
      PERd %               130.0
    D Condition (12°CDB/11°CWB) Pdh kW               5.4
      PERd %               235.2
    Tbiv (bivalent temperature) Pdh kW               10.3
      PERd %               71.2
      Tbiv °C               2
Notes EW 30°C; LW 35°C; ambient conditions: 7°CDB/6°CWB EW 30°C; LW 35°C; ambient conditions: 7°CDB/6°CWB EW 30°C; LW 35°C; ambient conditions: 7°CDB/6°CWB EW 30°C; LW 35°C; ambient conditions: 7°CDB/6°CWB EW 30°C; LW 35°C; ambient conditions: 7°CDB/6°CWB EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
  EW 40°C; LW 45°C; ambient conditions: 7°CDB/6°CWB EW 40°C; LW 45°C; ambient conditions: 7°CDB/6°CWB EW 40°C; LW 45°C; ambient conditions: 7°CDB/6°CWB EW 40°C; LW 45°C; ambient conditions: 7°CDB/6°CWB EW 40°C; LW 45°C; ambient conditions: 7°CDB/6°CWB EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )
  EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB EW 30°C; LW 35°C; ambient conditions: 7°CDB/6°CWB EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB
  EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB EW 40°C; LW 45°C; ambient conditions: 7°CDB/6°CWB EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB
  Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) EW 30°C; LW 35°C; ambient conditions: 7°CDB/6°CWB EW 30°C; LW 35°C; ambient conditions: 7°CDB/6°CWB
  Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) EW 40°C; LW 45°C; ambient conditions: 7°CDB/6°CWB EW 40°C; LW 45°C; ambient conditions: 7°CDB/6°CWB
  Tamb 35°C - LWE 18°C (DT=5°C) Tamb 35°C - LWE 18°C (DT=5°C) Tamb 35°C - LWE 18°C (DT=5°C) Tamb 35°C - LWE 18°C (DT=5°C) Tamb 35°C - LWE 18°C (DT=5°C) Tamb 35°C - LWE 18°C (DT=5°C) Tamb 35°C - LWE 18°C (DT=5°C) Tamb 35°C - LWE 18°C (DT=5°C)
  Tamb 35°C - LWE 7°C (DT=5°C) Tamb 35°C - LWE 7°C (DT=5°C) Tamb 35°C - LWE 7°C (DT=5°C) Tamb 35°C - LWE 7°C (DT=5°C) Tamb 35°C - LWE 7°C (DT=5°C) Tamb 35°C - LWE 7°C (DT=5°C) Tamb 35°C - LWE 7°C (DT=5°C) Tamb 35°C - LWE 7°C (DT=5°C)
  DB/WB 7°C/6°C - LWC 35°C (DT=5°C) DB/WB 7°C/6°C - LWC 35°C (DT=5°C) DB/WB 7°C/6°C - LWC 35°C (DT=5°C) DB/WB 7°C/6°C - LWC 35°C (DT=5°C) DB/WB 7°C/6°C - LWC 35°C (DT=5°C) DB/WB 7°C/6°C - LWC 35°C (DT=5°C) DB/WB 7°C/6°C - LWC 35°C (DT=5°C) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)
  DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
Domestic hot water heating General Declared load profile               Yes
  Average climate Water heating energy efficiency class               A
Space heating general Other Capacity control               0.9
  Integrated supplementary heater Type of energy input               Electrical
Pump Pump-=-Pump type               Grundfos UPM3 25-75 CHBL
Space heating Cold climate water outlet 55°C A Condition (-7°CDB/-8°CWB) Space heating-=-Cold climate water outlet 55°C-=-A Condition (-7°CDB/-8°CWB)-=-Copd               1.0
    C Condition (7°CDB/6°CWB) Space heating-=-Cold climate water outlet 55°C-=-C Condition (7°CDB/6°CWB)-=-Copd               0.9
    Tol (temperature operating limit) Space heating-=-Cold climate water outlet 55°C-=-Tol (temperature operating limit)-=-Copd               1.08
    G Condition (-15°CDB/-) Space heating-=-Cold climate water outlet 55°C-=-G Condition (-15°CDB/-)-=-Copd               1.42
    Tbiv (bivalent temperature) Space heating-=-Cold climate water outlet 55°C-=-Tbiv (bivalent temperature)-=-Copd               1.42
    B Condition (2°CDB/1°CWB) Space heating-=-Cold climate water outlet 55°C-=-B Condition (2°CDB/1°CWB)-=-Copd               1.0
    D Condition (12°CDB/11°CWB) Space heating-=-Cold climate water outlet 55°C-=-D Condition (12°CDB/11°CWB)-=-Copd               7.56
  Warm climate water outlet 55°C Tbiv (bivalent temperature) Space heating-=-Warm climate water outlet 55°C-=-Tbiv (bivalent temperature)-=-Copd               1.78
    B Condition (2°CDB/1°CWB) Space heating-=-Warm climate water outlet 55°C-=-B Condition (2°CDB/1°CWB)-=-Copd               1.0
    C Condition (7°CDB/6°CWB) Space heating-=-Warm climate water outlet 55°C-=-C Condition (7°CDB/6°CWB)-=-Copd               1.0
    D Condition (12°CDB/11°CWB) Space heating-=-Warm climate water outlet 55°C-=-D Condition (12°CDB/11°CWB)-=-Copd               0.9
  Average climate water outlet 55°C A Condition (-7°CDB/-8°CWB) Space heating-=-Average climate water outlet 55°C-=-A Condition (-7°CDB/-8°CWB)-=-Copd               1.0
    Tbiv (bivalent temperature) Space heating-=-Average climate water outlet 55°C-=-Tbiv (bivalent temperature)-=-Copd               1.84
    Tol (temperature operating limit) Space heating-=-Average climate water outlet 55°C-=-Tol (temperature operating limit)-=-Copd               1.57
    General Space heating-=-Average climate water outlet 55°C-=-General-=-Seasonal space heating eff class               A++
    B Condition (2°CDB/1°CWB) Space heating-=-Average climate water outlet 55°C-=-B Condition (2°CDB/1°CWB)-=-Copd               1.0
    C Condition (7°CDB/6°CWB) Space heating-=-Average climate water outlet 55°C-=-C Condition (7°CDB/6°CWB)-=-Copd               1.0
    D Condition (12°CDB/11°CWB) Space heating-=-Average climate water outlet 55°C-=-D Condition (12°CDB/11°CWB)-=-Copd               0.9
General Product description General-=-Product description-=-Low temperature heat pump               Yes
Indoor unit               2.72 (1), 2.29 (2)