ERLQ004CAV3 ERLQ006CAV3 ERLQ008CAV3 ERLQ011CAV3 ERLQ014CAV3 ERLQ016CAV3
Casing Colour   Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white
  Material   Polyester painted galvanised steel plate Polyester painted galvanised steel plate Polyester painted galvanised steel plate Painted galvanized steel plate Painted galvanized steel plate Painted galvanized steel plate
Dimensions Unit Height mm 735 735 735 1,345 1,345 1,345
    Width mm 832 832 832 900 900 900
    Depth mm 307 307 307 320 320 320
  Packed unit Height mm 797 797 797 1,524 1,524 1,524
    Width mm 990 990 990 980 980 980
    Depth mm 390 390 390 420 420 420
Weight Unit kg 54 56 56 113 113 113
  Packed unit kg 57 59 59 119 119 119
Packing Material   EPS, Carton EPS, Carton EPS, Carton Wood, EPS, Carton, PE (Straps) Wood, EPS, Carton, PE (Straps) Wood, EPS, Carton, PE (Straps)
  Weight kg 3 3 3 15 15 15
Heat exchanger Length mm 845 845 845 857 857 857
  Rows Quantity   2 2 2 2 2 2
  Fin pitch mm 1.80 1.80 1.80 1.40 1.40 1.40
  Passes Quantity       7 7 7
  Face area       1.131 1.131 1.131
  Stages Quantity   32 32 32 60 60 60
  Empty tubeplate hole Quantity       0 0 0
  Tube type   ø8 Hi-XA ø8 Hi-XA ø8 Hi-XA ø8 Hi-XSS ø8 Hi-XSS ø8 Hi-XSS
  Fin Type   WF fin WF fin WF fin WF fin WF fin WF fin
    Treatment   Anti-corrosion treatment (PE) Anti-corrosion treatment (PE) Anti-corrosion treatment (PE) Anti-corrosion treatment (PE) Anti-corrosion treatment (PE) Anti-corrosion treatment (PE)
Fan Type   Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan
  Quantity   1 1 1 2 2 2
  Air flow rate Heating Nom. m³/min 45.0 47.0 47.0      
    Cooling Nom. m³/min 52.5 52.5 52.5      
  Discharge direction   Horizontal Horizontal Horizontal Horizontal Horizontal Horizontal
Fan motor Quantity   1 1 1 2 2 2
  Model       Brushless DC motor Brushless DC motor Brushless DC motor
  Output W 53.00 53.00 53.00 70.00 70.00 70.00
  Drive       Direct drive Direct drive Direct drive
  Speed Steps       8 8 8
    Heating Nom. rpm       740 750 760
    Cooling Nom. rpm       780 780 780
Compressor Quantity   1 1 1 1 1 1
  Model   2YC36BXD#C 2YC45DXD#C 2YC45DXD#C JT100G-VD@B2 JT100G-VD@B2 JT100G-VD@B2
  Type   Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor
  Output W       2,200.0 2,200.0 2,200.0
  Starting method       Inverter driven Inverter driven Inverter driven
  Motor Crankcase heater Quantity       1 1 1
      Output W       33 33 33
PED Category   Category I, Excluded from scope of PED due to article 1, item 3.6 of 97/23/EC Category I, Excluded from scope of PED due to article 1, item 3.6 of 97/23/EC Category I, Excluded from scope of PED due to article 1, item 3.6 of 97/23/EC Category I, Excluded from scope of PED due to article 1, item 3.6 of 97/23/EC Category I, Excluded from scope of PED due to article 1, item 3.6 of 97/23/EC Category I, Excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
Operation range Heating Min. °CDB -25 (1) -25 (1) -25 (1) -25 (1) -25 (1) -25 (1)
    Max. °CDB 25 25 25 35 35 35
  Cooling Min. °CDB 10.0 10.0 10.0 10.0 10.0 10.0
    Max. °CDB 43.0 43.0 43.0 46.0 46.0 46.0
  Domestic hot water Min. °CDB -25 (2) -25 (2) -25 (2) -20 (2) -20 (2) -20 (2)
    Max. °CDB 35 (2) 35 (2) 35 (2) 35 (2) 35 (2) 35 (2)
Piping connections Liquid Quantity   1 1 1 1 1 1
    Type   Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection
    OD mm 6.35 6.35 6.35 9.52 9.52 9.52
  Gas Quantity   1 1 1 1 1 1
    Type   Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection
    OD mm 15.90 15.90 15.90 15.90 15.90 15.90
  Drain Quantity   2 2 2 3 3 3
    Type   Hole Hole Hole Hole Hole Hole
    OD mm 1x ø15 + 1x ø20 1x ø15 + 1x ø20 1x ø15 + 1x ø20 26 26 26
  Drain 2 Quantity       1 1 1
    Type       Hole Hole Hole
    OD mm       18 18 18
  Piping length OU - IU Min. m 3 3 3 3 3 3
      Max. m 30 30 30 50 50 50
    System Equivalent m       70 70 70
      Chargeless m 10 10 10 10 10 10
  Additional refrigerant charge kg/m 0.02 (for piping length exceeding 10m) 0.02 (for piping length exceeding 10m) 0.02 (for piping length exceeding 10m) See installation manual See installation manual See installation manual
  Level difference IU - OU Max. m 20.0 20.0 20.0 30.0 30.0 30.0
  Heat insulation   Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Sound power level Heating Nom. dBA 61 61 62 64 (3) 64 (3) 66 (3)
  Cooling Nom. dBA 63 63 63 64 (4) 66 (4) 69 (4)
Sound pressure level Heating Nom. dBA 48 (3) 48 (3) 49 (3) 51 (5) 51 (5) 52 (5)
  Cooling Nom. dBA 48 (3) 49 (3) 50 (3) 50 (5) 52 (5) 54 (5)
  Night quiet mode Heating dBA       42 (5) 42 (5) 43 (5)
    Cooling dBA       45 (5) 45 (5) 46 (5)
Refrigerant Type   R-410A R-410A R-410A R-410A R-410A R-410A
  GWP   2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5
  Charge TCO2Eq 3.1 3.3 3.3 7.1 7.1 7.1
  Charge kg 1.5 1.6 1.6 3.4 3.4 3.4
  Control   Expansion valve (electronic type) Expansion valve (electronic type) Expansion valve (electronic type) Expansion valve (electronic type) Expansion valve (electronic type) Expansion valve (electronic type)
  Circuits Quantity   1 1 1 1 1 1
Refrigerant oil Type   FVC50K FVC50K FVC50K Daphne FVC68D Daphne FVC68D Daphne FVC68D
  Charged volume l 0.65 0.65 0.65 1.5 1.5 1.5
Defrost method Reversed cycle Reversed cycle Reversed cycle Reversed cycle Reversed cycle Reversed cycle
Defrost control Sensor for outdoor heat exchanger temperature Sensor for outdoor heat exchanger temperature Sensor for outdoor heat exchanger temperature Sensor for outdoor heat exchanger temperature Sensor for outdoor heat exchanger temperature Sensor for outdoor heat exchanger temperature
Capacity control Method   Inverter controlled Inverter controlled Inverter controlled Inverter controlled Inverter controlled Inverter controlled
Safety devices Item 01       High pressure switch High pressure switch High pressure switch
    02       Fan motor thermal protection Fan motor thermal protection Fan motor thermal protection
    03       Fuse Fuse Fuse
Power supply Name   V3 V3 V3 V3 V3 V3
  Phase   1~ 1~ 1~ 1~ 1~ 1~
  Frequency Hz 50 50 50 50 50 50
  Voltage V 230 230 230 230 230 230
  Voltage range Min. % -10 -10 -10 -10 -10 -10
    Max. % 10 10 10 10 10 10
Current Zmax Text Ω       0.22 0.22 0.22
  Minimum Ssc value kVa       Equipment complying with EN / IEC 61000-3-12 Equipment complying with EN / IEC 61000-3-12 Equipment complying with EN / IEC 61000-3-12
  Starting current Heating A 15.7 (4) 15.7 (4) 15.9 (4)      
    Cooling A 15.7 (4) 15.7 (4) 15.9 (4)      
  Maximum running current Heating A 15.7 15.7 15.9      
    Cooling A 15.7 15.7 15.9 34.2 34.2 34.2
  Recommended fuses A 16 16 20 40 40 40
Wiring connections For power supply Quantity   3 3 3      
    Remark       See installation manual outdoor unit See installation manual outdoor unit See installation manual outdoor unit
  For connection with indoor Quantity   3 3 3      
    Remark   No earth wiring No earth wiring No earth wiring See installation manual outdoor unit See installation manual outdoor unit See installation manual outdoor unit
Power supply intake       Outdoor unit only Outdoor unit only Outdoor unit only
Notes (1) - Operation range heating (outdoor unit): range increase by support back-up heater. See separate drawing for operation range. (1) - Operation range heating (outdoor unit): range increase by support back-up heater. See separate drawing for operation range. (1) - Operation range heating (outdoor unit): range increase by support back-up heater. See separate drawing for operation range. (1) - Operation range heating (outdoor unit): range increase by support back-up heater. See separate drawing for operation range. (1) - Operation range heating (outdoor unit): range increase by support back-up heater. See separate drawing for operation range. (1) - Operation range heating (outdoor unit): range increase by support back-up heater. See separate drawing for operation range.
  (2) - Operation range domestic hot water (outdoor unit): range increase by support booster heater or backup heater. See separate drawing for operation range. (2) - Operation range domestic hot water (outdoor unit): range increase by support booster heater or backup heater. See separate drawing for operation range. (2) - Operation range domestic hot water (outdoor unit): range increase by support booster heater or backup heater. See separate drawing for operation range. (2) - Operation range domestic hot water (outdoor unit): range increase by support booster heater or backup heater. See separate drawing for operation range. (2) - Operation range domestic hot water (outdoor unit): range increase by support booster heater or backup heater. See separate drawing for operation range. (2) - Operation range domestic hot water (outdoor unit): range increase by support booster heater or backup heater. See separate drawing for operation range.
  (3) - The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. (3) - The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. (3) - The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. (3) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (3) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (3) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
  (4) - Daikin Altherma inverter controlled compressor starting current always <= max. running current (4) - Daikin Altherma inverter controlled compressor starting current always <= max. running current (4) - Daikin Altherma inverter controlled compressor starting current always <= max. running current (4) - Condition: Ta 35°C - LWE 7°C ( DT = 5°C) (4) - Condition: Ta 35°C - LWE 7°C ( DT = 5°C) (4) - Condition: Ta 35°C - LWE 7°C ( DT = 5°C)
  (5) - Contains fluorinated greenhouse gases (5) - Contains fluorinated greenhouse gases (5) - Contains fluorinated greenhouse gases (5) - The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. (5) - The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. (5) - The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information.
        (6) - Contains fluorinated greenhouse gases (6) - Contains fluorinated greenhouse gases (6) - Contains fluorinated greenhouse gases