FBA100A2VEB / RZQSG100L8Y1B FBA125A2VEB / RZQSG125L8Y1B FBA140A2VEB / RZQSG140L7Y1B
Indoor unit FBA100A2VEB FBA125A2VEB FBA140A2VEB
Outdoor unit RZQSG100L8Y1 RZQSG125L8Y1 RZQSG140LY1
Cooling capacity Nom. kW 9.50 (1) 12.0 (1) 13.4 (1)
Heating capacity Nom. kW 10.8 (2) 13.5 (2) 15.5 (2)
Power input Cooling Nom. kW 2.84 (3) 3.72 (3) 5.89 (3)
  Heating Nom. kW 2.94 (3) 3.72 (3) 4.56 (3)
Nominal efficiency EER   3.35 (3) 3.23 (3) 2.28 (3)
  COP   3.67 (3) 3.63 (3) 3.40 (3)
  Annual energy consumption kWh 1,418 (0.000) 1,858 (0.000)  
  Energy labeling Directive Cooling   A A  
    Heating   A A  
Space cooling Energy efficiency class   A+ A  
  Capacity Pdesign kW 9.50 12.0 13.4
  SEER   5.61 5.47 5.23
  ηs,c %     206.3
  Annual energy consumption kWh/a 593 768 1,537
  A Condition (35°C - 27/19) Pdc kW 9.50 12.00 13.40
    EERd   3.35 3.23 2.28
    Power input kW 2.84 3.72 5.89
  B Condition (30°C - 27/19) Pdc kW 7.00 8.84 9.88
    EERd   4.83 3.70 4.02
    Power input kW 1.45 2.39 2.46
  C Condition (25°C - 27/19) Pdc kW 4.50 5.68 6.35
    EERd   7.05 7.38 6.56
    Power input kW 0.64 0.77 0.97
  D Condition (20°C - 27/19) Pdc kW 3.94 3.95 5.95
    EERd   9.04 9.51 8.56
    Power input kW 0.44 0.42 0.69
Space heating (Average climate) Energy efficiency class   A+ A+  
  Capacity Pdesign kW 7.60 7.60 11.6
  SCOP/A   4.15 4.01 3.81
  SCOPnet/A   4.19 4.05 3.81
  ηs,h %     149.3
  Pdh Heating capacity at -10° kW 6 6  
  Annual energy consumption kWh/a 2,564 2,653 4,255
  Required back up heating cap at design conditions kW 1.84 1.82 0.00
  TOL Tol (temperature operating limit) °C -15 -15 -10
    Pdh (declared heating cap) kW 4.16 4.21 11.57
    COPd (declared COP)   2.11 2.24 2.15
    Power input kW 1.97 1.88 5.38
  TBivalent Tbiv (bivalent temperature) °C -7 -7 -10
    Pdh (declared heating cap) kW 6.72 6.72 11.57
    COPd (declared COP)   2.98 2.83 2.15
    Power input kW 2.26 2.37 5.38
  A Condition (-7°C) Pdh (declared heating cap) kW 6.72 6.72 10.24
    COPd (declared COP)   2.98 2.83 2.54
    Power input kW 2.26 2.37 4.03
  B Condition (2°C) Pdh (declared heating cap) kW 4.09 4.09 6.23
    COPd (declared COP)   4.32 4.32 3.77
    Power input kW 0.95 0.95 1.65
  C Condition (7°C) Pdh (declared heating cap) kW 2.82 2.85 4.11
    COPd (declared COP)   4.70 4.35 4.84
    Power input kW 0.60 0.66 0.85
  D Condition (12°C) Pdh (declared heating cap) kW 2.93 2.94 4.79
    COPd (declared COP)   5.95 5.46 5.73
    Power input kW 0.49 0.54 0.84
Power consumption in other than active mode Crankcase heater mode Cooling PCK kW 0.000 0.000 0.000
    Heating PCK kW 0.000 0.000 0.014
  Off mode Cooling POFF kW 0.022 0.022 0.014
    Heating POFF kW 0.022 0.022 0.014
  Standby mode Cooling PSB kW 0.022 0.022 0.014
    Heating PSB kW 0.022 0.022 0.014
  Thermostat-off mode Cooling PTO kW 0.004 0.004 0.000
    Heating PTO kW 0.004 0.004 0.014
Indication if the heater is equipped with a supplementary heater (pair application)     No
Supplementary heater (pair application) Back-up capacity Heating elbu kW     0.0
Cooling Cdc (Degradation cooling)   0.25 0.25 0.25
Heating Cdh (Degradation heating)   0.25 0.25 0.25
Cooling function included Yes Yes Yes
Heating function included Yes Yes Yes
Average climate included Yes Yes Yes
Cold season included No No No
Warm season included No No No
Ecolabel logo No No No
Notes Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  EER/COP according to Eurovent 2012, for use outside EU only EER/COP according to Eurovent 2012, for use outside EU only EER/COP according to Eurovent 2012, for use outside EU only