FBQ35C8VEB / RXS35L3V1B
Poff (Off mode) W 14.0
Cooling Psb (Standby mode cooling) W 14.0
  Cooling-=-Cooling cdc degradation cooling 0.25
Seasonal efficiency (according to EN14825) Cooling Pdesign kW 3.50
    Annual energy consumption kWh 205
    Seasonal efficiency (according to EN14825)-=-Cooling-=-Seasonal efficiency according to en14825 cooling energy efficiency class 5.97
    D Condition (20°C - 27/19) Pdc kW 1.70
      power input kW 0.16
      Seasonal efficiency (according to EN14825)-=-Cooling-=-D Condition (20°C - 27/19)-=-Eerd 10.92
    C Condition (25°C - 27/19) power input kW 0.20
      Pdc kW 1.66
      Seasonal efficiency (according to EN14825)-=-Cooling-=-C Condition (25°C - 27/19)-=-Eerd 8.26
    A Condition (35°C - 27/19) power input kW 0.95
      Pdc kW 3.50
      Seasonal efficiency (according to EN14825)-=-Cooling-=-A Condition (35°C - 27/19)-=-Eerd 3.70
    B Condition (30°C - 27/19) Pdc kW 2.58
      power input kW 0.47
      Seasonal efficiency (according to EN14825)-=-Cooling-=-B Condition (30°C - 27/19)-=-Eerd 5.48
  Heating (Average climate) Annual energy consumption kWh 1,033
    Pdesign kW 2.90
    Required back up heating cap at design conditions kW 0.51
    Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-Seasonal efficiency according to en14825 heating average climate scopnet a A+
    TBivalent Pdh (declared heating cap) kW 2.57
      Power input kW 1.07
      Tbiv (bivalent temperature) °C -7
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TBivalent-=-Copd declared cop 2.41
    C Condition (7°C) Pdh (declared heating cap) kW 1.02
      Power input kW 0.21
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-C Condition (7°C)-=-Copd declared cop 4.78
    TOL Tol (temperature operating limit) °C -15
      Pdh (declared heating cap) kW 2.12
      Power input kW 1.09
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TOL-=-Copd declared cop 1.95
    A Condition (-7°C) Pdh (declared heating cap) kW 2.57
      Power input kW 1.07
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-A Condition (-7°C)-=-Copd declared cop 2.41
    D Condition (12°C) Pdh (declared heating cap) kW 1.19
      Power input kW 0.19
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-D Condition (12°C)-=-Copd declared cop 6.31
    B Condition (2°C) Power input kW 0.38
      Pdh (declared heating cap) kW 1.57
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-B Condition (2°C)-=-Copd declared cop 4.09
Cooling capacity Nom. Btu/h 11,590 (2)
  Min. kW 1.4
  Nom. kcal/h 2,920 (2)
  Max. kW 3.9
  Min. kcal/h 1,200
  Min. Btu/h 4,770
  Nom. kW 3.40 (2)
  Max. Btu/h 13,300
  Max. kcal/h 3,350
Pck (Crankcase heater mode) W 0.0
Nominal efficiency Annual energy consumption kWh 459 (0.000)
  Energy labeling Directive Heating A
  Nominal efficiency-=-Cop 3.70
Heating Heating-=-Heating cdh degradation heating 0.25
Piping connections Liquid OD mm 6.35
  Gas OD mm 9.5
  Drain OD mm VP25 (External dia.32, internal dia. 25)
  Heat insulation Both liquid and gas pipes
Heating capacity Min. Btu/h 4,430
  Nom. Btu/h 13,640 (2)
  Max. kcal/h 4,300
  Max. Btu/h 17,050
  Nom. kW 4.00 (2)
  Min. kW 1.3
  Nom. kcal/h 3,440 (2)
  Min. kcal/h 1,120
  Max. kW 5.0
Pto (Thermostat off) W 7.0
Power input Cooling Min. kW 0.490
    Nom. kW 0.918 (2)
    Max. kW 1.490
  Heating Max. kW 1.760
    Min. kW 0.270
    Nom. kW 1.110 (2)
Indoor unit Yes
Current Nominal running current (RLA) - 50Hz Heating A 5.20 (3), 5.00 (4), 4.80 (5)
    Cooling A 4.16 (3), 3.98 (4), 3.81 (5)
Notes EER/COP according to Eurovent 2012, for use outside EU only
  Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load
  220V
  230V
  240V