FBQ71C8VEB / RZQG71L9V1B FBQ100C8VEB / RZQG100L9V1B FBQ125C8VEB / RZQG125L9V1B
Poff (Off mode) W 0.0    
Cooling Psb (Standby mode cooling) W 7.0    
  Cooling-=-Cooling cdc degradation cooling 0.25    
Seasonal efficiency (according to EN14825) Cooling Pdesign kW 6.80    
    Annual energy consumption kWh 390    
    Seasonal efficiency (according to EN14825)-=-Cooling-=-Seasonal efficiency according to en14825 cooling energy efficiency class 5.61, 6.11    
    D Condition (20°C - 27/19) Pdc kW 4.06    
      power input kW 0.40    
      Seasonal efficiency (according to EN14825)-=-Cooling-=-D Condition (20°C - 27/19)-=-Eerd 10.18    
    C Condition (25°C - 27/19) power input kW 0.50    
      Pdc kW 3.92    
      Seasonal efficiency (according to EN14825)-=-Cooling-=-C Condition (25°C - 27/19)-=-Eerd 7.89    
    A Condition (35°C - 27/19) power input kW 1.95    
      Pdc kW 6.80    
      Seasonal efficiency (according to EN14825)-=-Cooling-=-A Condition (35°C - 27/19)-=-Eerd 3.50    
    B Condition (30°C - 27/19) Pdc kW 5.01    
      power input kW 1.05    
      Seasonal efficiency (according to EN14825)-=-Cooling-=-B Condition (30°C - 27/19)-=-Eerd 4.78    
  Heating (Average climate) Annual energy consumption kWh 2,095    
    Pdesign kW 6.00    
    Required back up heating cap at design conditions kW 0.28    
    Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-Seasonal efficiency according to en14825 heating average climate scopnet a A+    
    TBivalent Pdh (declared heating cap) kW 5.31    
      Power input kW 1.89    
      Tbiv (bivalent temperature) °C -7    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TBivalent-=-Copd declared cop 2.81    
    C Condition (7°C) Pdh (declared heating cap) kW 2.85    
      Power input kW 0.60    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-C Condition (7°C)-=-Copd declared cop 4.76    
    TOL Tol (temperature operating limit) °C -15    
      Pdh (declared heating cap) kW 6.38    
      Power input kW 3.23    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TOL-=-Copd declared cop 1.98    
    A Condition (-7°C) Pdh (declared heating cap) kW 5.31    
      Power input kW 1.89    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-A Condition (-7°C)-=-Copd declared cop 2.81    
    D Condition (12°C) Pdh (declared heating cap) kW 3.24    
      Power input kW 0.60    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-D Condition (12°C)-=-Copd declared cop 5.48    
    B Condition (2°C) Power input kW 0.76    
      Pdh (declared heating cap) kW 3.23    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-B Condition (2°C)-=-Copd declared cop 4.26    
Cooling capacity Nom. kW 6.8 9.5 12.0
Pck (Crankcase heater mode) W 0.0    
Nominal efficiency Annual energy consumption kWh 970 (0.000) 1,220 1,575
  Energy labeling Directive Heating A    
  Nominal efficiency-=-Cop 3.50    
Heating Psb (Standby mode heating) W 7.0    
  Heating-=-Heating cdh degradation heating 0.25    
Heating capacity Nom. kW 7.5 10.8 13.5
Pto (Thermostat off) W 7.0    
Cold season included Yes    
Notes EER/COP according to Eurovent 2012, for use outside EU only (1) - EER/COP according to Eurovent 2012, for use outside EU only (1) - EER/COP according to Eurovent 2012, for use outside EU only
  Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load (2) - Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load (2) - Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load
Nominal efficiency EER     3.89 3.81
  COP     4.21 3.83
  Energy labeling Directive Cooling     A A
    Heating     A A
Space cooling Energy efficiency class     A+ A+
  Capacity Pdesign kW   9.50 12.00
  SEER     5.80 5.81
  Annual energy consumption kWh/a   574 723
Space heating (Average climate) Energy efficiency class     A++ A+
  Capacity Pdesign kW   11.30 12.71
  SCOP/A     4.61 4.21