FCAG35AVEB / RXS35L3V1B
Indoor unit FCAG35AVEB
Outdoor unit RXS35L3V1B
Cooling capacity Nom. kW 3.40
  Nom. Btu/h 11,590.0
  Nom. kcal/h 2,920.0
Heating capacity Nom. kW 4.20
  Nom. Btu/h 14,320.0
  Nom. kcal/h 3,610.0
Power input Cooling Nom. kW 0.91
  Heating Nom. kW 1.20
Nominal efficiency EER   3.74
  COP   3.50
  Annual energy consumption kWh 455 (0.000)
  Energy labeling Directive Cooling   A
    Heating   B
Space cooling Energy efficiency class   A++
  Capacity Pdesign kW 3.50
  SEER   6.35
  Annual energy consumption kWh/a 193
  A Condition (35°C - 27/19) Pdc kW 3.50
    EERd   3.74
    Power input kW 0.94
  B Condition (30°C - 27/19) Pdc kW 2.58
    EERd   5.87
    Power input kW 0.44
  C Condition (25°C - 27/19) Pdc kW 1.65
    EERd   8.84
    Power input kW 0.19
  D Condition (20°C - 27/19) Pdc kW 1.53
    EERd   12.20
    Power input kW 0.13
Space heating (Average climate) Energy efficiency class   A++
  Capacity Pdesign kW 3.32
  SCOP/A   4.90
  SCOPnet/A   4.96
  Pdh Heating capacity at -10° kW 2.60
  Annual energy consumption kWh/a 949
  Required back up heating cap at design conditions kW 0.72
  TOL Tol (temperature operating limit) °C -15
    Pdh (declared heating cap) kW 2.04
    COPd (declared COP)   2.46
    Power input kW 0.83
  TBivalent Tbiv (bivalent temperature) °C -7
    Pdh (declared heating cap) kW 2.94
    COPd (declared COP)   2.93
    Power input kW 1.00
  A Condition (-7°C) Pdh (declared heating cap) kW 2.94
    COPd (declared COP)   2.93
    Power input kW 1.00
  B Condition (2°C) Pdh (declared heating cap) kW 1.79
    COPd (declared COP)   5.09
    Power input kW 0.35
  C Condition (7°C) Pdh (declared heating cap) kW 1.15
    COPd (declared COP)   6.15
    Power input kW 0.19
  D Condition (12°C) Pdh (declared heating cap) kW 1.29
    COPd (declared COP)   7.97
    Power input kW 0.16
Power consumption in other than active mode Standby mode Cooling PSB W 14.0
  Crankcase heater mode PCK W 0.0
  Off mode POFF W 14.0
Pto (Thermostat off) W 7.0
Cooling Cdc (Degradation cooling)   0.25
Heating Cdh (Degradation heating)   0.25
Cooling function included Yes
Heating function included Yes
Average climate included Yes
Cold season included No
Warm season included No
Ecolabel logo No
Piping connections Liquid OD mm 6,35
  Gas OD mm 9.50
  Drain OD mm VP25 (External dia.32, internal dia. 25)
  Heat insulation   Both liquid and gas pipes
Eurovent Sound power level outdoor Cooling Nom. dBA 61
  Sound power level indoor Cooling Nom. dBA 49
  Piping length Cooling Measuring condition m 5.0
Notes Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
  See separate drawing for operation range
  See separate drawing for electrical data