Specifications Table for FCAHG-G / RZQSG-L3/9V1

FCAHG71GVEB / RZQSG71L3V1B FCAHG100GVEB / RZQSG100L9V1B FCAHG125GVEB / RZQSG125L9V1B FCAHG140GVEB / RZQSG140L9V1B
Cooling capacity Nom. kW 6.80 (1) 9.50 (1) 12.0 (1) 13.4 (1)
Heating capacity Nom. kW 7.50 (2) 10.8 (2) 13.5 (2) 15.5 (2)
Nominal efficiency EER   3.50 (3) 3.70 (3) 3.23 (3) 3.11 (3)
  COP   4.10 (3) 4.30 (3) 3.75 (3) 3.61 (3)
  Annual energy consumption kWh 970 1,285 1,855  
  Energy labeling Directive Cooling   A A A  
    Heating   A A A  
Space cooling Energy efficiency class   A++ A++ A  
  Capacity Pdesign kW 6.80 9.50 12.0  
  SEER   6.50 6.70 5.40  
  Annual energy consumption kWh/a 367 497 778  
Space heating (Average climate) Energy efficiency class   A+ A+ A+  
  Capacity Pdesign kW 7.60 8.03 8.03  
  SCOP/A   4.15 4.30 4.10  
  Annual energy consumption kWh/a 2,563 2,615 2,742  
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - EER/COP according to Eurovent 2012, for use outside EU only (3) - EER/COP according to Eurovent 2012, for use outside EU only (3) - EER/COP according to Eurovent 2012, for use outside EU only EER/COP according to Eurovent 2012, for use outside EU only