FCQG60FVEB / RXS60F4V1B FCQG60FVEB / RXS60F3V1B
Poff (Off mode) W 20.0  
Cooling Psb (Standby mode cooling) W 20.0  
Seasonal efficiency (according to EN14825) Cooling Pdesign kW 5.70  
    Annual energy consumption kWh 347  
    Seasonal efficiency (according to EN14825)-=-Cooling-=-Seasonal efficiency according to en14825 cooling energy efficiency class 5.74  
    D Condition (20°C - 27/19) Pdc kW 2.35  
      power input kW 0.20  
      Seasonal efficiency (according to EN14825)-=-Cooling-=-D Condition (20°C - 27/19)-=-Eerd 11.44  
    C Condition (25°C - 27/19) power input kW 0.33  
      Pdc kW 2.69  
      Seasonal efficiency (according to EN14825)-=-Cooling-=-C Condition (25°C - 27/19)-=-Eerd 8.05  
    A Condition (35°C - 27/19) power input kW 1.69  
      Pdc kW 5.70  
      Seasonal efficiency (according to EN14825)-=-Cooling-=-A Condition (35°C - 27/19)-=-Eerd 3.37  
    B Condition (30°C - 27/19) Pdc kW 4.20  
      power input kW 0.79  
      Seasonal efficiency (according to EN14825)-=-Cooling-=-B Condition (30°C - 27/19)-=-Eerd 5.34  
  Heating (Average climate) Annual energy consumption kWh 1,704  
    Pdesign kW 4.71  
    Required back up heating cap at design conditions kW 0.94  
    Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-Seasonal efficiency according to en14825 heating average climate scop a A  
    TBivalent Pdh (declared heating cap) kW 4.17  
      Power input kW 2.01  
      Tbiv (bivalent temperature) °C -7  
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TBivalent-=-Copd declared cop 2.07  
    C Condition (7°C) Pdh (declared heating cap) kW 1.64  
      Power input kW 0.33  
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-C Condition (7°C)-=-Copd declared cop 4.92  
    TOL Tol (temperature operating limit) °C -15  
      Pdh (declared heating cap) kW 3.09  
      Power input kW 1.88  
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TOL-=-Copd declared cop 1.64  
    A Condition (-7°C) Pdh (declared heating cap) kW 4.17  
      Power input kW 2.01  
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-A Condition (-7°C)-=-Copd declared cop 2.07  
    D Condition (12°C) Pdh (declared heating cap) kW 1.81  
      Power input kW 0.29  
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-D Condition (12°C)-=-Copd declared cop 6.21  
    B Condition (2°C) Power input kW 0.60  
      Pdh (declared heating cap) kW 2.53  
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-B Condition (2°C)-=-Copd declared cop 4.21  
Cooling capacity Nom. kW 5.70 5.70 (3)
Pck (Crankcase heater mode) W 0.0  
Nominal efficiency Annual energy consumption kWh 820 (0.000) 820 (0.000)
  Energy labeling Directive Heating A A
  Nominal efficiency-=-Cop 3.48 3.48
Heating Psb (Standby mode heating) W 20.0  
Piping connections Liquid OD mm 6.35  
  Gas OD mm 12.7  
  Drain OD mm VP20 (External dia.26, Internal dia. 20)  
  Heat insulation Both liquid and gas pipes  
Heating capacity Nom. kW 7.00 7.00 (4)
Pto (Thermostat off) W 80.0  
Power input Cooling Nom. kW 1.64 1.64
  Heating Nom. kW 1.99 1.99
Cold season included Yes  
Current Nominal running current (RLA) - 50Hz Cooling A 9.6  
Notes EER/COP according to Eurovent 2012, for use outside EU only Energy label: scale from A (most efficient) to G (less efficient)
  Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions)
    Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m
    Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m
    Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load