FCQG71FVEB / RZQG71L8Y1B FCQG100FVEB / RZQG71L8Y1B FCQG100FVEB / RZQG100L8Y1B FCQG140FVEB / RZQG100L8Y1B FCQG125FVEB / RZQG125L8Y1B FCQG140FVEB / RZQG125L8Y1B FCQG140FVEB / RZQG140L7Y1B
Poff (Off mode) W 0.0   0   0    
Cooling Psb (Standby mode cooling) W 9.1   9   9    
  Cooling-=-Cooling cdc degradation cooling 0.25   0.25   0.25    
Eurovent Sound power level indoor Cooling Nom. dBA 51            
  Sound power level outdoor Cooling Nom. dBA 64            
Seasonal efficiency (according to EN14825) Cooling Pdesign kW 6.80   9.5   12    
    Annual energy consumption kWh 355   489   700    
    Seasonal efficiency (according to EN14825)-=-Cooling-=-Seasonal efficiency according to en14825 cooling energy efficiency class 6.72   6.8   6    
    D Condition (20°C - 27/19) Pdc kW 3.96   5.78   5.62    
      power input kW 0.31   0.5   0.59    
      Seasonal efficiency (according to EN14825)-=-Cooling-=-D Condition (20°C - 27/19)-=-Eerd 13.06   11.56   9.6    
    C Condition (25°C - 27/19) power input kW 0.40   0.63   0.81    
      Pdc kW 3.85   5.59   5.91    
      Seasonal efficiency (according to EN14825)-=-Cooling-=-C Condition (25°C - 27/19)-=-Eerd 9.86   8.89   7.31    
    A Condition (35°C - 27/19) power input kW 2.01   2.46   3.24    
      Pdc kW 6.80   9.5   12    
      Seasonal efficiency (according to EN14825)-=-Cooling-=-A Condition (35°C - 27/19)-=-Eerd 3.39   3.87   3.71    
    B Condition (30°C - 27/19) Pdc kW 5.05   7   8.84    
      power input kW 1.14   1.34   1.99    
      Seasonal efficiency (according to EN14825)-=-Cooling-=-B Condition (30°C - 27/19)-=-Eerd 4.46   5.23   4.46    
  Heating (Average climate) Annual energy consumption kWh 2,110   3,432   4,323    
    Pdh Heating capacity at -10° kW 5.99            
    Pdesign kW 6.33   11.3   12.66    
    Required back up heating cap at design conditions kW 0.34   1.65   1.52    
    Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-Seasonal efficiency according to en14825 heating average climate scopnet a A+   A++   A+    
    TBivalent Pdh (declared heating cap) kW 5.60   10   11.2    
      Power input kW 1.98   2.81   4.63    
      Tbiv (bivalent temperature) °C -7   -7   -7    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TBivalent-=-Copd declared cop 2.84   3.57   2.42    
    C Condition (7°C) Pdh (declared heating cap) kW 2.87   4.17   4.7    
      Power input kW 0.42   0.62   0.71    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-C Condition (7°C)-=-Copd declared cop 6.96   6.8   6.64    
    TOL Tol (temperature operating limit) °C -15   -15   -15    
      Pdh (declared heating cap) kW 6.63   9.06   11.04    
      Power input kW 3.30   3.5   6.07    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TOL-=-Copd declared cop 2.01   2.59   1.82    
    A Condition (-7°C) Pdh (declared heating cap) kW 5.60   10   11.2    
      Power input kW 1.98   2.81   4.63    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-A Condition (-7°C)-=-Copd declared cop 2.84   3.57   2.42    
    D Condition (12°C) Pdh (declared heating cap) kW 3.27   4.77   5.35    
      Power input kW 0.41   0.61   0.71    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-D Condition (12°C)-=-Copd declared cop 8.03   7.87   7.6    
    B Condition (2°C) Power input kW 1.18   1.62   1.9    
      Pdh (declared heating cap) kW 4.60   6.42   7.06    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-B Condition (2°C)-=-Copd declared cop 3.91   3.97   3.72    
Cooling capacity Nom. kW 6.8   9.5   12.0   13.4
Pck (Crankcase heater mode) W 0.0   0   0    
Nominal efficiency Annual energy consumption kWh 1,005 (0.000)   1,225 (0.000)   1,610 (0.000)    
  Energy labeling Directive Heating A   A   A    
  Nominal efficiency-=-Cop 3.39   3.87   3.73   3.21
Heating Psb (Standby mode heating) W 9.1   9   9    
  Heating-=-Heating cdh degradation heating 0.25   0.25   0.25    
Heating capacity Nom. kW 7.5   10.8   13.5   15.5
Pto (Thermostat off) W 7.0 7.0 9 9.0 9 9.0  
Power input Cooling Nom. kW 2.01   2.45   3.22   4.17
  Heating Nom. kW 1.89   2.60   3.72   4.30
Indoor unit Yes   Yes   Yes   RZQG140LY1
Notes Annual energy consumption is according to Energy labeling directive 2002/31/EC   EER/COP according to Eurovent 2012, for use outside EU only   EER/COP according to Eurovent 2012, for use outside EU only   EER/COP according to Eurovent 2012, for use outside EU only
  SEER and SCOP are according to EN 14825   Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load   Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load   Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load
Indoor unit   FCQG100F   FCQG140F   FCQG140F  
Outdoor unit   RZQG71L8Y1   RZQG100L8Y1   RZQG125L8Y1  
Space cooling Energy efficiency class     A++   A++   A+  
  Capacity Pdesign kW   6.80   9.50   12.00  
  SEER     6.80   6.80   6.00  
  Annual energy consumption kWh/a   350   489   700  
  A Condition (35°C - 27/19) Pdc kW   6.80   9.50   12.00  
    EERd     3.39   3.87   3.71  
    Power input kW   2.01   2.46   3.24  
  B Condition (30°C - 27/19) Pdc kW   5.05   7.00   8.84  
    EERd     4.46   5.23   4.46  
    Power input kW   1.14   1.34   1.99  
  C Condition (25°C - 27/19) Pdc kW   3.85   5.59   5.91  
    EERd     9.86   8.89   7.31  
    Power input kW   0.40   0.63   0.81  
  D Condition (20°C - 27/19) Pdc kW   3.96   5.78   5.62  
    EERd     13.06   11.56   9.60  
    Power input kW   0.31   0.50   0.59  
Space heating (Average climate) Energy efficiency class     A+   A++   A+  
  Capacity Pdesign kW   6.33   11.30   12.66  
  SCOP/A     4.20   4.61   4.10  
  SCOPnet/A     4,212.00   4,642.00   4.12  
  Annual energy consumption kWh/a   2,110   3,432   4,323  
  Required back up heating cap at design conditions kW   0.34   1.65   1.52  
  TOL Tol (temperature operating limit) °C   -15   -15   -15  
    Pdh (declared heating cap) kW   6.63   9.06   11.04  
    COPd (declared COP)     2.01   2.59   1.82  
    Power input kW   3.30   3.50   6.07  
  TBivalent Tbiv (bivalent temperature) °C   -7   -7   -7  
    Pdh (declared heating cap) kW   5.60   10.00   11.20  
    COPd (declared COP)     2.84   3.57   2.42  
    Power input kW   1.98   2.81   4.63  
  A Condition (-7°C) Pdh (declared heating cap) kW   5.60   10.00   11.20  
    COPd (declared COP)     2.84   3.57   2.42  
    Power input kW   1.98   2.81   4.63  
  B Condition (2°C) Pdh (declared heating cap) kW   4.60   6.42   7.06  
    COPd (declared COP)     3.91   3.97   3.72  
    Power input kW   1.18   1.62   1.90  
  C Condition (7°C) Pdh (declared heating cap) kW   2.87   4.17   4.70  
    COPd (declared COP)     6.96   6.80   6.64  
    Power input kW   0.42   0.62   0.71  
  D Condition (12°C) Pdh (declared heating cap) kW   3.27   4.77   5.35  
    COPd (declared COP)     8.03   7.87   7.60  
    Power input kW   0.41   0.61   0.71  
Power consumption in other than active mode Standby mode Cooling PSB W   7.0   9.0   9.0  
    Heating PSB W   7.0   9.0   9.0  
  Crankcase heater mode PCK W   0.0   0.0   0.0  
  Off mode POFF W   0.0   0.0   0.0  
Cooling Cdc (Degradation cooling)     0.25   0.25   0.25  
Heating Cdh (Degradation heating)     0.25   0.25   0.25  
Cooling function included   Yes   Yes   Yes  
Heating function included   Yes   Yes   Yes  
Average climate included   Yes   Yes   Yes  
Cold season included   No   No   No  
Warm season included   No   No   No  
Ecolabel logo   No   No   No