FCQHG100FVEB / RZQG71L9V1B FCQHG71FVEB / RZQG71L9V1B FCQHG140FVEB / RZQG100L9V1B FCQHG100FVEB / RZQG100L9V1B FCQHG140FVEB / RZQG125L9V1B FCQHG125FVEB / RZQG125L9V1B FCQHG140FVEB / RZQG140L9V1B
Indoor unit FCQHG100F FCQHG71F FCQHG140F FCQHG100F FCQHG140F FCQHG125F FCQHG140F
Outdoor unit RZQG71L9V1 RZQG71L9V1 RZQG100L9V1 RZQG100L9V1 RZQG125L9V1 RZQG125L9V1 RZQG140L9V1
Cooling capacity Nom. kW   6.8   9.5   12.0 13.4
Heating capacity Nom. kW   7.5   10.8   13.5 15.5
Power input Cooling Nom. kW   1.66   2.15   3.00 4.00
  Heating Nom. kW   1.56   2.16   3.07 3.77
Nominal efficiency EER   4.09   4.42   4.00 3.35
  COP   4.80   4.99   4.40 4.12
  Annual energy consumption kWh   830 (0.000)   1,075 (0.000)   1,500 (0.000)  
  Energy labeling Directive Cooling   A   A   A  
    Heating   A   A   A  
Space cooling Energy efficiency class   A++ A++ A++ A++ A++ A++  
  Capacity Pdesign kW 6.80 6.80 9.50 9.50 12.00 12.00  
  SEER   7.00 6.91 7.00 7.00 6.61 6.61  
  Annual energy consumption kWh/a 340 345 475 475 636 636  
  A Condition (35°C - 27/19) Pdc kW 6.80 6.80 9.50 9.50 12.00 12.00  
    EERd   4.09 4.09 4.42 4.42 3.94 3.81  
    Power input kW 1.67 1.67 2.15 2.15 3.05 3.15  
  B Condition (30°C - 27/19) Pdc kW 5.01 5.01 7.00 7.00 8.84 7.00  
    EERd   6.12 6.12 5.92 5.92 4.82 5.61  
    Power input kW 0.82 0.82 1.19 1.19 1.84 1.25  
  C Condition (25°C - 27/19) Pdc kW 4.12 4.12 5.79 5.79 6.00 5.89  
    EERd   8.56 8.56 8.66 8.66 8.27 6.54  
    Power input kW 0.49 0.49 0.67 0.67 0.73 0.91  
  D Condition (20°C - 27/19) Pdc kW 4.33 4.33 6.05 6.05 5.73 5.87  
    EERd   11.63 11.63 11.24 11.24 10.76 7.87  
    Power input kW 0.38 0.38 0.54 0.54 0.54 0.75  
Space heating (Average climate) Energy efficiency class   A+ A+ A++ A++ A++ A++  
  Capacity Pdesign kW 7.60 7.60 11.30 11.30 12.66 12.66  
  SCOP/A   4.54 4.54 4.80 4.80 4.63 4.63  
  SCOPnet/A   4,566.00 4.57 4,835.00 4.84 4.65 4.65  
  Pdh Heating capacity at -10° kW   6.71          
  Annual energy consumption kWh/a 2,344 2,344 3,296 3,296 3,829 3,829  
  Required back up heating cap at design conditions kW 0.89 0.89 1.60 1.60 1.11 1.11  
  TOL Tol (temperature operating limit) °C -15 -15 -15 -15 -15 -15  
    Pdh (declared heating cap) kW 6.69 6.69 9.18 9.18 12.12 12.12  
    COPd (declared COP)   2.32 2.32 2.75 2.75 2.13 2.13  
    Power input kW 2.89 2.89 3.34 3.34 5.70 5.70  
  TBivalent Tbiv (bivalent temperature) °C -7 -7 -7 -7 -7 -7  
    Pdh (declared heating cap) kW 6.72 6.72 10.00 10.00 11.20 11.20  
    COPd (declared COP)   3.11 3.11 3.72 3.72 2.95 2.95  
    Power input kW 2.17 2.17 2.69 2.69 3.80 3.80  
  A Condition (-7°C) Pdh (declared heating cap) kW 6.72 6.72 10.00 10.00 11.20 11.20  
    COPd (declared COP)   3.11 3.11 3.72 3.72 2.95 2.95  
    Power input kW 2.17 2.17 2.69 2.69 3.80 3.80  
  B Condition (2°C) Pdh (declared heating cap) kW 4.70 4.70 6.43 6.43 6.82 6.82  
    COPd (declared COP)   4.20 4.20 4.24 4.24 4.24 4.24  
    Power input kW 1.12 1.12 1.52 1.52 1.61 1.61  
  C Condition (7°C) Pdh (declared heating cap) kW 2.93 2.93 4.16 4.16 4.38 4.38  
    COPd (declared COP)   6.93 6.93 6.76 6.76 7.02 7.02  
    Power input kW 0.43 0.43 0.62 0.62 0.63 0.63  
  D Condition (12°C) Pdh (declared heating cap) kW 3.33 3.33 4.76 4.76 5.40 5.40  
    COPd (declared COP)   8.11 8.11 7.94 7.94 7.89 7.89  
    Power input kW 0.42 0.42 0.60 0.60 0.69 0.69  
Pto (Thermostat off) W 7.0 7.0 9.0 9.0 9.0 9.0  
Power consumption in other than active mode Standby mode Cooling PSB W 7.0 9.1 9.0 9.0 9.0 9.0  
    Heating PSB W 7.0 9.1 9.0 9.0 9.0 9.0  
  Crankcase heater mode PCK W 0.0 0.0 0.0 0.0 0.0 0.0  
  Off mode POFF W 0.0 0.0 0.0 0.0 0.0 0.0  
Cooling Cdc (Degradation cooling)   0.25 0.25 0.25 0.25 0.25 0.25  
Heating Cdh (Degradation heating)   0.25 0.25 0.25 0.25 0.25 0.25  
Cooling function included Yes Yes Yes Yes Yes Yes  
Heating function included Yes Yes Yes Yes Yes Yes  
Average climate included Yes Yes Yes Yes Yes Yes  
Cold season included No No No No No No  
Warm season included No No No No No No  
Ecolabel logo No No No No No No  
Eurovent Sound power level outdoor Cooling Nom. dBA   64          
  Sound power level indoor Cooling Nom. dBA   53          
Notes   Annual energy consumption is according to Energy labeling directive 2002/31/EC   EER/COP according to Eurovent 2012, for use outside EU only   EER/COP according to Eurovent 2012, for use outside EU only EER/COP according to Eurovent 2012, for use outside EU only
    SEER and SCOP are according to EN 14825   Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load   Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load