FDA125A5VEB / RZQSG125L9V1B
Indoor unit FDA125A5VEB
Outdoor unit RZQSG125L9V1
Cooling capacity Nom. kW 12.0 (1)
Heating capacity Nom. kW 13.5 (2)
Power input Cooling Nom. kW 3.74 (3)
  Heating Nom. kW 3.85 (3)
Nominal efficiency EER   3.21 (3)
  COP   3.51 (3)
  Annual energy consumption kWh 1,870 (0.000)
  Energy labeling Directive Cooling   A
    Heating   B
Space cooling Energy efficiency class   A
  Capacity Pdesign kW 12.0
  SEER   5.20
  Annual energy consumption kWh/a 808
  A Condition (35°C - 27/19) Pdc kW 12.00
    EERd   3.09
    Power input kW 3.89
  B Condition (30°C - 27/19) Pdc kW 8.84
    EERd   3.41
    Power input kW 2.60
  C Condition (25°C - 27/19) Pdc kW 5.69
    EERd   6.59
    Power input kW 0.87
  D Condition (20°C - 27/19) Pdc kW 4.04
    EERd   8.52
    Power input kW 0.48
Space heating (Average climate) Energy efficiency class   A
  Capacity Pdesign kW 7.60
  SCOP/A   3.90
  SCOPnet/A   3.91
  Annual energy consumption kWh/a 2,729
  Required back up heating cap at design conditions kW 0.580
  TOL Tol (temperature operating limit) °C -15
    Pdh (declared heating cap) kW 7.51
    COPd (declared COP)   2.21
    Power input kW 3.40
  TBivalent Tbiv (bivalent temperature) °C -7
    Pdh (declared heating cap) kW 6.72
    COPd (declared COP)   2.89
    Power input kW 2.33
  A Condition (-7°C) Pdh (declared heating cap) kW 6.72
    COPd (declared COP)   2.89
    Power input kW 2.33
  B Condition (2°C) Pdh (declared heating cap) kW 4.85
    COPd (declared COP)   3.86
    Power input kW 1.26
  C Condition (7°C) Pdh (declared heating cap) kW 3.02
    COPd (declared COP)   5.12
    Power input kW 0.59
  D Condition (12°C) Pdh (declared heating cap) kW 3.42
    COPd (declared COP)   6.00
    Power input kW 0.57
Power consumption in other than active mode Crankcase heater mode Cooling PCK kW 0.000
    Heating PCK kW 0.000
  Off mode Cooling POFF kW 0.000
    Heating POFF kW 0.000
  Standby mode Cooling PSB kW 0.007
    Heating PSB kW 0.007
  Thermostat-off mode Cooling PTO kW 0.007
    Heating PTO kW 0.007
Cooling Cdc (Degradation cooling)   0.25
Heating Cdh (Degradation heating)   0.25
Cooling function included Yes
Heating function included Yes
Average climate included Yes
Cold season included No
Warm season included No
Ecolabel logo No
Eurovent Sound power level outdoor Cooling Nom. dBA 70
  Sound power level indoor Cooling Nom. dBA 66
Notes Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  EER/COP according to Eurovent 2012, for use outside EU only