Specifications Table for FHA-A(9) / RZQSG-L3/9V1

FHA71AVEB9 / RZQSG71L3V1B FHA100AVEB / RZQSG100L9V1B FHA125AVEB / RZQSG125L9V1B FHA140AVEB / RZQSG140L9V1B
Cooling capacity Nom. kW 6.80 9.50 12.00 13.40
Heating capacity Nom. kW 7.50 10.80 13.50 15.50
Nominal efficiency EER   3.46 3.21 2.89 2.63
  COP   4.00 3.61 3.62 3.41
  Annual energy consumption kWh 983 1,480 2,076  
  Energy labeling Directive Cooling   A A C  
    Heating   A A A  
Space cooling Energy efficiency class   A+ A+ A+  
  Capacity Pdesign kW 6.80 9.50 12.00 13.40
  SEER   5.61 5.61 5.61 5.61
  Annual energy consumption kWh/a 425 593 749 1,434
Space heating (Average climate) Energy efficiency class   A A A+  
  Capacity Pdesign kW 7.60 7.60 7.60 11.61
  SCOP/A   3.90 3.91 4.01 3.72
  Annual energy consumption kWh/a 2,727 2,722 2,654 4,376
Notes (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
  (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range
  (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data