FHQ71CBVEB / RZQG71L8Y1B FHQ100CBVEB / RZQG71L8Y1B FHQ100CBVEB / RZQG100L8Y1B FHQ140CBVEB / RZQG100L8Y1B FHQ125CBVEB / RZQG125L8Y1B FHQ140CBVEB / RZQG125L8Y1B FHQ140CBVEB / RZQG140L7Y1B
Poff (Off mode) W 0.0   0.0   0.0    
Cooling Psb (Standby mode cooling) W 9.1   9.0   9.0    
  Cooling-=-Cooling cdc degradation cooling 0.25   0.25   0.25    
Eurovent Sound power level indoor Cooling Nom. dBA 55 60 60 64 62 64  
  Sound power level outdoor Cooling Nom. dBA 64 64 66 66 67 67  
Seasonal efficiency (according to EN14825) Cooling Pdesign kW 6.80   9.50   12.00    
    Annual energy consumption kWh 347   545   699    
    Seasonal efficiency (according to EN14825)-=-Cooling-=-Seasonal efficiency according to en14825 cooling energy efficiency class 6.86   6.11   6.01    
    D Condition (20°C - 27/19) Pdc kW 4.17   5.87   5.64    
      power input kW 0.34   0.58   0.59    
      Seasonal efficiency (according to EN14825)-=-Cooling-=-D Condition (20°C - 27/19)-=-Eerd 12.58   10.14   9.69    
    C Condition (25°C - 27/19) power input kW 0.43   0.73   0.80    
      Pdc kW 4.01   5.66   5.92    
      Seasonal efficiency (according to EN14825)-=-Cooling-=-C Condition (25°C - 27/19)-=-Eerd 9.47   7.86   7.45    
    A Condition (35°C - 27/19) power input kW 1.79   2.31   3.41    
      Pdc kW 6.80   9.50   12.00    
      Seasonal efficiency (according to EN14825)-=-Cooling-=-A Condition (35°C - 27/19)-=-Eerd 3.82   4.13   3.52    
    B Condition (30°C - 27/19) Pdc kW 5.16   7.16   8.84    
      power input kW 1.04   1.60   2.00    
      Seasonal efficiency (according to EN14825)-=-Cooling-=-B Condition (30°C - 27/19)-=-Eerd 5.00   4.50   4.44    
  Heating (Average climate) Annual energy consumption kWh 2,463   3,432   4,677    
    Pdh Heating capacity at -10° kW 6.74   9.71   12.51    
    Pdesign kW 7.60   11.30   14.13    
    Required back up heating cap at design conditions kW 0.86   1.59   1.62    
    Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-Seasonal efficiency according to en14825 heating average climate scopnet a A+   A++   A+    
    TBivalent Pdh (declared heating cap) kW 6.72   10.00   12.50    
      Power input kW 2.28   2.78   4.97    
      Tbiv (bivalent temperature) °C -7   -7   -7    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TBivalent-=-Copd declared cop 2.95   3.61   2.52    
    C Condition (7°C) Pdh (declared heating cap) kW 2.95   4.21   4.89    
      Power input kW 0.45   0.65   0.75    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-C Condition (7°C)-=-Copd declared cop 6.67   6.54   6.57    
    TOL Tol (temperature operating limit) °C -15   -15   -15    
      Pdh (declared heating cap) kW 6.76   9.22   12.52    
      Power input kW 3.21   3.50   6.05    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TOL-=-Copd declared cop 2.11   2.64   2.07    
    A Condition (-7°C) Pdh (declared heating cap) kW 6.72   10.00   12.50    
      Power input kW 2.28   2.78   4.97    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-A Condition (-7°C)-=-Copd declared cop 2.95   3.61   2.52    
    D Condition (12°C) Pdh (declared heating cap) kW 3.36   4.81   5.37    
      Power input kW 0.44   0.64   0.74    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-D Condition (12°C)-=-Copd declared cop 7.70   7.58   7.35    
    B Condition (2°C) Power input kW 1.19   1.62   1.95    
      Pdh (declared heating cap) kW 4.74   6.54   7.61    
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-B Condition (2°C)-=-Copd declared cop 3.99   4.04   3.92    
Cooling capacity Nom. kW 6.8   9.5   12.0   13.4
Pck (Crankcase heater mode) W 0.0   0.0   0.0    
Nominal efficiency Annual energy consumption kWh 890 (0.000)   1,245 (0.000)   1,790 (0.000)   2,025 (0.000)
  Energy labeling Directive Heating A   A   A   A
  Nominal efficiency-=-Cop 3.82   3.81   3.35   3.31
Heating Psb (Standby mode heating) W 9.1   9.0   9.0    
  Heating-=-Heating cdh degradation heating 0.25   0.25   0.25    
Heating capacity Nom. kW 7.5   10.8   13.5   15.5
Pto (Thermostat off) W 7.0 7.0 9.0 9.0 9.0 9.0  
Power input Cooling Nom. kW 1.78   2.49   3.58   4.05
  Heating Nom. kW 1.82   2.60   3.48   4.27
Cold season included Yes   Yes   Yes    
Notes Annual energy consumption is according to Energy labeling directive 2002/31/EC   EER/COP according to Eurovent 2012, for use outside EU only   EER/COP according to Eurovent 2012, for use outside EU only   EER/COP according to Eurovent 2012, for use outside EU only
  SEER and SCOP are according to EN 14825   Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load   Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load   Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load
Space cooling Energy efficiency class     A++   A++   A+  
  Capacity Pdesign kW   6.80   9.50   12.00  
  SEER     6.95   6.11   6.01  
  Annual energy consumption kWh/a   343   545   699  
  A Condition (35°C - 27/19) Pdc kW   6.80   9.50   12.00  
    EERd     3.82   4.13   3.52  
    Power input kW   1.79   2.31   3.41  
  B Condition (30°C - 27/19) Pdc kW   5.16   7.16   8.84  
    EERd     5.00   4.50   4.44  
    Power input kW   1.04   1.60   2.00  
  C Condition (25°C - 27/19) Pdc kW   4.01   5.66   5.92  
    EERd     9.47   7.86   7.45  
    Power input kW   0.43   0.73   0.80  
  D Condition (20°C - 27/19) Pdc kW   4.17   5.87   5.64  
    EERd     12.58   10.14   9.69  
    Power input kW   0.34   0.58   0.59  
Space heating (Average climate) Energy efficiency class     A+   A++   A+  
  Capacity Pdesign kW   7.60   11.30   14.13  
  SCOP/A     4.32   4.61   4.23  
  SCOPnet/A     4.34   4.64   4.25  
  Pdh Heating capacity at -10° kW   6.74   9.71   12.51  
  Annual energy consumption kWh/a   2,463   3,432   4,677  
  Required back up heating cap at design conditions kW   0.86   1.59   1.62  
  TOL Tol (temperature operating limit) °C   -15   -15   -15  
    Pdh (declared heating cap) kW   6.76   9.22   12.52  
    COPd (declared COP)     2.11   2.64   2.07  
    Power input kW   3.21   3.50   6.05  
  TBivalent Tbiv (bivalent temperature) °C   -7   -7   -7  
    Pdh (declared heating cap) kW   6.72   10.00   12.50  
    COPd (declared COP)     2.95   3.61   2.52  
    Power input kW   2.28   2.78   4.97  
  A Condition (-7°C) Pdh (declared heating cap) kW   6.72   10.00   12.50  
    COPd (declared COP)     2.95   3.61   2.52  
    Power input kW   2.28   2.78   4.97  
  B Condition (2°C) Pdh (declared heating cap) kW   4.74   6.54   7.61  
    COPd (declared COP)     3.99   4.04   3.92  
    Power input kW   1.19   1.62   1.95  
  C Condition (7°C) Pdh (declared heating cap) kW   2.95   4.21   4.89  
    COPd (declared COP)     6.67   6.54   6.57  
    Power input kW   0.45   0.65   0.75  
  D Condition (12°C) Pdh (declared heating cap) kW   3.36   4.81   5.37  
    COPd (declared COP)     7.70   7.58   7.35  
    Power input kW   0.44   0.64   0.74  
Power consumption in other than active mode Standby mode Cooling PSB W   7.0   9.0   9.0  
    Heating PSB W   7.0   9.0   9.0  
  Crankcase heater mode PCK W   0.0   0.0   0.0  
  Off mode POFF W   0.0   0.0   0.0  
Cooling Cdc (Degradation cooling)     0.25   0.25   0.25  
Heating Cdh (Degradation heating)     0.25   0.25   0.25  
Cooling function included   Yes   Yes   Yes  
Heating function included   Yes   Yes   Yes  
Average climate included   Yes   Yes   Yes  
Cold season included   No   No   No  
Warm season included   No   No   No  
Ecolabel logo   No   No   No