FTX60GV1B / RX60G4V1B FTX71GV1B / RX71GV1B8
Poff (Off mode) W 15.0 20.0
Cooling Psb (Standby mode cooling) W 15.0 20.0
  Cooling-=-Cooling cdc degradation cooling 0.25 0.25
Seasonal efficiency (according to EN14825) Cooling Pdesign kW 6.00 7.10
    Annual energy consumption kWh 391 500
    Seasonal efficiency (according to EN14825)-=-Cooling-=-Seasonal efficiency according to en14825 cooling energy efficiency class 5.37 4.97
    D Condition (20°C - 27/19) Pdc kW 2.25 3.10
      Seasonal efficiency (according to EN14825)-=-Cooling-=-D Condition (20°C - 27/19)-=-Eerd 11.00 9.48
    C Condition (25°C - 27/19) Pdc kW 2.84 3.37
      Seasonal efficiency (according to EN14825)-=-Cooling-=-C Condition (25°C - 27/19)-=-Eerd 6.74 6.87
    A Condition (35°C - 27/19) Pdc kW 6.00 7.10
      Seasonal efficiency (according to EN14825)-=-Cooling-=-A Condition (35°C - 27/19)-=-Eerd 2.81 2.90
    B Condition (30°C - 27/19) Pdc kW 4.42 5.24
      Seasonal efficiency (according to EN14825)-=-Cooling-=-B Condition (30°C - 27/19)-=-Eerd 4.48 4.57
  Heating (Average climate) Annual energy consumption kWh 1,730 2,276
    Pdesign kW 4.80 6.20
    Required back up heating cap at design conditions kW 0.76 0.83
    Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-Seasonal efficiency according to en14825 heating average climate scop a A A
    TBivalent Pdh (declared heating cap) kW 4.25 5.48
      Tbiv (bivalent temperature) °C -7 -7
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TBivalent-=-Copd declared cop 2.21 2.26
    C Condition (7°C) Pdh (declared heating cap) kW 1.66 2.28
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-C Condition (7°C)-=-Copd declared cop 4.91 4.85
    TOL Tol (temperature operating limit) °C -15 -15
      Pdh (declared heating cap) kW 3.69 5.18
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TOL-=-Copd declared cop 1.81 1.77
    A Condition (-7°C) Pdh (declared heating cap) kW 4.25 5.48
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-A Condition (-7°C)-=-Copd declared cop 2.21 2.26
    D Condition (12°C) Pdh (declared heating cap) kW 1.95 2.60
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-D Condition (12°C)-=-Copd declared cop 6.12 5.20
    B Condition (2°C) Pdh (declared heating cap) kW 2.58 3.34
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-B Condition (2°C)-=-Copd declared cop 4.11 4.05
Cooling capacity Nom. Btu/h 20,500 (2) 24,200 (2)
  Min. kW 1.7 (2) 2.3 (2)
  Nom. kcal/h 5,160 (2) 6,110 (2)
  Max. kW 6.7 (2) 8.5 (2)
  Min. kcal/h 1,460 (2) 1,980 (2)
  Min. Btu/h 5,800 (2) 7,800 (2)
  Nom. kW 6.0 (2) 7.10 (2)
  Max. Btu/h 22,900 (2) 29,000 (2)
  Max. kcal/h 5,760 (2) 7,310 (2)
Pck (Crankcase heater mode) W 0.0 10.0
Nominal efficiency Annual energy consumption kWh 995 (0.000) 1,175 (0.000)
  Energy labeling Directive Heating B B
  Nominal efficiency-=-Cop 3.02 (1) 3.02 (1)
Heating Heating-=-Heating cdh degradation heating 0.25 0.25
Piping connections Liquid OD mm 6.35 6.35
  Gas OD mm 12.7 15.9
  Drain OD mm 18 18
Heating capacity Min. Btu/h 5,800 (3) 7,800 (3)
  Nom. Btu/h 23,900 (3) 28,000 (3)
  Max. kcal/h 6,880 (3) 8,770 (3)
  Max. Btu/h 27,300 (3) 34,800 (3)
  Nom. kW 7.0 (3) 8.20 (3)
  Min. kW 1.7 (3) 2.3 (3)
  Nom. kcal/h 6,020 (3) 7,050 (3)
  Min. kcal/h 1,460 (3) 1,980 (3)
  Max. kW 8.0 (3) 10.2 (3)
Pto (Thermostat off) W 42.0 42.0
Power input Cooling Min. kW 0.440 (2) 0.570 (2)
    Nom. kW 1.990 (2) 2.350 (2)
    Max. kW 2.400 (2) 3.200 (2)
  Heating Max. kW 2.810 (3) 3.820 (3)
    Min. kW 0.400 (3) 0.520 (3)
    Nom. kW 2.040 (3) 2.550 (3)
Cold season included Yes Yes
Current Nominal running current (RLA) - 50Hz Heating A 9.4 (4), 9.0 (5), 8.6 (6) 11.7 (4), 11.2 (5), 10.7 (6)
    Cooling A 9.2 (4), 8.8 (5), 8.4 (6) 10.8 (4), 10.4 (5), 9.9 (6)
Notes EER/COP according to Eurovent 2012, for use outside EU only EER/COP according to Eurovent 2012, for use outside EU only
  Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB; equivalent piping length: 5m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB; equivalent piping length: 5m
  Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m
  220V 220V
  230V 230V
  240V 240V
  Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load