FTXA20A2V1BW / RXA20A2V1B FTXA25A2V1BW / RXA25A2V1B FTXA35A2V1BW / RXA35A2V1B FTXA42A2V1BW / RXA42A2V1B FTXA50A2V1BW / RXA50A2V1B
Indoor unit FTXA20A2V1BW FTXA25A2V1BW FTXA35A2V1BW FTXA42A2V1BW FTXA50A2V1BW
Outdoor unit RXA20A2V1B RXA25A2V1B RXA35A2V1B RXA42A2V1B RXA50A2V1B
Cooling capacity Min. kW 1.3 1.3 1.4 1.7 1.7
  Min. Btu/h 4,400.0 4,400.0 4,800.0 5,800.0 5,800.0
  Min. kcal/h 1,120.0 1,120.0 1,200.0 1,460.0 1,460.0
  Nom. kW 2.0 2.5 3.4 4.2 5.0
  Nom. Btu/h 6,800.0 8,500.0 11,600.0 14,300.0 17,100.0
  Nom. kcal/h 1,720.0 2,150.0 2,920.0 3,610.0 4,300.0
  Max. kW 2.6 3.2 4.0 5.0 5.3
  Max. Btu/h 8,900.0 10,900.0 13,600.0 17,100.0 18,100.0
  Max. kcal/h 2,240.0 2,750.0 3,440.0 4,300.0 4,560.0
Heating capacity Min. kW 1.30 1.30 1.40 1.70 1.70
  Min. Btu/h 4,400.0 4,400.0 4,800.0 5,800.0 5,800.0
  Min. kcal/h 1,120.0 1,120.0 1,200.0 1,460.0 1,460.0
  Nom. kW 2.50 2.80 4.00 5.40 5.80
  Nom. Btu/h 8,500.0 9,600.0 13,600.0 18,400.0 19,800.0
  Nom. kcal/h 2,150.0 2,410.0 3,440.0 4,640.0 4,990.0
  Max. kW 3.50 4.70 5.20 6.00 6.50
  Max. Btu/h 11,900.0 16,000.0 17,700.0 20,500.0 22,200.0
  Max. kcal/h 3,010.0 4,040.0 4,470.0 5,160.0 5,590.0
Power input Cooling Min. kW 0.27 0.27 0.31    
    Nom. kW 0.43 0.56 0.78 1.05 1.36
    Max. kW 0.63 0.78 1.04    
  Heating Min. kW 0.25 0.25 0.26 0.46 0.49
    Nom. kW 0.50 0.56 0.99 1.31 1.45
    Max. kW 0.91 1.22 1.67    
Nominal efficiency EER   4.70 4.46 4.37 3.99 3.68
  COP   5.00 5.00 4.04 4.12 4.00
  Energy labeling Directive Cooling   A A A A A
    Heating   A A A A A
Space cooling Capacity Pdesign kW 2.00 2.50 3.40 4.20 5.00
  Energy efficiency class   A+++ A+++ A+++ A++ A++
  SEER   8.75 8.74 8.73 7.50 7.33
  Annual energy consumption kWh/a 80 101 137 196 239
  A Condition (35°C - 27/19) Pdc kW 2.00 2.50 3.40 4.20 5.00
    EERd   4.70 4.46 4.37 3.99 3.68
    Power input kW 0.43 0.56 0.78 1.05 1.36
  B Condition (30°C - 27/19) Pdc kW 1.47 1.84 2.51 3.09 3.68
    EERd   6.96 6.79 6.28 5.54 5.29
    Power input kW 0.21 0.27 0.40 0.56 0.70
  C Condition (25°C - 27/19) Pdc kW 0.95 1.18 1.61 1.99 2.37
    EERd   10.37 10.35 10.58 9.31 9.24
    Power input kW 0.09 0.11 0.15 0.21 0.26
  D Condition (20°C - 27/19) Pdc kW 1.27 1.29 1.33 1.86 1.87
    EERd   16.36 16.30 16.21 12.06 12.03
    Power input kW 0.08 0.08 0.08 0.15 0.16
Space heating (Average climate) Capacity Pdesign kW 2.40 2.45 2.50 3.80 4.00
  Energy efficiency class   A+++ A+++ A+++ A++ A++
  SCOP/A   5.15 5.15 5.15 4.60 4.60
  SCOPnet/A   5.19 5.18 5.18 4.63 4.61
  Pdh Heating capacity at -10° kW 2.19 2.30 2.36 3.34 3.45
  Annual energy consumption kWh/a 653 666 680 1,150 1,217
  Required back up heating cap at design conditions kW 0.21 0.15 0.14 0.46 0.55
  TOL Tol (temperature operating limit) °C -15 -15 -15 -15 -15
    Pdh (declared heating cap) kW 2.31 2.52 2.62 3.90 4.12
    COPd (declared COP)   2.48 2.36 2.30 2.04 2.16
    Power input kW 0.93 1.07 1.14 1.91 1.91
  TBivalent Tbiv (bivalent temperature) °C -7 -7 -7 -7 -7
    Pdh (declared heating cap) kW 2.12 2.17 2.21 3.36 3.54
    COPd (declared COP)   3.56 3.59 3.58 3.24 3.16
    Power input kW 0.60 0.60 0.62 1.04 1.12
  A Condition (-7°C) Pdh (declared heating cap) kW 2.12 2.17 2.21 3.36 3.54
    COPd (declared COP)   3.56 3.59 3.58 3.24 3.16
    Power input kW 0.60 0.60 0.62 1.04 1.12
  B Condition (2°C) Pdh (declared heating cap) kW 1.29 1.32 1.35 2.05 2.15
    COPd (declared COP)   5.24 5.22 5.19 4.44 4.43
    Power input kW 0.25 0.25 0.26 0.46 0.49
  C Condition (7°C) Pdh (declared heating cap) kW 0.92 0.94 0.94 1.65 1.71
    COPd (declared COP)   6.27 6.25 6.19 6.33 6.32
    Power input kW 0.15 0.15 0.15 0.26 0.27
  D Condition (12°C) Pdh (declared heating cap) kW 1.10 1.10 1.10 1.52 1.52
    COPd (declared COP)   8.05 8.02 7.97 7.35 7.25
    Power input kW 0.14 0.14 0.14 0.21 0.21
Space heating (Warm climate) Capacity Pdesignh kW 1.75 1.87 2.00 2.15 2.15
  Energy efficiency class   A+++ A+++ A+++ A+++ A+++
  SCOP   6.26 6.26 6.28 5.93 5.84
  SCOPnet   6.42 6.42 6.42 6.03 5.95
  Annual energy consumption kWh/a 392 418 446 508 515
  Required back up heating cap at design conditions kW 0.00 0.00 0.00 0.00 0.00
  TOL Tol (temperature operating limit) °C -15 -15 -15 -15 -15
    Pdh (declared heating cap) kW 2.31 2.52 2.62 3.90 4.12
    COPd (declared COP)   2.48 2.36 2.30    
    Power input kW 0.93 1.07 1.14    
  TBivalent Tbiv (bivalent temperature) °C 2 2 2    
    Pdh (declared heating cap) kW 1.75 1.87 2.00    
    COPd (declared COP)   4.76 4.67 4.64    
    Power input kW 0.37 0.40 0.43    
  B Condition (2°C) Pdh (declared heating cap) kW 1.75 1.87 2.00    
    COPd (declared COP)   4.76 4.67 4.64    
    Power input kW 0.37 0.40 0.43    
  C Condition (7°C) Pdh (declared heating cap) kW 1.16 1.20 1.29    
    COPd (declared COP)   6.15 6.12 6.11    
    Power input kW 0.19 0.20 0.21    
  D Condition (12°C) Pdh (declared heating cap) kW 1.1 1.1 1.1    
    COPd (declared COP)   8.05 8.02 7.97    
    Power input kW 0.14 0.14 0.14    
Power consumption in other than active mode Thermostat-off mode PTO Cooling W 7 7 7    
      Heating W 13 13 13    
  Crankcase heater mode PCK W 0.0 0.0 0.0    
  Off mode POFF W 0.5 0.5 0.5    
  Standby mode Cooling PSB W 0.5 0.5 0.5    
    Heating PSB W 0.5 0.5 0.5    
Cooling Cdc (Degradation cooling)   0.25 0.25 0.25 0.25 0.25
Heating Cdh (Degradation heating)   0.25 0.25 0.25 0.25 0.25
Cooling function included Yes Yes Yes Yes Yes
Heating function included Yes Yes Yes Yes Yes
Average climate included Yes Yes Yes Yes Yes
Cold season included No No No No No
Warm season included Yes Yes Yes Yes Yes
Ecolabel logo No No No No No
Eurovent Sound power level outdoor Cooling Nom. dBA 59 59 61 62 62
  Sound power level indoor Cooling Nom. dBA 57 57 60 60 60
  Piping length Cooling Measuring condition m 5.0 5.0 5.0 5.0 5.0
Power factor Nominal Cooling % 91.73 (0.000) 93.94 (0.000) 95.64 (0.000) 94.10 (0.000) 95.74 (0.000)
    Heating % 93.11 (0.000) 93.94 (0.000) 98.09 (0.000) 95.47 (0.000) 96.21 (0.000)
Current Nominal running current (RLA) - 50Hz Cooling A 2.0 2.6 3.6 4.9 6.2
    Heating A 2.3 2.6 4.4 6.0 6.6
Space heating (Warm climate) TOL COPd (declared COP)         2.04 2.16
    Power input kW       1.91 1.91
  TBivalent Tbiv (bivalent temperature) °C       2 2
    Pdh (declared heating cap) kW       2.15 2.15
    COPd (declared COP)         4.42 4.43
    Power input kW       0.49 0.49
  B Condition (2°C) Pdh (declared heating cap) kW       2.15 2.15
    COPd (declared COP)         4.42 4.43
    Power input kW       0.49 0.49
  C Condition (7°C) Pdh (declared heating cap) kW       1.71 1.71
    COPd (declared COP)         6.43 6.32
    Power input kW       0.27 0.27
  D Condition (12°C) Pdh (declared heating cap) kW       1.5 1.5
    COPd (declared COP)         7.35 7.25
    Power input kW       0.21 0.21
Power consumption in other than active mode Crankcase heater mode PCK W       0.0 0.0
  Off mode POFF W       0.5 0.5
  Standby mode Cooling PSB W       0.5 0.5
    Heating PSB W       0.5 0.5
  Thermostat-off mode PTO Cooling W       13 13
      Heating W       13 13