FUQ71CVEB / RZQSG71L3V1B FUQ100CVEB / RZQSG100L9V1B FUQ125CVEB / RZQSG125L9V1B
Indoor unit   FUQ100C FUQ125C
Outdoor unit   RZQSG100L9V1 RZQSG125L9V1
Cooling capacity Nom. kW 6.80 9.5 12.0
Heating capacity Nom. kW 7.50 10.8 13.5
Power input Cooling Nom. kW 2.12 2.96 4.53
  Heating Nom. kW 2.08 2.99 3.95
Nominal efficiency EER   3.21 3.21 2.65
  COP   3.61 3.61 3.41
  Annual energy consumption kWh 1,060 (0.000) 1,480 2,265
  Energy labeling Directive Cooling   A A D
    Heating   A A B
Space cooling Energy efficiency class   A+ A+ A
  Capacity Pdesign kW 6.80 9.50 12.00
  SEER   5.81 5.61 5.30
  Annual energy consumption kWh/a 410 593 793
  A Condition (35°C - 27/19) Pdc kW 6.80 9.50 12.00
    EERd   3.21 3.21 2.65
    Power input kW   2.96 4.53
  B Condition (30°C - 27/19) Pdc kW 5.01 7.00 8.84
    EERd   3.86 3.73 3.01
    Power input kW   1.88 2.94
  C Condition (25°C - 27/19) Pdc kW 3.65 4.59 5.69
    EERd   7.91 7.23 7.33
    Power input kW   0.64 0.78
  D Condition (20°C - 27/19) Pdc kW 3.81 4.02 3.96
    EERd   10.81 9.63 10.43
    Power input kW   0.42 0.38
Space heating (Average climate) Energy efficiency class   A A+ A
  Capacity Pdesign kW 6.33 7.60 7.60
  SCOP/A   3.90 4.01 3.85
  SCOPnet/A   4.02 3.86
  Pdh Heating capacity at -10° kW   7.04 7.05
  Annual energy consumption kWh/a 2,273 2,654 2,764
  Required back up heating cap at design conditions kW 0.63 0.56 0.55
  TOL Tol (temperature operating limit) °C -15 -15 -15
    Pdh (declared heating cap) kW 5.87 7.56 7.60
    COPd (declared COP)   1.73 1.89 1.88
    Power input kW   4.00 4.05
  TBivalent Tbiv (bivalent temperature) °C -7 -7 -7
    Pdh (declared heating cap) kW 5.60 6.72 6.72
    COPd (declared COP)   2.44 2.69 2.62
    Power input kW   2.50 2.57
  A Condition (-7°C) Pdh (declared heating cap) kW 5.60 6.72 6.72
    COPd (declared COP)   2.44 2.69 2.62
    Power input kW   2.50 2.57
  B Condition (2°C) Pdh (declared heating cap) kW 3.46 4.13 4.14
    COPd (declared COP)   3.88 3.82 3.68
    Power input kW   1.09 1.13
  C Condition (7°C) Pdh (declared heating cap) kW 2.86 3.02 3.03
    COPd (declared COP)   5.41 5.56 5.26
    Power input kW   0.55 0.58
  D Condition (12°C) Pdh (declared heating cap) kW 3.25 3.44 3.46
    COPd (declared COP)   6.31 6.59 6.24
    Power input kW   0.53 0.56
Pto (Thermostat off) W 7.0 7.0 7.0
Power consumption in other than active mode Standby mode Cooling PSB W 7.0    
  Crankcase heater mode PCK W 0.0    
  Off mode POFF W 0.0    
Cooling Cdc (Degradation cooling)   0.25 0.25 0.25
Heating Cdh (Degradation heating)   0.25 0.25 0.25
Cooling function included Yes Yes Yes
Heating function included Yes Yes Yes
Average climate included Yes Yes Yes
Cold season included No No No
Warm season included No No No
Ecolabel logo No No No
Eurovent Sound power level outdoor Cooling Nom. dBA 65 70 70
  Sound power level indoor Cooling Nom. dBA 59 64 65
Notes EER/COP according to Eurovent 2012, for use outside EU only    
  Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load    
Power consumption in other than active mode Standby mode Cooling PSB W   7.0 7.0
    Heating PSB W   7.0 7.0
  Crankcase heater mode PCK W   0.0 0.0
  Off mode POFF W   0.0 0.0