FXNQ20A2VEB FXNQ25A2VEB FXNQ32A2VEB FXNQ40A2VEB FXNQ50A2VEB FXNQ63A2VEB
Cooling capacity Sensible capacity Nom. kW 1.90 2.10 2.60 3.30 4.00 4.90
  Latent capacity Nom. kW 0.300 0.700 1.00 1.20 1.60 2.20
  Total capacity Nom. kW 2.20 2.80 3.60 4.50 5.60 7.10
Heating capacity Total capacity Nom. kW 2.50 3.20 4.00 5.00 6.30 8.00
Power input - 50Hz Cooling Nom. kW 0.071 0.071 0.071 0.078 0.099 0.110
  Heating Nom. kW 0.068 0.068 0.068 0.075 0.096 0.107
Dimensions Unit Height mm 620, 720 (1) 620, 720 (1) 620, 720 (1) 620, 720 (1) 620, 720 (1) 620, 720 (1)
    Width mm 790 790 790 990 990 1,190
    Depth mm 200 200 200 200 200 200
  Packed unit Height mm 265 265 265 265 265 265
    Width mm 925 925 925 1,125 1,125 1,325
    Depth mm 885 885 885 885 885 885
Weight Unit kg 23.5 23.5 23.5 27.5 27.5 32.0
  Packed unit kg 27.5 27.5 27.5 32.0 32.0 37.0
Casing Colour   Unpainted Unpainted Unpainted Unpainted Unpainted Unpainted
  Material   Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate
Heat exchanger Inside length mm 500 500 500 700 700 900
  Rows Quantity   2 2 3 3 3 3
  Fin pitch mm 1.50 1.50 1.50 1.50 1.50 1.50
  Passes Quantity   3 3 6 6 6 6
  Face area 0.126 0.126 0.126 0.176 0.176 0.227
  Stages Quantity   12 12 12 12 12 12
  Empty tubeplate hole Quantity   0 0 4 0 0 0
  Tube type   7.0 Hi-XD 7.0 Hi-XD 7.0 Hi-XD 7.0 Hi-XD 7.0 Hi-XD 7.0 Hi-XD
  Fin Type   Cross fin coil Cross fin coil Cross fin coil Cross fin coil Cross fin coil Cross fin coil
Fan Type   Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan
  Quantity   2 2 2 3 3 4
  Air flow rate - 50Hz Cooling High m³/min 8.0 8.0 8.0 10.5 12.5 16.5
      Medium m³/min 7.20 7.20 7.20 9.50 11.0 14.5
      Low m³/min 6.4 6.4 6.4 8.5 10.0 13.0
    Heating High m³/min 8.0 8.0 8.0 10.5 12.5 16.5
      Medium m³/min 7.2 7.2 7.2 9.5 11.0 14.5
      Low m³/min 6.4 6.4 6.4 8.5 10.0 13.0
  External static pressure - 50Hz High Pa 41.0 41.0 42.0 52.0 59.0 55.0
    Nom. Pa 10 10 10 15 15 15
Sound pressure level Cooling High dBA 30.0 30.0 30.0 32.0 33.0 35.0
    Nom. dBA 28.5 28.5 28.5 30.0 31.0 33.0
    Low dBA 27.0 27.0 27.0 28.0 29.0 32.0
  Heating High dBA 30.0 30.0 30.0 32.0 33.0 35.0
    Nom. dBA 28.5 28.5 28.5 30.0 31.0 33.0
    Low dBA 27.0 27.0 27.0 28.0 29.0 32.0
Fan motor Quantity   1 1 1 1 1 1
  Model   KFD-280-44-8A KFD-280-44-8A KFD-280-44-8A KFD-280-65-8A KFD-280-65-8A KFD-280-65-8A
  Speed Steps   3 3 3 3 3 3
  Output Max W 44 44 44 65 65 65
Refrigerant Type   R-410A R-410A R-410A R-410A R-410A R-410A
  GWP   2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5
Sound power level Cooling High dBA 51 51 51 52 53 54
Piping connections Liquid Type   Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection
    OD mm 6,35 6,35 6,35 6,35 6,35 9,52
  Gas Type   Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection
    OD mm 12.7 12.7 12.7 12.7 12.7 15.9
  Drain   VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26)
  Heat insulation   Foamed polystyrene / Foamed polyethylene Foamed polystyrene / Foamed polyethylene Foamed polystyrene / Foamed polyethylene Foamed polystyrene / Foamed polyethylene Foamed polystyrene / Foamed polyethylene Foamed polystyrene / Foamed polyethylene
  Sound absorbing insulation   Butyl Rubber Butyl Rubber Butyl Rubber Butyl Rubber Butyl Rubber Butyl Rubber
Air filter Type   Resin net Resin net Resin net Resin net Resin net Resin net
Control systems Infrared remote control   BRC4C65 BRC4C65 BRC4C65 BRC4C65 BRC4C65 BRC4C65
  Wired remote control   BRC1D52, BRC1E53A, BRC1E53B, BRC1E53C, BRC1H519W/S/K BRC1D52, BRC1E53A, BRC1E53B, BRC1E53C, BRC1H519W/S/K BRC1D52, BRC1E53A, BRC1E53B, BRC1E53C, BRC1H519W/S/K BRC1D52, BRC1E53A, BRC1E53B, BRC1E53C, BRC1H519W/S/K BRC1D52, BRC1E53A, BRC1E53B, BRC1E53C, BRC1H519W/S/K BRC1D52, BRC1E53A, BRC1E53B, BRC1E53C, BRC1H519W/S/K
Power supply Name   VE VE VE VE VE VE
  Phase   1~ 1~ 1~ 1~ 1~ 1~
  Frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60
  Voltage V 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220
Current - 50Hz Minimum circuit amps (MCA) A 0.4 0.4 0.4 0.5 0.5 0.6
  Maximum fuse amps (MFA) A 16 16 16 16 16 16
  Full load amps (FLA) Total A 0.3 0.3 0.3 0.4 0.4 0.5
Notes Including installation legs Including installation legs Including installation legs Including installation legs Including installation legs Including installation legs
  The sound power level is an absolute value indicating the power which a sound source generates. The sound power level is an absolute value indicating the power which a sound source generates. The sound power level is an absolute value indicating the power which a sound source generates. The sound power level is an absolute value indicating the power which a sound source generates. The sound power level is an absolute value indicating the power which a sound source generates. The sound power level is an absolute value indicating the power which a sound source generates.
  Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA
  Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%.
  Use a circuit breaker instead of a fuse. Use a circuit breaker instead of a fuse. Use a circuit breaker instead of a fuse. Use a circuit breaker instead of a fuse. Use a circuit breaker instead of a fuse. Use a circuit breaker instead of a fuse.
  MCA/MFA; MCA= 1,25 x FLA; MFA=< 4 x FLA; The next lower standard fuse rating is minimum 16 ampere. MCA/MFA; MCA= 1,25 x FLA; MFA=< 4 x FLA; The next lower standard fuse rating is minimum 16 ampere. MCA/MFA; MCA= 1,25 x FLA; MFA=< 4 x FLA; The next lower standard fuse rating is minimum 16 ampere. MCA/MFA; MCA= 1,25 x FLA; MFA=< 4 x FLA; The next lower standard fuse rating is minimum 16 ampere. MCA/MFA; MCA= 1,25 x FLA; MFA=< 4 x FLA; The next lower standard fuse rating is minimum 16 ampere. MCA/MFA; MCA= 1,25 x FLA; MFA=< 4 x FLA; The next lower standard fuse rating is minimum 16 ampere.
  Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases