HXY080A8V1B HXY125A8V1B
Cooling capacity Nom. kW 8.0 (1) 12.5 (1)
Heating capacity Nom. kW 9.00 (2) 14.00 (2)
Casing Colour   White White
  Material   Precoated sheet metal Precoated sheet metal
Dimensions Unit Height mm 890 890
    Width mm 480 480
    Depth mm 344 344
  Packed unit Height mm 415 415
    Width mm 650 650
    Depth mm 1,016 1,016
Weight Unit kg 44 44
  Packed unit kg 47 47
Packing Material   Carton, EPS, PP (Straps) Carton, EPS, PP (Straps)
  Weight kg 2.8 2.8
PED Category   Art3§3 Art3§3
Pump Type   DC motor DC motor
  Nr of speeds   Inverter controlled Inverter controlled
  Nominal ESP unit Heating kPa 85.0 (2) 65.0 (2)
    Cooling kPa 88.0 (1) 73.0 (1)
  Power input W 110 135
Water side Heat exchanger Type   Brazed plate Brazed plate
  Quantity   1 1
  Water flow rate Min. l/min 15.0 (3) 15.0 (3)
    Heating Nom. l/min 25.8 (2) 40.1 (2)
    Cooling Nom. l/min 22.9 (1) 35.8 (1)
  Insulation material   Foamed synthetic elastomer Foamed synthetic elastomer
Expansion vessel Volume l 10 10
  Max. water pressure bar 3 3
  Pre pressure bar 1 1
Water filter Diameter perforations mm 1.0 1.0
  Material   Copper - brass - stainless steel Copper - brass - stainless steel
Water circuit Piping connections diameter inch G 1"1/4 (female) G 1"1/4 (female)
  Safety valve bar 3 3
  Shut off valve   Yes Yes
  flowswitch   Yes Yes
  Air purge valve   Yes Yes
Refrigerant Type   R-410A R-410A
  GWP   2,087.5 2,087.5
Refrigerant circuit Gas side diameter mm 15.9 15.9
  Liquid side diameter mm 9.5 9.5
Operation range Heating Ambient Min. °C -20 -20
      Max. °C 24 24
    Water side Min. °C 25 25
      Max. °C 45 45
  Cooling Ambient Min. °CDB 10 10
      Max. °CDB 43 43
    Water side Min. °C 5 5
      Max. °C 20 20
Power supply Phase   1~ 1~
  Frequency Hz 50 50
  Voltage V 220-240 220-240
  Voltage range Min. % -10 -10
    Max. % 10 10
Current Recommended fuses A 6~16 6~16
Current - 50Hz Nominal running current A 2.5 2.5
Wiring connections For power supply Quantity   3G 3G
    Type of wires   Wire type/size has to be selected according to applicable legislation Wire type/size has to be selected according to applicable legislation
  Communication cable Quantity   2 2
    Type of wires   0,75 ~1,25 mm² (F1F2) 0,75 ~1,25 mm² (F1F2)
  For connection with user interface Quantity   2 2
    Type of wires   0,75 ~1,25 mm² (P1P2) 0,75 ~1,25 mm² (P1P2)
Notes Tamb 35°C - LWE 18°C (DT=5°C) Tamb 35°C - LWE 18°C (DT=5°C)
  DB/WB 7°C/6°C - LWC 35°C (DT=5°C) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)
  Flow switch setting Flow switch setting
  The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value, depending on the distance and acoustic environment. The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value, depending on the distance and acoustic environment.
  Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases