Specifications Table for RQEQ-P3

RQEQ140PY13 RQEQ180PY13 RQEQ212PY13
Cooling capacity Nom. kW 14.0 (1) 18.0 (1) 21.2 (1)
Heating capacity Nom. kW 16.0 (2) 20.0 (2) 22.4 (2)
Dimensions Unit Height mm 1,680 1,680 1,680
    Width mm 635 635 635
    Depth mm 765 765 765
Weight Unit kg 175 175 179
Fan Air flow rate Cooling Nom. m³/min 95 110 110
Compressor Type   Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor
Operation range Cooling Min. °CDB -5 -5 -5
    Max. °CDB 43 43 43
  Heating Min. °CWB -20 -20 -20
    Max. °CWB 15.5 15.5 15.5
Sound power level Cooling Nom. dBA 79 83 87
Refrigerant Type   R-410A R-410A R-410A
  GWP   2,087.5 2,087.5 2,087.5
  Charge TCO2Eq 21.5 22.1 23.4
  Charge kg 10.3 10.6 11.2
Piping connections Liquid Type   Braze connection Braze connection Braze connection
    OD mm 9.52 9.52 9.52
  Gas Type   Braze connection Braze connection Braze connection
    OD mm 15.9 19.1 19.1
  Discharge gas OD mm 12.7 15.9 15.9
    Type   Braze connection Braze connection Braze connection
Power supply Name   Y1 Y1 Y1
  Phase   3~ 3~ 3~
  Frequency Hz 50 50 50
  Voltage V 380-415 380-415 380-415
Notes Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise.
  RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set.
  MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor
  Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%.
  Select wire size based on the larger value of MCA or TOCA Select wire size based on the larger value of MCA or TOCA Select wire size based on the larger value of MCA or TOCA
  MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases