RQYQ140PY1 RQYQ20PY1 RQYQ24PY1 RQYQ8PY1 RQYQ22PY1 RQYQ34PY1 RQYQ38PY1 RQYQ18PY1 RQYQ28PY1 RQYQ40PY1 RQYQ26PY1 RQYQ32PY1 RQYQ30PY1 RQYQ46PY1 RQYQ36PY1 RQYQ42PY1 RQYQ44PY1 RQYQ48PY1 RQYQ10PY1 RQYQ12PY1 RQYQ14PY1 RQYQ16PY1
System Outdoor unit module 1   RQYQ140P                                          
Recommended combinations 4 x FXSQ32A2VEB                                          
Cooling capacity Prated,c kW 14.0 (0.000)                                          
  Nom. 35°CDB kW 14.0 (1)       61.5 (1) 96.0 (1) 107 (1) 50.4 (1) 78.5 (1) 112 (1) 73.0 (1) 90.0 (1) 85.0 (1) 130 (1) 101 (1) 118 (1) 124 (1) 135 (1)       45.0 (1)
Heating capacity Nom. 6°CWB kW 16.0 (2)       69.0 (2) 108 (2) 119 (2) 56.5 (2) 87.5 (2) 125 (2) 81.5 (2) 100 (2) 95.0 (2) 145 (2) 113 (2) 132 (2) 138 (2) 150 (2)       50.0 (2)
  Prated,h kW 16.0 (0.000)                                          
Power input - 50Hz Cooling Nom. 35°CDB kW 3.36       17.8 26.9 31.4 12.9 23.7 33.8 21.3 27.2 25.2 38.8 28.9 34.9 35.3 40.8       13.6
  Heating Nom. 6°CWB kW 3.91       18.8 29.4 32.4 15.1 23.8 34.0 22.2 27.2 25.8 39.4 30.8 35.8 36.0 40.8       13.6
EER at nom. capacity 35°CDB kW/kW 4.17       3.46 3.57 3.41 3.91 3.31 3.31 3.43 3.31 3.37 3.35 3.49 3.38 3.51 3.31       3.31
COP at max. capacity 6°CWB kW/kW 4.09       3.67 3.67 3.67 3.74 3.68 3.68 3.67 3.68 3.68 3.68 3.67 3.69 3.83 3.68       3.68
ηs,c % 194                                          
ηs,h % 137                                          
Space cooling A Condition (35°C - 27/19) EERd   2.54                                          
    Pdc kW 14.0                                          
  B Condition (30°C - 27/19) EERd   4.40                                          
    Pdc kW 10.3                                          
  C Condition (25°C - 27/19) EERd   7.31                                          
    Pdc kW 6.63                                          
  D Condition (20°C - 27/19) EERd   9.29                                          
    Pdc kW 5.01                                          
Space heating (Average climate) TBivalent COPd (declared COP)   1.92                                          
    Pdh (declared heating cap) kW 8.5                                          
    Tbiv (bivalent temperature) °C -10                                          
  TOL COPd (declared COP)   1.92                                          
    Pdh (declared heating cap) kW 8.5                                          
  A Condition (-7°C) COPd (declared COP)   2.20                                          
    Pdh (declared heating cap) kW 7.52                                          
  B Condition (2°C) COPd (declared COP)   3.42                                          
    Pdh (declared heating cap) kW 4.58                                          
  C Condition (7°C) COPd (declared COP)   4.84                                          
    Pdh (declared heating cap) kW 3.29                                          
  D Condition (12°C) COPd (declared COP)   6.43                                          
    Pdh (declared heating cap) kW 4.18                                          
Capacity range HP 5 20 24 8 22 34 38 18 28 40 26 32 30 46 36 42 44 48 10 12 14 16
Maximum number of connectable indoor units 10                                          
Indoor index connection Min.   62.5                                          
  Nom.   125                                          
  Max.   162.5                                          
Dimensions Unit Height mm 1,680     1,680                             1,680 1,680 1,680 1,680
    Width mm 635     930                             930 930 1,240 1,240
    Depth mm 765     765                             765 765 765 765
Weight Unit kg 175     230                             284 284 381 381
Casing Colour   Ivory white (Munsell code: 5Y7.5/1)                                          
Heat exchanger Type   Cross fin coil                                          
  Air flow rate Cooling Rated m³/h 5,700 (0.000)                                          
    Heating Rated m³/h 5,700 (0.000)                                          
Fan Air flow rate Cooling Nom. m³/min 95                                         233
  External static pressure Max. Pa 78       78 78 78 78 78 78 78 78 78 78 78 78 78 78       78
  Type   Propeller fan                                          
Fan motor Quantity   1                                          
  Output W 350                                         350
  Drive   Direct drive                                          
Fan motor 2 Output W                                           350
Compressor Quantity   1                                          
  Type   Hermetically sealed scroll compressor                                          
  Output W 2,800                                         2,700
  Piston displacement m³/h 13.34                                         13.34
  Speed rpm 6,300                                         6,300
  Starting method   Soft start                                          
Compressor 2 Output W                                           4,500
  Piston displacement m³/h                                           10.53
  Speed rpm                                           2,900
Compressor 3 Output W                                           4,500
  Piston displacement m³/h                                           10.53
  Speed rpm                                           2,900
Operation range Cooling Min. °CDB -5       -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5 -5       -5
    Max. °CDB 43       43 43 43 43 43 43 43 43 43 43 43 43 43 43       43
  Heating Min. °CWB -20       -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20       -20
    Max. °CWB 15.5       15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5       15.5
Sound power level Cooling Nom. dBA 79                                          
  Heating Nom. dBA 79                                          
Sound pressure level Cooling Nom. dBA         63 64 65 61 63 65 63 63 63 65 64 65 65 65       60.0
Refrigerant Type   R-410A                                          
  GWP   2,087.5                                          
  Charge TCO2Eq 23.2                                         24.4
  Charge kg 11.1                                         11.7
  Control   Electronic expansion valve                                          
Piping connections Liquid Type   Braze connection                                          
    OD mm 9.52       15.9 19.1 19.1 15.9 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1       12.7
  Gas Type   Braze connection                                          
    OD mm 15.9       28.6 34.9 41.3 28.6 34.9 41.3 34.9 34.9 34.9 41.3 41.3 41.3 41.3 41.3       28.6
  Total piping length System Actual m 300       300 300 300 300 300 300 300 300 300 300 300 300 300 300       300
  Level difference OU - IU Outdoor unit in highest position m 50       50 50 50 50 50 50 50 50 50 50 50 50 50 50       50
      Indoor unit in highest position m 40       40 40 40 40 40 40 40 40 40 40 40 40 40 40       40
    IU - IU Max. m 15       15 15 15 15 15 15 15 15 15 15 15 15 15 15       15
  Piping length After branch Max. m 40       40 40 40 40 40 40 40 40 40 40 40 40 40 40       40
    OU - IU Max. m 150       150 150 150 150 150 150 150 150 150 150 150 150 150 150       150
Defrost method Deicer                                          
Capacity control Method   Inverter controlled                                          
  Steps % 25 ~ 100       7 ~ 100 5 ~ 100 4 ~ 100 9 ~ 100 5 ~ 100 4 ~ 100 6 ~ 100 5 ~ 100 5 ~ 100 3 ~ 100 4 ~ 100 4 ~ 100 4 ~ 100 3 ~ 100       10 ~ 100
Supplementary heater Back-up capacity Heating elbu kW 0.000                                          
Power consumption in other than active mode Crankcase heater Cooling PCK kW 0                                          
    Heating PCK kW 0.042                                          
  Off mode Cooling POFF kW 0.144                                          
    Heating POFF kW 0.042                                          
  Standby mode Cooling PSB kW 0.144                                          
    Heating PSB kW 0.042                                          
  Thermostat-off mode Cooling PTO kW 0.045                                          
    Heating PTO kW 0.080                                          
Cooling Cdc (Degradation cooling)   0.25                                          
Heating Cdh (Degradation heating)   0.25                                          
Safety devices Item 01   High pressure switch                                          
    02   Fan driver overload protector                                          
    03   Overcurrent relay                                          
    04   Inverter overload protector                                          
Power supply Name   Y1                                          
  Phase   3~                                          
  Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Voltage V 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415
Voltage range Min. % -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
  Max. % 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
Current Nominal running current (RLA) - 50Hz Compressor 1 Cooling A 4.8                                         6.1
    Compressor 2 Cooling A                                           7.6
    Compressor 3 Cooling A                                           7.6
Current - 50Hz Starting current (MSC) A         88 110 111 78 98 111 98 109 108 132 111 122 122 134       85
  Minimum circuit amps (MCA) A 11.9       44.3 74.7 75.8 40.1 54.2 76.9 53.1 63.0 63.0 94.5 75.8 84.6 85.7 94.5       31.5
  Maximum fuse amps (MFA) A 15       50 90 90 45 60 90 60 70 70 110 90 100 100 110       35
  Total overcurrent amps (TOCA) A 15.6       63.0 109.4 109.4 48.0 77.9 109.4 77.9 92.8 92.8 139.3 109.4 124.3 124.3 139.3       46.4
  Full load amps (FLA) Fan motor A 0.7                                         0.6
    Fan motor 2 A                                           0.6
Notes Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB TOCA means the total value of each OC set. RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set. MSC means the maximum current during start up of the compressor TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set.
  MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor MSC means the maximum current during start up of the compressor
  Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Maximum allowable voltage range variation between phases is 2%. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Select wire size based on the value of MCA or TOCA. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%.
  Select wire size based on the larger value of MCA or TOCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA
  MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. Contains fluorinated greenhouse gases Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. Contains fluorinated greenhouse gases Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise.
  Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases     Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases   Contains fluorinated greenhouse gases   Contains fluorinated greenhouse gases           Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases
Sound pressure level Cooling Nom. dBA   62 63 57.0                             58.0 60.0 60.0  
Refrigerant Refrigerant-=-Gwp   Electronic expansion valve Electronic expansion valve Electronic expansion valve                             Electronic expansion valve Electronic expansion valve Electronic expansion valve  
System Outdoor unit module 1   RQYQ12P RQYQ12P RQYQ8P RQYQ12P RQYQ14P RQYQ16P RQYQ10P RQYQ16P RQYQ16P RQYQ16P RQYQ16P RQYQ16P RQYQ16P RQYQ16P RQYQ16P RQYQ16P RQYQ16P RQYQ10P RQYQ12P RQYQ14P RQYQ16P
Operation range Cooling Max. °CDB   43 43 43                             43 43 43  
    Min. °CDB   -5 -5 -5                             -5 -5 -5  
  Heating Max. °CWB   15.5 15.5 15.5                             15.5 15.5 15.5  
    Min. °CWB   -20 -20 -20                             -20 -20 -20  
Power input - 50Hz Cooling Nom. kW   15.4 20.2 5.24                             7.64 10.10 11.6  
  Heating Nom. kW   16.7 20.4 6.42                             8.59 10.20 12.2  
Indoor index connection Indoor index connection-=-Max   500 600 200 550 850 950 450 700 1,000 650 800 750 1,150 900 1,050 1,100 1,200 250 300 350 400
Cooling capacity Nom. kW   55.9 (1) 67.0 (1) 22.4 (1)                             28.0 (1) 33.5 (1) 40.0 (1)  
Piping connections Liquid OD mm   15.9 15.9 9.52                             9.52 12.7 12.7  
    Type   Braze connection Braze connection Braze connection                             Braze connection Braze connection Braze connection  
  Total piping length System Actual m   300 300 300                             300 300 300  
  Piping length OU - IU Max. m   150 150 150                             150 150 150  
    After branch Max. m   40 40 40                             40 40 40  
  Gas OD mm   28.6 34.9 19.1                             22.2 28.6 28.6  
    Type   Braze connection Braze connection Braze connection                             Braze connection Braze connection Braze connection  
  Level difference OU - IU Outdoor unit in highest position m   50 50 50                             50 50 50  
      Indoor unit in highest position m   40 40 40                             40 40 40  
    IU - IU Max. m   15 15 15                             15 15 15  
Casing Colour   Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1) Ivory white (Munsell code: 5Y7.5/1)
Capacity control Steps %   8 ~ 100 6 ~ 100 20 ~ 100                             14 ~ 100 14 ~ 100 10 ~ 100  
Fan External static pressure Max. Pa   78 78 78                             78 78 78  
Heating capacity Nom. kW   62.5 (2) 75.0 (2) 25.0 (2)                             31.5 (2) 37.5 (2) 45.0 (2)  
Maximum number of connectable indoor units   3.63 3.32 Deicer 47 64 64 39 60 64 56 64 64 64 64 64 64 64 Deicer Deicer Deicer Deicer
Current - 50Hz Starting current (MSC) A   79 88                               74 75 84  
  Minimum circuit amps (MCA) A   41.2 45.4 18.5                             21.6 22.7 31.5  
  Total overcurrent amps (TOCA) A   48.0 63.0 16.5                             31.5 31.5 46.4  
  Maximum fuse amps (MFA) A   50 50 25                             25 25 35  
Power supply Phase   3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
Refrigerant Charge TCO2Eq       22.5                             24.4 24.4 24.4  
  Charge kg       10.8                             11.7 11.7 11.7  
Fan motor Output W       750                             750 750 350  
  Quantity       Direct drive                             Direct drive Direct drive Direct drive  
Heat exchanger Type       Cross fin coil                             Cross fin coil Cross fin coil Cross fin coil  
Safety devices Item 01       Inverter overload protector                             Inverter overload protector Inverter overload protector Inverter overload protector Inverter overload protector
Compressor Speed rpm       7,980                             6,300 6,300 6,300  
  Output W       4,500                             1,400 3,300 1,600  
  Piston displacement m³/h       16.90                             13.34 13.34 13.34  
  Quantity       Hermetically sealed scroll compressor                             Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor  
Fan Air flow rate Cooling Nom. m³/min       180                             185 200 233  
  Type       Propeller fan                             Propeller fan Propeller fan Propeller fan  
Current - 50Hz Full load amps (FLA) Fan motor A       0.7                             0.9 1.2 0.6  
Current Nominal running current (RLA) - 50Hz Compressor 1 Cooling A       8.2                             4.5 7.0 3.4  
Refrigerant Refrigerant-=-Refrigerant control         2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5       2,087.5
Piping connections Liquid Type         Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection       Braze connection
  Gas Type         Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection       Braze connection
Compressor 2 Piston displacement m³/h                                     10.53 10.53 10.53  
  Speed rpm                                     2,900 2,900 2,900  
  Output W                                     4,500 4,500 4,500  
  Starting method                                     Soft start Soft start Soft start  
Current Nominal running current (RLA) - 50Hz Compressor 2 Cooling A                                     6.8 6.7 7.5  
Compressor 3 Piston displacement m³/h                                         10.53  
  Output W                                         4,500  
  Speed rpm                                         2,900  
  Starting method                                         Soft start  
Fan motor 2 Output W                                         350  
  Drive                                         Direct drive  
Current - 50Hz Full load amps (FLA) Fan motor 2 A                                         0.6  
Current Nominal running current (RLA) - 50Hz Compressor 3 Cooling A                                         7.5  
Compressor 3 Compressor 3-=-Compressor 3 starting method                                           Soft start
Compressor 2 Compressor 2-=-Compressor 2 starting method                                           Soft start
Compressor Compressor-=-Compressor quantity                                           Hermetically sealed scroll compressor
  Compressor-=-Compressor starting method                                           Soft start
Fan motor Fan motor-=-Fan motor quantity                                           2
  Fan motor-=-Fan motor drive                                           Direct drive
Heat exchanger Heat exchanger-=-Heat exchanger type                                           Cross fin coil
Fan motor 2 Fan motor 2-=-Fan motor 2 drive                                           Direct drive
Fan Fan-=-Fan type                                           Propeller fan