Specifications Table for RXMLQ-T

RXMLQ8T7Y1B
PED Category   Category II
  Most critical part Name   Compressor
    Ps*V Bar*l 459
Dimensions Unit Height mm 1,685
    Width mm 1,240
    Depth mm 765
  Packed unit Height mm 1,820
    Width mm 1,305
    Depth mm 860
Weight Unit kg 302
  Packed unit kg 322
Packing Material   Carton
  Weight kg 3
Packing 2 Material   Wood
  Weight kg 19
Packing 3 Material   Plastic
  Weight kg 1
Casing Colour   Daikin White
  Material   Painted galvanized steel plate
Heat exchanger Type   Cross fin coil
  Indoor side   Air
  Outdoor side   Air
  Air flow rate Cooling Rated m³/h 10,290
    Heating Rated m³/h 13,554
Fan Quantity   2
  Diameter mm 541
  External static pressure Max. Pa 78
Fan motor Quantity   2
  Type   DC motor
  Output W 750
Compressor Quantity   1
  Type   Hermetically sealed scroll compressor
  Crankcase heater W 33
Operation range Cooling Min. °CDB -5
    Max. °CDB 43
  Heating Min. °CWB -25
    Max. °CWB 16
Sound power level Cooling Nom. dBA 75.0 (4)
Sound pressure level Cooling Nom. dBA 55.0 (5)
Refrigerant Type   R-410A
  GWP   2,087.5
  Charge TCO2Eq 24.6
  Charge kg 11.8
Refrigerant oil Type   Synthetic (ether) oil FVC68D
Piping connections Liquid Type   Braze connection
    OD mm 9,5
  Gas Type   Braze connection
    OD mm 19.1
  Total piping length System Actual m 500 (6)
  Level difference OU - IU Outdoor unit in highest position m 50
      Indoor unit in highest position m 40
    IU - IU Max. m 5
Defrost method Reversed cycle
Capacity control Method   Inverter controlled
Indication if the heater is equipped with a supplementary heater no
Supplementary heater Back-up capacity Heating elbu kW 0.0
Power consumption in other than active mode Crankcase heater mode Cooling PCK kW 0.000
    Heating PCK kW 0.0430
  Off mode Cooling POFF kW 0.0380
    Heating POFF kW 0.0380
  Standby mode Cooling PSB kW 0.0380
    Heating PSB kW 0.0380
  Thermostat-off mode Cooling PTO kW 0.0140
    Heating PTO kW 0.0610
Cooling Cdc (Degradation cooling)   0.25
Heating Cdh (Degradation heating)   0.25
Safety devices Item 01   High pressure switch
    02   Fan driver overload protector
    03   Inverter overload protector
    04   PC board fuse
Standard Accessories Installation manual 1
  Operation manual 2
  Connection pipes 25
Power supply Name   Y1
  Phase   3N~
  Frequency Hz 50
  Voltage V 380-415
Power supply intake Both indoor and outdoor unit
Voltage range Min. % -10
  Max. % 10
Current Nominal running current (RLA) - 50Hz Cooling A 10.1 (7)
Current - 50Hz Starting current (MSC) - remark   See note 8
  Zmax List   No requirements
  Minimum Ssc value kVa 5,638 (9.000)
  Minimum circuit amps (MCA) A 16.1 (10)
  Maximum fuse amps (MFA) A 20 (11)
  Total overcurrent amps (TOCA) A 42.5 (12)
  Full load amps (FLA) Total A 1.5 (13)
Wiring connections - 50Hz For power supply Quantity   5G
  For connection with indoor Quantity   2
    Remark   F1,F2
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal); level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (70% <= CR <= 130%)
  (4) - Sound power level is an absolute value that a sound source generates.
  (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
  (6) - Refer to refrigerant pipe selection or installation manual
  (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current.
  (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
  (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
  (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  (12) - TOCA means the total value of each OC set.
  (13) - FLA means the nominal running current of the fan