Specifications Table for RXYQQ-U

RXYQQ8U7Y1B RXYQQ10U7Y1B RXYQQ12U7Y1B RXYQQ14U7Y1B RXYQQ16U7Y1B RXYQQ18U7Y1B RXYQQ20U7Y1B RXYQQ22U7Y1B RXYQQ24U7Y1B RXYQQ26U7Y1B RXYQQ28U7Y1B RXYQQ30U7Y1B RXYQQ32U7Y1B RXYQQ34U7Y1B RXYQQ36U7Y1B RXYQQ38U7Y1B RXYQQ40U7Y1B RXYQQ42U7Y1B
System Outdoor unit module 1               RXYQQ10U   RXYQQ12U RXYQQ12U RXYQQ12U RXYQQ16U   RXYQQ16U RXYQQ8U    
  Outdoor unit module 2               RXYQQ12U   RXYQQ14U RXYQQ16U RXYQQ18U RXYQQ16U   RXYQQ20U RXYQQ10U    
  Outdoor unit module 3                               RXYQQ20U    
Recommended combination 2 4 x FXSQ50A2VEB 4 x FXSQ63A2VEB 6 x FXSQ50A2VEB   4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 3 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 2 x FXSQ50A2VEB + 6 x FXSQ63A2VEB 6 x FXSQ50A2VEB + 4 x FXSQ63A2VEB   7 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 6 x FXSQ50A2VEB + 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 9 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 8 x FXSQ63A2VEB + 4 x FXSQ80A2VEB   2 x FXSQ50A2VEB + 10 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 6 x FXSQ50A2VEB + 10 x FXSQ63A2VEB    
Recommended combination 3 4 x FXMQ50P7VEB 4 x FXMQ63P7VEB 6 x FXMQ50P7VEB   4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 3 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 2 x FXMQ50P7VEB + 6 x FXMQ63P7VEB 6 x FXMQ50P7VEB + 4 x FXMQ63P7VEB   7 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 6 x FXMQ50P7VEB + 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 9 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 8 x FXMQ63P7VEB + 4 x FXMQ80P7VEB   2 x FXMQ50P7VEB + 10 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 6 x FXMQ50P7VEB + 10 x FXMQ63P7VEB    
ESEER - Automatic 7.53 7.20 6.96   6.50 6.38 5.67 7.07   6.89 6.69 6.60 6.50   6.02 6.36    
ESEER - Standard 6.37 5.67 5.50   5.05 4.97 4.42 5.58   5.39 5.23 5.17 5.05   4.68 5.03    
SCOP recommended combination 2 4.2 4.3 4.1   4.1 4.2 4.0 4.4   4.2 4.2 4.3 4.2   4.2 4.3    
SCOP recommended combination 3 4.2 4.1 4.1   4.0 4.1 3.9 4.3   4.2 4.2 4.3 4.1   4.1 4.2    
SEER recommended combination 2 6.9 6.8 5.9   5.9 6.0 5.9 6.7   6.5 6.3 6.3 6.3   6.3 6.8    
SEER recommended combination 3 7.5 6.8 6.2   5.8 6.0 5.9 6.9   6.6 6.4 6.5 6.2   6.3 6.9    
Space cooling recommended combination 2 A Condition (35°C - 27/19) Pdc kW                               102.4    
  B Condition (30°C - 27/19) Pdc kW                               75.4    
  C Condition (25°C - 27/19) Pdc kW                               48.5    
  D Condition (20°C - 27/19) Pdc kW                               21.6    
Space cooling recommended combination 3 A Condition (35°C - 27/19) Pdc kW                               102.4    
  B Condition (30°C - 27/19) Pdc kW                               75.5    
  C Condition (25°C - 27/19) Pdc kW                               48.5    
  D Condition (20°C - 27/19) Pdc kW                               21.6    
Space heating (Average climate) recommended combination 2 A Condition (-7°C) Pdh (declared heating cap) kW                               53.7    
  B Condition (2°C) Pdh (declared heating cap) kW                               32.7    
  C Condition (7°C) Pdh (declared heating cap) kW                               21.3    
  D Condition (12°C) Pdh (declared heating cap) kW                               13.2    
  TBivalent COPd (declared COP)   2.4 2.4 1.9   2.2 1.9 1.8 2.2   2.2 2.2 2.1 2.4   2.2 2.3    
    Pdh (declared heating cap) kW 13.7 16.0 18.4   23.2 27.9 31.0 34.4   39.0 41.6 46.3 46.4   54.2 60.7    
    Tbiv (bivalent temperature) °C                               -10    
  TOL COPd (declared COP)   2.4 2.4 1.9   2.2 1.9 1.8 2.2   2.2 2.2 2.1 2.4   2.2 2.3    
    Pdh (declared heating cap) kW 13.7 16.0 18.4   23.2 27.9 31.0 34.4   39.0 41.6 46.3 46.4   54.2 60.7    
    Tol (temperature operating limit) °C                               -10    
Space heating (Average climate) recommended combination 3 A Condition (-7°C) Pdh (declared heating cap) kW                               53.7    
  B Condition (2°C) Pdh (declared heating cap) kW                               32.7    
  C Condition (7°C) Pdh (declared heating cap) kW                               21.2    
  D Condition (12°C) Pdh (declared heating cap) kW                               12.9    
  TBivalent COPd (declared COP)   2.5 2.4 2.0   2.2 1.9 1.8 2.3   2.2 2.2 2.1 2.4   2.1 2.2    
    Pdh (declared heating cap) kW 13.7 16.0 18.4   23.2 27.9 31.0 34.4   39.0 41.6 46.3 46.4   54.2 60.7    
    Tbiv (bivalent temperature) °C                               -10    
  TOL COPd (declared COP)   2.5 2.4 2.0   2.2 1.9 1.8 2.3   2.2 2.2 2.1 2.4   2.1 2.2    
    Pdh (declared heating cap) kW 13.7 16.0 18.4   23.2 27.9 31.0 34.4   39.0 41.6 46.3 46.4   54.2 60.7    
    Tol (temperature operating limit) °C                               -10    
Capacity range HP 8 10 12   16 18 20 22   26 28 30 32   36 38    
Maximum number of connectable indoor units 64 (3) 64 (3) 64 (3)   64 (3) 64 (3) 64 (3) 64 (3)   64 (3) 64 (3) 64 (3) 64 (3)   64 (3) 64 (3)    
Indoor index connection Min.   100.0 125.0 150.0   200.0 225.0 250.0 275.0   325.0 350.0 375.0 400.0   450.0 475.0    
  Max.   260.0 325.0 390.0   520.0 585.0 650.0 715.0   845.0 910.0 975.0 1,040.0   1,170.0 1,235.0    
Dimensions Unit Height mm 1,685 1,685 1,685   1,685 1,685 1,685                      
    Width mm 930 930 930   1,240 1,240 1,240                      
    Depth mm 765 765 765   765 765 765                      
Weight Unit kg 198 198 198   275 308 308                      
Fan External static pressure Max. Pa 78 78 78   78 78 78                      
Compressor Type   Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor   Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor                      
Sound power level Cooling Nom. dBA 78.0 (4) 79.1 (4) 83.4 (4)   85.6 (4) 83.8 (4) 87.9 (4) 84.8 (4)   85.3 (4) 87.6 (4) 86.6 (4) 88.6 (4)   89.9 (4) 88.8 (4)    
Sound pressure level Cooling Nom. dBA 57.0 (5) 57.0 (5) 61.0 (5)   63.0 (5) 62.0 (5) 65.0 (5) 62.5 (5)   63.5 (5) 65.1 (5) 64.5 (5) 66.0 (5)   67.1 (5) 66.2 (5)    
Refrigerant Type   R-410A R-410A R-410A   R-410A R-410A R-410A R-410A   R-410A R-410A R-410A R-410A   R-410A R-410A    
  GWP   2,087.5 2,087.5 2,087.5   2,087.5 2,087.5 2,087.5 2,087.5   2,087.5 2,087.5 2,087.5 2,087.5   2,087.5 2,087.5    
  Charge TCO2Eq 12.3 12.5 13.2   23.6 24.4 24.6                      
  Charge kg 5.9 6.0 6.3   11.3 11.7 11.8                      
Piping connections Liquid Type   Braze connection Braze connection Braze connection   Braze connection Braze connection Braze connection Braze connection   Braze connection Braze connection Braze connection Braze connection   Braze connection Braze connection    
    OD mm 9,52 9,52 12,7   12,7 15,9 15,9 15,9   19,1 19,1 19,1 19,1   19,1 19,1    
  Gas Type   Braze connection Braze connection Braze connection   Braze connection Braze connection Braze connection Braze connection   Braze connection Braze connection Braze connection Braze connection   Braze connection Braze connection    
    OD mm 19.1 22.2 28.6   28.6 28.6 28.6 28.6   34.9 34.9 34.9 34.9   41.3 41.3    
  Total piping length System Actual m 300 (6) 300 (6) 300 (6)   300 (6) 300 (6) 300 (6) 300 (6)   300 (6) 300 (6) 300 (6) 300 (6)   300 (6) 300 (6)    
Standard Accessories Installation manual 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
  Operation manual 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
  Connection pipes 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Power supply Name   Y1 Y1 Y1   Y1 Y1 Y1 Y1   Y1 Y1 Y1 Y1   Y1 Y1    
  Phase   3N~ 3N~ 3N~   3N~ 3N~ 3N~ 3N~   3N~ 3N~ 3N~ 3N~   3N~ 3N~    
  Frequency Hz 50 50 50   50 50 50 50   50 50 50 50   50 50    
  Voltage V 380-415 380-415 380-415   380-415 380-415 380-415 380-415   380-415 380-415 380-415 380-415   380-415 380-415    
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%)
  (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates.
  (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
  (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual
  (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current.
  (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
  (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
  (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan
  (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%.
  (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature )
  (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality
  (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room.
  (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
  (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
  (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power
  (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual
  (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination
Space cooling recommended combination 2 A Condition (35°C - 27/19) EERd                                 2.3    
  B Condition (30°C - 27/19) EERd                                 4.5    
  C Condition (25°C - 27/19) EERd                                 8.4    
  D Condition (20°C - 27/19) EERd                                 17.8    
Space cooling recommended combination 3 A Condition (35°C - 27/19) EERd                                 2.4    
  B Condition (30°C - 27/19) EERd                                 4.5    
  C Condition (25°C - 27/19) EERd                                 8.5    
  D Condition (20°C - 27/19) EERd                                 17.9    
Space heating (Average climate) recommended combination 2 A Condition (-7°C) COPd (declared COP)                                 2.5    
  B Condition (2°C) COPd (declared COP)                                 3.9    
  C Condition (7°C) COPd (declared COP)                                 6.5    
  D Condition (12°C) COPd (declared COP)                                 8.8    
Space heating (Average climate) recommended combination 3 A Condition (-7°C) COPd (declared COP)                                 2.5    
  B Condition (2°C) COPd (declared COP)                                 3.8    
  C Condition (7°C) COPd (declared COP)                                 6.3    
  D Condition (12°C) COPd (declared COP)                                 8.5