Specifications Table for RZAG-LV1

RZAG71L7V1B RZAG100L7V1B RZAG125L7V1B RZAG140L7V1B
Dimensions Unit Height mm 990 1,430 1,430 1,430
    Width mm 940 940 940 940
    Depth mm 320 320 320 320
Weight Unit kg 67 93 93 93
Compressor Type   Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor
Operation range Cooling Ambient Min. °CDB -15 -15 -15 -15
      Max. °CDB 50 50 50 50
  Heating Ambient Min. °CWB -20 -20 -20 -20
      Max. °CWB 15.5 15.5 15.5 15.5
Sound power level Cooling dBA 64 (0.000) 64 (0.000) 66 (0.000) 67 (0.000)
Sound pressure level Cooling Nom. dBA 48 49 51 52
  Heating Nom. dBA 50 51 52 52
  Night quiet mode Level 1 dBA 43 45 45 45
Refrigerant Type   R-32 R-32 R-32 R-32
  Charge kg 2.6 3.4 3.4 3.4
  Charge TCO2Eq 1.8 2.3 2.3 2.3
  GWP   675 675 675 675
Piping connections Additional refrigerant charge kg/m See installation manual See installation manual See installation manual See installation manual
  Level difference IU - OU Max. m 30.0 30.0 30.0 30.0
    IU - IU Max. m 0.5 0.5 0.5 0.5
Standard Accessories Tie-wraps 2 2 2 2
  Installation manual 1 1 1 1
Power supply Phase   1~ 1~ 1~ 1~
  Frequency Hz 50/60 50/60 50/60 50/60
  Voltage V 220-240 220-240 220-240 220-240
Notes Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases
  Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series
  Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series
  See separate drawing for electrical data See separate drawing for electrical data See separate drawing for electrical data See separate drawing for electrical data