Specifications Table for SB.RKXYQ-TA

SB.RKXYQ5TAY1B
System Heat exchanger unit   RDXYQ5TA
  Compressor unit   RKXYQ5TA
Capacity range HP 5
Maximum number of connectable indoor units 10 (3)
Indoor index connection Min.   100
  Nom.   125
  Max.   162.5
Fan External static pressure Max. Pa 150
Refrigerant Type   R-410A
Piping connections Between Compressor module (CM) and heat exchanger module (HM) Liquid OD mm 12.7
    Gas OD mm 22.2
    Piping length Max. m 30.0
    Level difference CM below HM m 10.0
      CM above HM m 10.0
  Between Compressor module (CM) and indoor units (IU) Liquid OD mm 9.52
    Gas OD mm 15.9
    Level difference CM below IU m 30.0
      CM above IU m 30.0
  Total piping length System Actual m 140 (6)
  Level difference IU - IU Max. m 15
Notes (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series
  (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series
  (3) - Actual number of units depends on the indoor unit type (VRV DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤ 130%).
  (4) - The sound power level is an absolute value indicating the power which a sound source generates.
  (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to sound level drawings. Nominal air flow rate, ESP 60 Pa.
  (6) - Refer to refrigerant pipe selection or installation manual
  (7) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
  (8) - Sound values are measured in a semi-anechoic room.
  (9) - Contains fluorinated greenhouse gases