ADEQ71B2VEB / AZQS71B2V1B |
ADEQ100B2VEB / AZQS100B8V1B |
ADEQ125B2VEB / AZQS125B8V1B |
Poff (Off mode) |
W |
14.5 |
22.0 |
|
Cooling |
Psb (Standby mode cooling) |
W |
14.5 |
22.0 |
|
|
Cdc (Degradation cooling) |
0.25 |
0.25 |
|
Seasonal efficiency (according to EN14825) |
Cooling |
Pdesign |
kW |
6.80 |
9.50 |
|
|
|
Annual energy consumption |
kWh |
441 |
652 |
|
|
|
Energy efficiency class |
5.40 |
5.10 |
|
|
|
D Condition (20°C - 27/19) |
Pdc |
kW |
3.76 |
3.94 |
|
|
|
|
power input |
kW |
0.42 |
0.51 |
|
|
|
|
EERd |
9.03 |
7.78 |
|
|
|
C Condition (25°C - 27/19) |
power input |
kW |
0.51 |
0.71 |
|
|
|
|
Pdc |
kW |
3.63 |
4.50 |
|
|
|
|
EERd |
7.16 |
6.31 |
|
|
|
A Condition (35°C - 27/19) |
power input |
kW |
2.12 |
2.96 |
|
|
|
|
Pdc |
kW |
6.80 |
9.50 |
|
|
|
|
EERd |
3.21 |
3.21 |
|
|
|
B Condition (30°C - 27/19) |
Pdc |
kW |
5.01 |
7.00 |
|
|
|
|
power input |
kW |
1.15 |
1.57 |
|
|
|
|
EERd |
4.35 |
4.46 |
|
|
Heating (Average climate) |
Annual energy consumption |
kWh |
2,205 |
2,792 |
|
|
|
Pdesign |
kW |
6.00 |
7.60 |
|
|
|
Required back up heating cap at design conditions |
kW |
1.25 |
1.83 |
|
|
|
SCOPnet/A |
A |
A |
|
|
|
TBivalent |
Pdh (declared heating cap) |
kW |
5.31 |
6.72 |
|
|
|
|
Power input |
kW |
2.45 |
2.37 |
|
|
|
|
Tbiv (bivalent temperature) |
°C |
-7 |
-7 |
|
|
|
|
COPd (declared COP) |
2.17 |
2.84 |
|
|
|
C Condition (7°C) |
Pdh (declared heating cap) |
kW |
2.83 |
2.82 |
|
|
|
|
Power input |
kW |
0.51 |
0.66 |
|
|
|
|
COPd (declared COP) |
5.55 |
4.28 |
|
|
|
TOL |
Tol (temperature operating limit) |
°C |
-15 |
-15 |
|
|
|
|
Pdh (declared heating cap) |
kW |
3.81 |
4.18 |
|
|
|
|
Power input |
kW |
2.28 |
2.06 |
|
|
|
|
COPd (declared COP) |
1.67 |
2.03 |
|
|
|
A Condition (-7°C) |
Pdh (declared heating cap) |
kW |
5.31 |
6.72 |
|
|
|
|
Power input |
kW |
2.45 |
2.37 |
|
|
|
|
COPd (declared COP) |
2.17 |
2.84 |
|
|
|
D Condition (12°C) |
Pdh (declared heating cap) |
kW |
3.27 |
2.93 |
|
|
|
|
Power input |
kW |
0.50 |
0.55 |
|
|
|
|
COPd (declared COP) |
6.55 |
5.31 |
|
|
|
B Condition (2°C) |
Power input |
kW |
0.84 |
1.04 |
|
|
|
|
Pdh (declared heating cap) |
kW |
3.23 |
4.09 |
|
|
|
|
COPd (declared COP) |
3.85 |
3.94 |
|
Cooling capacity |
Nom. |
kW |
6.8 (2) |
9.5 (2) |
12.1 (2) |
Pck (Crankcase heater mode) |
W |
0.0 |
0.0 |
|
Nominal efficiency |
Annual energy consumption |
kWh |
1,059 (0.000) |
1,480 (0.000) |
1,945 (0.000) |
|
Energy labeling Directive |
Heating |
A |
A |
B |
|
COP |
3.21 (1) |
3.21 (1) |
3.11 (1) |
Heating |
Cdh (Degradation heating) |
0.25 |
0.25 |
|
Heating capacity |
Nom. |
kW |
7.50 (2) |
10.8 (2) |
13.50 (2) |
Pto (Thermostat off) |
W |
3.0 |
4.0 |
|
Power input |
Cooling |
Nom. |
kW |
2.12 |
2.96 |
3.89 |
|
Heating |
Nom. |
kW |
2.08 |
2.99 |
3.91 |
Indoor unit |
Yes |
Yes |
AZQS125B8V1 |
Notes |
EER/COP according to Eurovent 2012, for use outside EU only |
EER/COP according to Eurovent 2012, for use outside EU only |
EER/COP according to Eurovent 2012, for use outside EU only |
|
Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load |
Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load |
Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load |
|
|
PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC |
PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC |
|
|
Minimum Ssc (=Short-circuit power) value: Equipment complying with EN 61000-3-2 |
Minimum Ssc (=Short-circuit power) value: Equipment complying with EN 61000-3-2 |
|
|
See separate drawing for electrical data |
See separate drawing for electrical data |
|
|
Contains fluorinated greenhouse gases |
Contains fluorinated greenhouse gases |