EBLQ011CA3V3 |
EBLQ014CA3V3 |
EBLQ016CA3V3 |
Heating capacity |
Nom. |
kW |
11.2 (1), 11.0 (2) |
14.5 (1), 13.6 (2) |
16.0 (1), 15.2 (2) |
Cooling capacity |
Nom. |
kW |
12.4 (1), 11.6 (2) |
12.8 (1), 12.6 (2) |
13.9 (1), 13.6 (2) |
Heater capacity |
Step 1 |
kW |
3 |
3 |
3 |
Power input |
Cooling |
Nom. |
kW |
3.18 (1), 5.09 (2) |
3.16 (1), 5.14 (2) |
3.56 (1), 5.96 (2) |
|
Heating |
Nom. |
kW |
2.43 (1), 3.10 (2) |
3.37 (1), 4.10 (2) |
3.76 (1), 4.66 (2) |
COP |
4.61 (1), 3.55 (2) |
4.30 (1), 3.32 (2) |
4.26 (1), 3.26 (2) |
EER |
3.90 (1), 2.28 (2) |
4.05 (1), 2.45 (2) |
3.90 (1), 2.28 (2) |
Dimensions |
Unit |
Height |
Mm |
1,348 |
1,348 |
1,348 |
|
|
Width |
Mm |
1,160 |
1,160 |
1,160 |
|
|
Depth |
Mm |
380 |
380 |
380 |
Weight |
Unit |
kg |
157 |
157 |
157 |
Sound power level |
Heating |
Nom. |
dBA |
64 (6) |
64 (6) |
66 (6) |
|
Cooling |
Nom. |
dBA |
64 (7) |
66 (7) |
69 (7) |
Sound pressure level |
Heating |
Nom. |
dBA |
51 (8) |
51 (8) |
52 (8) |
|
Cooling |
Nom. |
dBA |
50 (8) |
52 (8) |
54 (8) |
Refrigerant |
Type |
|
R-410A |
R-410A |
R-410A |
|
GWP |
|
2,087.5 |
2,087.5 |
2,087.5 |
|
Charge |
kg |
3.40 |
3.40 |
3.40 |
|
Charge |
TCO2Eq |
7.10 |
7.10 |
7.10 |
Power supply |
Name |
|
V3 |
V3 |
V3 |
|
Phase |
|
1~ |
1~ |
1~ |
|
Frequency |
Hz |
50 |
50 |
50 |
|
Voltage |
V |
230 |
230 |
230 |
Notes |
(1) - Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) |
(1) - Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) |
(1) - Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) |
|
(2) - Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) |
(2) - Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) |
(2) - Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) |
|
(3) - Condition 3: heating Ta DB -7°C (RH85%) - LWC 35°C |
(3) - Condition 3: heating Ta DB -7°C (RH85%) - LWC 35°C |
(3) - Condition 3: heating Ta DB -7°C (RH85%) - LWC 35°C |
|
(4) - Condition 4: heating Ta DB -7°C (RH85%) - LWC 45°C |
(4) - Condition 4: heating Ta DB -7°C (RH85%) - LWC 45°C |
(4) - Condition 4: heating Ta DB -7°C (RH85%) - LWC 45°C |
|
(5) - Including BUH and / or booster heater. For more details see data-book |
(5) - Including BUH and / or booster heater. For more details see data-book |
(5) - Including BUH and / or booster heater. For more details see data-book |
|
(6) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) |
(6) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) |
(6) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) |
|
(7) - Condition: Ta 35°C - LWE 7°C ( DT = 5°C) |
(7) - Condition: Ta 35°C - LWE 7°C ( DT = 5°C) |
(7) - Condition: Ta 35°C - LWE 7°C ( DT = 5°C) |
|
(8) - The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. |
(8) - The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. |
(8) - The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. |
|
(9) - Including piping + PHE; excluding expansion vessel |
(9) - Including piping + PHE; excluding expansion vessel |
(9) - Including piping + PHE; excluding expansion vessel |