Specifications Table for ETBX16E6V / EPRA014-018DV

ETBX16EF6V / EPRA14DAV3 ETBX16EF6V / EPRA16DAV3 ETBX16EF6V / EPRA18DAV3
Heating capacity Min. kW 3.70 (1) 3.96 (1) 4.40 (1)
  Nom. kW 5.69 (2) 9.00 (2) 9.00 (2)
  Max. kW 10.18 (1) 10.91 (1) 12.12 (1)
Cooling capacity Nom. kW 10.6 (3), 6.90 (4) 11.5 (3), 7.88 (4) 12.5 (3), 8.86 (4)
Power input Heating Min. kW 0.88 (5) 0.95 (5) 1.05 (5)
    Nom. kW 1.22 (2) 1.80 (2) 1.80 (2)
    Max. kW 2.09 (5) 2.24 (5) 2.49 (5)
  Cooling Nom. kW 2.55 (3), 2.56 (4) 2.80 (3), 2.93 (4) 3.05 (3), 3.31 (4)
COP 4.67 (2) 5.00 (2) 5.00 (2)
EER 4.13 (3), 2.70 (4) 4.11 (3), 2.69 (4) 4.09 (3), 2.68 (4)
Space heating Average climate water outlet 55°C General SCOP   3.62 3.62 3.62
      Seasonal space heating eff. class   A++ A++ A++
      ηs (Seasonal space heating efficiency) % 142 142 142
  Average climate water outlet 35°C General SCOP   4.57 4.57 4.57
      Seasonal space heating eff. class   A+++ A+++ A+++
      ηs (Seasonal space heating efficiency) % 180 180 180
Notes (1) - Capacity according to standard EN14511 and valid for heated water range dT = 3~8°C at Ta 7°C (1) - Capacity according to standard EN14511 and valid for heated water range dT = 3~8°C at Ta 7°C (1) - Capacity according to standard EN14511 and valid for heated water range dT = 3~8°C at Ta 7°C
  (2) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (2) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (2) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
  (3) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB (3) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB (3) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB
  (4) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB (4) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB (4) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB
  (5) - Power input is total input of indoor and outdoor units, including the circulation pump; according to EN14511 (5) - Power input is total input of indoor and outdoor units, including the circulation pump; according to EN14511 (5) - Power input is total input of indoor and outdoor units, including the circulation pump; according to EN14511
  (6) - Test at Ta DB/WB 7°C/6°C. According to EN 16147. (6) - Test at Ta DB/WB 7°C/6°C. According to EN 16147. (6) - Test at Ta DB/WB 7°C/6°C. According to EN 16147.
  (7) - DB/WB 7°C/6°C - LWC 35°C (dT=5°C) with pump at full speed (7) - DB/WB 7°C/6°C - LWC 35°C (dT=5°C) with pump at full speed (7) - DB/WB 7°C/6°C - LWC 35°C (dT=5°C) with pump at full speed