EWAD290T-SSB2 |
EWAD330T-SSB2 |
EWAD370T-SSB2 |
EWAD510T-SSB2 |
EWAD520T-SSB2 |
EWAD580T-SSB2 |
EWAD700T-SSB2 |
EWAD800T-SSB2 |
EWAD940T-SSB2 |
EWADC10T-SSB2 |
EWADH10T-SSB2 |
EWADC11T-SSB2 |
EWADH12T-SSB2 |
EWADH13T-SSB2 |
EWADH14T-SSB2 |
EWADH15T-SSB3 |
EWADH16T-SSB3 |
EWADC17T-SSB3 |
EWADH18T-SSB3 |
EWADC19T-SSB3 |
EWADC20T-SSB3 |
EWADC21T-SSB3 |
Cooling capacity |
Nom. |
kW |
290.7 |
334.5 |
373.4 |
505.8 |
522.7 |
575.8 |
701.3 |
809.9 |
936.3 |
999.7 |
1,051 |
1,135 |
1,268 |
1,352 |
1,456 |
1,579 |
1,684 |
1,762 |
1,871 |
1,967 |
2,065 |
2,148 |
Capacity control |
Method |
|
Fixed |
Fixed |
Fixed |
Fixed |
Fixed |
Fixed |
Fixed |
Fixed |
Fixed |
Fixed |
Fixed |
Fixed |
Fixed |
Fixed |
Fixed |
Stepless |
Stepless |
Stepless |
Stepless |
Stepless |
Stepless |
Stepless |
|
Minimum capacity |
% |
12.5 |
12.5 |
12.5 |
12.5 |
12.5 |
12.5 |
12.5 |
12.5 |
12.5 |
12.5 |
12.5 |
12.5 |
12.5 |
12.5 |
12.5 |
8.3 |
8.3 |
8.3 |
8.3 |
8.3 |
8.3 |
8.3 |
Power input |
Cooling |
Nom. |
kW |
92.73 |
111.6 |
120.8 |
166.6 |
171 |
189.6 |
234.1 |
266.1 |
308.3 |
340.7 |
362.4 |
387.9 |
438.8 |
464.4 |
490.7 |
534 |
563 |
605.3 |
654.1 |
682.5 |
710 |
735.3 |
EER |
3.135 |
2.996 |
3.09 |
3.037 |
3.057 |
3.036 |
2.996 |
3.043 |
3.037 |
2.934 |
2.903 |
2.928 |
2.89 |
2.913 |
2.969 |
2.956 |
2.992 |
2.912 |
2.861 |
2.882 |
2.908 |
2.922 |
ESEER |
3.86 |
3.73 |
3.74 |
3.87 |
3.95 |
4.05 |
3.87 |
3.89 |
3.82 |
3.89 |
3.74 |
3.77 |
3.77 |
3.79 |
3.8 |
3.89 |
3.93 |
3.88 |
3.73 |
3.71 |
3.66 |
3.71 |
Dimensions |
Unit |
Depth |
mm |
3,230 |
3,230 |
4,130 |
4,130 |
5,030 |
5,030 |
5,976 |
5,976 |
6,876 |
6,876 |
6,876 |
7,776 |
7,776 |
8,676 |
9,576 |
10,509 |
11,409 |
11,409 |
11,409 |
12,309 |
13,209 |
14,109 |
|
|
Height |
mm |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
2,537 |
|
|
Width |
mm |
2,258 |
2,258 |
2,258 |
2,258 |
2,258 |
2,258 |
2,282 |
2,282 |
2,282 |
2,282 |
2,282 |
2,282 |
2,282 |
2,282 |
2,282 |
2,282 |
2,282 |
2,282 |
2,282 |
2,282 |
2,282 |
2,282 |
Weight |
Operation weight |
kg |
3,161 |
3,161 |
4,274 |
4,894 |
5,030 |
5,030 |
5,825 |
5,825 |
6,188 |
6,188 |
6,710 |
6,981 |
7,272 |
8,554 |
8,887 |
10,460 |
11,446 |
11,446 |
11,589 |
11,855 |
12,237 |
12,457 |
|
Unit |
kg |
3,061 |
3,061 |
4,104 |
4,724 |
4,860 |
4,860 |
5,527 |
5,525 |
5,858 |
5,858 |
6,229 |
6,520 |
6,780 |
8,084 |
8,426 |
9,938 |
10,575 |
10,575 |
10,636 |
10,902 |
11,202 |
11,422 |
Water heat exchanger |
Type |
|
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
|
Water volume |
l |
89 |
89 |
181 |
164 |
170 |
164 |
298 |
300 |
330 |
330 |
481 |
461 |
492 |
470 |
461 |
522 |
871 |
871 |
953 |
953 |
1,035 |
1,035 |
Air heat exchanger |
Type |
|
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Microchannel |
Fan |
Air flow rate |
Nom. |
l/s |
33,129 |
33,129 |
44,172 |
44,172 |
55,214 |
55,214 |
66,257 |
66,257 |
77,300 |
77,300 |
77,300 |
88,343 |
88,343 |
99,386 |
110,429 |
121,472 |
132,515 |
132,515 |
132,515 |
143,557 |
154,600 |
165,643 |
|
Speed |
rpm |
900 |
900 |
900 |
900 |
900 |
900 |
900 |
900 |
900 |
900 |
900 |
900 |
900 |
900 |
900 |
900 |
900 |
900 |
900 |
900 |
900 |
900 |
Compressor |
Quantity |
|
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
|
Type |
|
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Driven vapour compression |
Sound power level |
Cooling |
Nom. |
dBA |
98 |
98 |
98 |
101 |
101 |
101 |
101 |
101 |
101 |
102 |
102 |
102 |
102 |
103 |
103 |
103 |
103 |
103 |
103 |
103 |
103 |
103 |
Sound pressure level |
Cooling |
Nom. |
dBA |
78 |
78 |
78 |
81 |
81 |
81 |
83 |
84 |
84 |
84 |
84 |
84 |
84 |
84 |
84 |
80 |
80 |
80 |
80 |
80 |
80 |
80 |
Refrigerant |
Type |
|
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
|
GWP |
|
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
|
Circuits |
Quantity |
|
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
|
Charge |
kg |
50 |
50 |
55 |
58 |
66 |
67 |
93.6 |
93.6 |
109.2 |
109.2 |
109.2 |
124.8 |
124.8 |
140.4 |
156 |
172 |
187 |
187 |
187 |
203 |
218 |
234 |
Charge |
Per circuit |
TCO2Eq |
35.75 |
35.75 |
39.32 |
41.47 |
47.19 |
47.90 |
66.92 |
66.92 |
78.08 |
78.08 |
78.08 |
89.23 |
89.23 |
100.39 |
111.54 |
|
|
|
|
|
|
|
Power supply |
Phase |
|
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
|
Frequency |
Hz |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
|
Voltage |
V |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
Compressor |
Starting method |
|
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Wye-Delta |
Notes |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
|
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
(2) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for info only, not considered bounding |
|
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
(3) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition |
|
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
(4) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. |
|
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
(5) - All data refers to the standard unit without options. |
|
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(6) - All data are subject to change without notice. Please refer to the unit nameplate data. |
|
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
(7) - Fluid: Water |
|
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(8) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
|
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
(9) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. |
|
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
(10) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. |
|
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
(11) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current |
|
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(12) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
|
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
(13) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 |
|
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |
(14) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book |