EWWD450VZXSA1 |
EWWD500VZXSA1 |
EWWD610VZXSA1 |
EWWD710VZXSA1 |
EWWD800VZXSA1 |
EWWD900VZXSA1 |
EWWDC11VZXSA1 |
EWWDC12VZXSA2 |
EWWDC13VZXSA2 |
EWWDC14VZXSA2 |
EWWDC16VZXSA2 |
EWWDC17VZXSA2 |
EWWDC19VZXSA2 |
EWWDC21VZXSA2 |
Cooling capacity |
Nom. |
kW |
449 |
501 |
613 |
713 |
794 |
901 |
1,053 |
1,194 |
1,305 |
1,407 |
1,593 |
1,748 |
1,912 |
2,074 |
Capacity control |
Method |
|
Variable |
Variable |
Variable |
Variable |
Variable |
Variable |
Variable |
Variable |
Variable |
Variable |
Variable |
Variable |
Variable |
Variable |
|
Minimum capacity |
% |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
Power input |
Cooling |
Nom. |
kW |
81.2 |
89.7 |
108 |
128 |
146 |
159 |
192 |
221 |
244 |
262 |
296 |
329 |
365 |
394 |
EER |
5.53 |
5.58 |
5.64 |
5.54 |
5.43 |
5.67 |
5.46 |
5.38 |
5.34 |
5.36 |
5.38 |
5.31 |
5.23 |
5.25 |
ESEER |
7.51 |
7.92 |
8.1 |
8.2 |
8.22 |
7.92 |
8.17 |
8.36 |
8.25 |
8.47 |
8.24 |
8.45 |
8.2 |
8.33 |
Dimensions |
Unit |
Depth |
Mm |
3,722 |
3,722 |
3,750 |
3,690 |
3,690 |
3,822 |
3,822 |
4,792 |
4,792 |
4,508 |
4,508 |
4,750 |
4,874 |
4,874 |
|
|
Height |
Mm |
2,135 |
2,135 |
2,123 |
2,235 |
2,235 |
2,487 |
2,487 |
2,296 |
2,296 |
2,301 |
2,350 |
2,500 |
2,469 |
2,493 |
|
|
Width |
Mm |
1,178 |
1,178 |
1,179 |
1,189 |
1,189 |
1,303 |
1,303 |
1,484 |
1,639 |
1,579 |
1,580 |
1,610 |
1,704 |
1,769 |
Weight |
Unit |
kg |
2,968 |
2,911 |
3,102 |
3,470 |
3,451 |
4,257 |
4,552 |
5,860 |
6,240 |
6,520 |
6,920 |
7,530 |
7,790 |
8,670 |
|
Operation weight |
kg |
3,098 |
3,006 |
3,274 |
3,648 |
3,611 |
4,518 |
4,860 |
6,370 |
6,760 |
7,130 |
7,530 |
8,300 |
8,560 |
9,630 |
Water heat exchanger - evaporator |
Type |
|
Flooded shell and tube |
Flooded shell and tube |
Flooded shell and tube |
Flooded shell and tube |
Flooded shell and tube |
Flooded shell and tube |
Flooded shell and tube |
Flooded shell and tube |
Flooded shell and tube |
Flooded shell and tube |
Flooded shell and tube |
Flooded shell and tube |
Flooded shell and tube |
Flooded shell and tube |
|
Water volume |
l |
70 |
88 |
136 |
134 |
134 |
168 |
199 |
270 |
270 |
320 |
320 |
380 |
480 |
480 |
Water heat exchanger - condenser |
Type |
|
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Shell and tube |
Compressor |
Type |
|
Driven vapour compressor |
Driven vapour compressor |
Driven vapour compressor |
Driven vapour compressor |
Driven vapour compressor |
Driven vapour compressor |
Driven vapour compressor |
Driven vapour compressor |
Driven vapour compressor |
Driven vapour compressor |
Driven vapour compressor |
Driven vapour compressor |
Driven vapour compressor |
Driven vapour compressor |
|
Quantity |
|
1 |
1 |
1 |
1 |
1 |
1 |
1 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
Sound power level |
Cooling |
Nom. |
dBA |
97 |
99 |
101 |
105 |
105 |
105 |
107 |
106 |
106 |
107 |
107 |
108 |
109 |
110 |
Sound pressure level |
Cooling |
Nom. |
dBA |
78 |
80 |
82 |
86 |
86 |
86 |
88 |
87 |
87 |
88 |
88 |
89 |
89 |
90 |
Refrigerant |
Type |
|
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
R-134a |
|
Charge |
kg |
95 |
95 |
100 |
110 |
170 |
170 |
180 |
250 |
260 |
290 |
290 |
320 |
320 |
350 |
|
Circuits |
Quantity |
|
1 |
1 |
1 |
1 |
1 |
1 |
1 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
|
GWP |
|
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
1,430 |
Power supply |
Phase |
|
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
|
Frequency |
Hz |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
|
Voltage |
V |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
Notes |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 |
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 |
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 |
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 |
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 |
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 |
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 |
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 |
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 |
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 |
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 |
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 |
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 |
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 |
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 |
|
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. |
|
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C |
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C |
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C |
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C |
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C |
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C |
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C |
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C |
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C |
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C |
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C |
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C |
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C |
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C |
|
(5) - Maximum running current is based on max compressor absorbed current in its envelope |
(5) - Maximum running current is based on max compressor absorbed current in its envelope |
(5) - Maximum running current is based on max compressor absorbed current in its envelope |
(5) - Maximum running current is based on max compressor absorbed current in its envelope |
(5) - Maximum running current is based on max compressor absorbed current in its envelope |
(5) - Maximum running current is based on max compressor absorbed current in its envelope |
(5) - Maximum running current is based on max compressor absorbed current in its envelope |
(5) - Maximum running current is based on max compressor absorbed current in its envelope |
(5) - Maximum running current is based on max compressor absorbed current in its envelope |
(5) - Maximum running current is based on max compressor absorbed current in its envelope |
(5) - Maximum running current is based on max compressor absorbed current in its envelope |
(5) - Maximum running current is based on max compressor absorbed current in its envelope |
(5) - Maximum running current is based on max compressor absorbed current in its envelope |
(5) - Maximum running current is based on max compressor absorbed current in its envelope |
|
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage. |
|
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1 |
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1 |
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1 |
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1 |
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1 |
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1 |
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1 |
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1 |
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1 |
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1 |
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1 |
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1 |
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1 |
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1 |
|
(8) - All data refers to the standard unit without options. |
(8) - All data refers to the standard unit without options. |
(8) - All data refers to the standard unit without options. |
(8) - All data refers to the standard unit without options. |
(8) - All data refers to the standard unit without options. |
(8) - All data refers to the standard unit without options. |
(8) - All data refers to the standard unit without options. |
(8) - All data refers to the standard unit without options. |
(8) - All data refers to the standard unit without options. |
(8) - All data refers to the standard unit without options. |
(8) - All data refers to the standard unit without options. |
(8) - All data refers to the standard unit without options. |
(8) - All data refers to the standard unit without options. |
(8) - All data refers to the standard unit without options. |
|
(9) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(9) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(9) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(9) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(9) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(9) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(9) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(9) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(9) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(9) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(9) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(9) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(9) - All data are subject to change without notice. Please refer to the unit nameplate data. |
(9) - All data are subject to change without notice. Please refer to the unit nameplate data. |
|
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). |
|
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. |
|
(12) - In case of inverter driven units, no inrush current at start up is experienced. |
(12) - In case of inverter driven units, no inrush current at start up is experienced. |
(12) - In case of inverter driven units, no inrush current at start up is experienced. |
(12) - In case of inverter driven units, no inrush current at start up is experienced. |
(12) - In case of inverter driven units, no inrush current at start up is experienced. |
(12) - In case of inverter driven units, no inrush current at start up is experienced. |
(12) - In case of inverter driven units, no inrush current at start up is experienced. |
(12) - In case of inverter driven units, no inrush current at start up is experienced. |
(12) - In case of inverter driven units, no inrush current at start up is experienced. |
(12) - In case of inverter driven units, no inrush current at start up is experienced. |
(12) - In case of inverter driven units, no inrush current at start up is experienced. |
(12) - In case of inverter driven units, no inrush current at start up is experienced. |
(12) - In case of inverter driven units, no inrush current at start up is experienced. |
(12) - In case of inverter driven units, no inrush current at start up is experienced. |