Specifications Table for FXCQ-A

FXCQ20AVEB FXCQ25AVEB FXCQ32AVEB FXCQ40AVEB FXCQ50AVEB FXCQ63AVEB FXCQ80AVEB FXCQ125AVEB
Cooling capacity Total capacity At high fan speed kW 2.2 (1) 2.8 (1) 3.6 (1) 4.5 (1) 5.6 (1) 7.1 (1) 9.0 (1) 14.0 (1)
Heating capacity Total capacity At high fan speed kW 2.5 (2) 3.2 (2) 4.0 (2) 5.0 (2) 6.3 (2) 8.0 (2) 10.0 (2) 16.0 (2)
Power input - 50Hz Cooling At high fan speed kW 0.031 0.039 0.039 0.041 0.059 0.063 0.090 0.149
  Heating At high fan speed kW 0.028 0.035 0.035 0.037 0.056 0.060 0.086 0.146
Dimensions Unit Height mm 305 305 305 305 305 305 305 305
    Width mm 775 775 775 775 990 990 1,445 1,445
    Depth mm 620 620 620 620 620 620 620 620
Weight Unit kg 19 19 19 19 22 25 33 38
Casing Material   Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate
Fan Air flow rate - 50Hz Cooling At high fan speed m³/min 10.5 11.5 11.5 12 15 16 26 32
      At low fan speed m³/min 7.5 8 8 8.5 10.5 11.5 18.5 22.5
Refrigerant Type   R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
  GWP   2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5
Sound power level Cooling At high fan speed dBA 48 50 50 52 53 55 58 62
Sound pressure level Cooling At high fan speed dBA 32.0 34.0 34.0 36.0 37.0 39.0 42.0 46.0
    At medium fan speed dBA 30.0 31.0 32.0 33.0 35.0 37.0 38.0 42.0
    At low fan speed dBA 28.0 29.0 30.0 31.0 31.0 32.0 33.0 38.0
  Heating At high fan speed dBA 32.0 34.0 34.0 36.0 37.0 39.0 42.0 46.0
    At medium fan speed dBA 30.0 31.0 32.0 33.0 35.0 37.0 38.0 42.0
    At low fan speed dBA 28.0 29.0 30.0 31.0 31.0 32.0 33.0 38.0
Piping connections Liquid Type   Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection
    OD mm 6.35 6.35 6.35 6.35 6.35 9.52 9.52 9.52
  Gas Type   Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection
    OD mm 12.7 12.7 12.7 12.7 12.7 15.9 15.9 15.9
  Drain   VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25)
Decoration panel Model   BYBCQ40HW1 BYBCQ40HW1 BYBCQ40HW1 BYBCQ40HW1 BYBCQ63HW1 BYBCQ63HW1 BYBCQ125HW1 BYBCQ125HW1
  Colour   Fresh white (6.5Y 9.5/0.5) Fresh white (6.5Y 9.5/0.5) Fresh white (6.5Y 9.5/0.5) Fresh white (6.5Y 9.5/0.5) Fresh white (6.5Y 9.5/0.5) Fresh white (6.5Y 9.5/0.5) Fresh white (6.5Y 9.5/0.5) Fresh white (6.5Y 9.5/0.5)
  Dimensions Height mm 55 55 55 55 55 55 55 55
    Width mm 1,070 1,070 1,070 1,070 1,285 1,285 1,740 1,740
    Depth mm 700 700 700 700 700 700 700 700
  Weight kg 10 10 10 10 11 11 13 13
Air filter Type   Resin net with mold resistance Resin net with mold resistance Resin net with mold resistance Resin net with mold resistance Resin net with mold resistance Resin net with mold resistance Resin net with mold resistance Resin net with mold resistance
Power supply Name   VE VE VE VE VE VE VE VE
  Phase   1~ 1~ 1~ 1~ 1~ 1~ 1~ 1~
  Frequency Hz 50 50 50 50 50 50 50 50
  Voltage V 220-240 220-240 220-240 220-240 220-240 220-240 220-240 220-240
Current - 50Hz Maximum fuse amps (MFA) A 16 16 16 16 16 16 16 16
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal)
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal)
  (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
  (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%.
  (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA
  (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA
  (8) - Next lower standard fuse rating minimum 16A (8) - Next lower standard fuse rating minimum 16A (8) - Next lower standard fuse rating minimum 16A (8) - Next lower standard fuse rating minimum 16A (8) - Next lower standard fuse rating minimum 16A (8) - Next lower standard fuse rating minimum 16A (8) - Next lower standard fuse rating minimum 16A (8) - Next lower standard fuse rating minimum 16A
  (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA
  (10) - Instead of a fuse, use a circuit breaker (10) - Instead of a fuse, use a circuit breaker (10) - Instead of a fuse, use a circuit breaker (10) - Instead of a fuse, use a circuit breaker (10) - Instead of a fuse, use a circuit breaker (10) - Instead of a fuse, use a circuit breaker (10) - Instead of a fuse, use a circuit breaker (10) - Instead of a fuse, use a circuit breaker
  (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases