FXSN50A2VEB |
FXSN71A2VEB |
FXSN112A2VEB |
Cooling capacity |
Total capacity |
At high fan speed |
kW |
5.60 |
8.00 |
12.50 |
Heating capacity |
Total capacity |
At high fan speed |
kW |
6.30 |
9.00 |
14.0 |
Power input - 50Hz |
Cooling |
At high fan speed |
kW |
0.186 |
0.258 |
0.388 |
|
Heating |
At high fan speed |
kW |
0.181 |
0.253 |
0.383 |
Dimensions |
Unit |
Height |
Mm |
245 |
245 |
245 |
|
|
Width |
Mm |
700 |
1,000 |
1,400 |
|
|
Depth |
Mm |
800 |
800 |
800 |
Weight |
Unit |
kg |
31.0 |
40.0 |
50.0 |
Casing |
Colour |
|
Not painted (galvanised) |
Not painted (galvanised) |
Not painted (galvanised) |
|
Material |
|
Galvanised steel plate |
Galvanised steel plate |
Galvanised steel plate |
Fan |
Air flow rate - 50Hz |
Cooling |
At high fan speed |
m³/min |
15.2 |
23.0 |
36.0 |
|
|
|
At low fan speed |
m³/min |
11.0 |
16.0 |
26.0 |
|
External static pressure - 50Hz |
High |
Pa |
150 |
150 |
150 |
Refrigerant |
Type |
|
R-744 |
R-744 |
R-744 |
|
GWP |
|
1.0 |
1.0 |
1.0 |
Sound power level |
Cooling |
At high fan speed |
dBA |
61 |
63 |
66 |
Sound pressure level |
Cooling |
At high fan speed |
dBA |
36.0 |
37.0 |
40.0 |
|
|
At medium fan speed |
dBA |
33.0 |
34.0 |
38.0 |
|
|
At low fan speed |
dBA |
31.0 |
32.0 |
34.0 |
|
Heating |
At high fan speed |
dBA |
38.0 |
39.0 |
42.0 |
|
|
At medium fan speed |
dBA |
35.0 |
36.0 |
40.0 |
|
|
At low fan speed |
dBA |
32.0 |
33.0 |
38.0 |
Piping connections |
Liquid |
Type |
|
Brazing-brazing connection |
Brazing-brazing connection |
Brazing-brazing connection |
|
|
OD |
Mm |
9.52 |
9.52 |
9.52 |
|
Gas |
Type |
|
Brazing-brazing connection |
Brazing-brazing connection |
Brazing-brazing connection |
|
|
OD |
Mm |
12.7 |
12.7 |
12.7 |
|
Drain |
|
VP20 (I.D. 20/O.D. 26), drain height 625 mm |
VP20 (I.D. 20/O.D. 26), drain height 625 mm |
VP20 (I.D. 20/O.D. 26), drain height 625 mm |
Drain-up height |
Mm |
625 |
625 |
625 |
Air filter |
Type |
|
Resin net |
Resin net |
Resin net |
Standard Accessories |
Installation and operation manual |
1 |
1 |
1 |
|
Drain hose |
1 |
1 |
1 |
|
Metal clamp for drain hose |
1 |
1 |
1 |
|
Washer for hanger bracket |
8 |
8 |
8 |
|
Screws |
40 |
40 |
40 |
|
Insulation for fitting |
2 |
2 |
2 |
|
Sealing pad |
5 |
5 |
5 |
|
Clamps |
4 |
4 |
4 |
Power supply |
Name |
|
VE |
VE |
VE |
|
Phase |
|
1~ |
1~ |
1~ |
|
Frequency |
Hz |
50/60 |
50/60 |
50/60 |
|
Voltage |
V |
220-240/220 |
220-240/220 |
220-240/220 |
Current - 50Hz |
Maximum fuse amps (MFA) |
A |
16 |
16 |
16 |
Notes |
(1) - The sound power level is an absolute value indicating the power which a sound source generates. |
(1) - The sound power level is an absolute value indicating the power which a sound source generates. |
(1) - The sound power level is an absolute value indicating the power which a sound source generates. |
|
(2) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(2) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(2) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
|
(3) - Select wire size based on the value of MCA |
(3) - Select wire size based on the value of MCA |
(3) - Select wire size based on the value of MCA |
|
(4) - Maximum allowable voltage range variation between phases is 2%. |
(4) - Maximum allowable voltage range variation between phases is 2%. |
(4) - Maximum allowable voltage range variation between phases is 2%. |
|
(5) - Use a circuit breaker instead of a fuse. |
(5) - Use a circuit breaker instead of a fuse. |
(5) - Use a circuit breaker instead of a fuse. |
|
(6) - MCA/MFA; MCA= 1,25 x FLA; MFA=< 4 x FLA; The next lower standard fuse rating is minimum 16 ampere. |
(6) - MCA/MFA; MCA= 1,25 x FLA; MFA=< 4 x FLA; The next lower standard fuse rating is minimum 16 ampere. |
(6) - MCA/MFA; MCA= 1,25 x FLA; MFA=< 4 x FLA; The next lower standard fuse rating is minimum 16 ampere. |
|
(7) - Contains fluorinated greenhouse gases |
(7) - Contains fluorinated greenhouse gases |
(7) - Contains fluorinated greenhouse gases |