AZQS100B7Y1B UK |
AZQS125B7Y1B UK |
AZQS140B7Y1B UK |
Sound pressure level
|
Heating
|
Nom.
|
dBA
|
57
|
58
|
54
|
|
Cooling
|
Nom.
|
dBA
|
53
|
54
|
53
|
|
Night quiet mode
|
Level 1
|
dBA
|
49
|
49
|
49
|
Standard Accessories
|
Tie-wraps
|
2
|
2
|
2
|
|
Installation manual
|
1
|
1
|
1
|
Refrigerant
|
Charge
|
TCO2Eq
|
6.1
|
6.1
|
8.4
|
|
GWP
|
|
2,087.5
|
2,087.5
|
2,087.5
|
|
Charge
|
kg
|
2.9
|
2.9
|
4.0
|
|
Type
|
|
R-410A
|
R-410A
|
R-410A
|
Piping connections
|
Liquid
|
OD
|
mm
|
9.52
|
9.52
|
9.52
|
|
Piping length
|
OU - IU
|
Max.
|
m
|
30 (7)
|
30 (7)
|
30 (7)
|
|
|
System
|
Chargeless
|
m
|
30
|
30
|
30
|
|
|
|
Equivalent
|
m
|
40
|
40
|
40
|
|
Gas
|
OD
|
mm
|
15.9
|
15.9
|
15.9
|
|
Level difference
|
IU - IU
|
Max.
|
m
|
0.5
|
0.5
|
0.5
|
|
|
IU - OU
|
Max.
|
m
|
30.0
|
30.0
|
30.0
|
|
Additional refrigerant charge
|
kg/m
|
See installation manual
|
See installation manual
|
See installation manual
|
Sound power level
|
Cooling
|
dBA
|
70
|
71
|
70
|
Dimensions
|
Unit
|
Width
|
mm
|
940
|
940
|
940
|
|
|
Depth
|
mm
|
320
|
320
|
320
|
|
|
Height
|
mm
|
990
|
990
|
1,430
|
Compressor
|
Type
|
|
Hermetically sealed swing compressor
|
Hermetically sealed swing compressor
|
Hermetically sealed swing compressor
|
Weight
|
Unit
|
kg
|
82
|
82
|
101
|
Power supply
|
Phase
|
|
3N~
|
3N~
|
3N~
|
|
Frequency
|
Hz
|
50
|
50
|
50
|
|
Voltage
|
V
|
380-415
|
380-415
|
380-415
|
Notes
|
(1) - PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
|
(1) - PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
|
(1) - PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
|
|
(2) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase
|
(2) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase
|
(2) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase
|
|
(3) - See separate drawing for electrical data
|
(3) - See separate drawing for electrical data
|
(3) - See separate drawing for electrical data
|
|
(4) - Contains fluorinated greenhouse gases
|
(4) - Contains fluorinated greenhouse gases
|
(4) - Contains fluorinated greenhouse gases
|
|
(5) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for high efficiency series, Eurovent certified
|
(5) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for high efficiency series, Eurovent certified
|
(5) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for high efficiency series, Eurovent certified
|
|
(6) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for high efficiency series, Eurovent certified
|
(6) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for high efficiency series, Eurovent certified
|
(6) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for high efficiency series, Eurovent certified
|
|
(7) - For details regarding your combination of oudoor and indoor unit, refer to the technical databook
|
(7) - For details regarding your combination of oudoor and indoor unit, refer to the technical databook
|
(7) - For details regarding your combination of oudoor and indoor unit, refer to the technical databook
|