| EBBX16DF6V / ERLA16DAV37 | EBBX16DF6V / ERLA16D2V37 | |||||
|---|---|---|---|---|---|---|
| Heating capacity | Nom. | kW | 16.0 (1) (2) | 16.0 (2) (1) | ||
| Cooling capacity | Nom. | kW | 13.8 (3), 15.9 (4) | 13.8 (3), 15.9 (4) | ||
| Power input | Heating | Nom. | kW | 3.53 (1), 4.56 (2) | 3.53 (1), 4.56 (2) | |
| Cooling | Nom. | kW | 4.68 (3), 3.82 (4) | 4.68 (3), 3.82 (4) | ||
| COP | 4.53 (1), 3.51 (2) | 4.53 (1), 3.51 (2) | ||||
| EER | 2.94 (3), 4.16 (4) | 2.94 (3), 4.16 (4) | ||||
| SEER | 5.76 (5) | 5.76 (5) | ||||
| Space heating | Average climate water outlet 55°C | General | SCOP | 3.35 | 3.35 | |
| Seasonal space heating eff. class | A++ | A++ | ||||
| Average climate water outlet 35°C | General | SCOP | 4.68 | 4.68 | ||
| Seasonal space heating eff. class | A+++ | A+++ | ||||
| Notes | (1) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) | (1) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) | ||||
| (2) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) | (2) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) | |||||
| (3) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB | (3) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB | |||||
| (4) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB | (4) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB | |||||
| (5) - According to EN14825 | (5) - According to EN14825 | |||||
| (6) - Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) | (6) - Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) | |||||
| (7) - Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) | (7) - Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) | |||||
| (8) - Measured with a pressure drop of 10 kPa in the heating system at an operating condition of leaving water 47-55°C in a room with an ambient of 20°C. DB/WB 7°C/6°. | (8) - Measured with a pressure drop of 10 kPa in the heating system at an operating condition of leaving water 47-55°C in a room with an ambient of 20°C. DB/WB 7°C/6°. | |||||