| ERA200AMYFB | ERA250AMYFB | ERA300AMYFB | |||||
|---|---|---|---|---|---|---|---|
| Cooling capacity | Nom. | 35°CDB | kW | 22.4 (1) | 28 | 33.5 (1) | |
| Heating capacity | Nom. | 6°CWB | kW | 22.4 (2) | 28 | 33.5 (2) | |
| SEER | 6.36 (3) | 6.93 (3) | 6.47 (3) | ||||
| SCOP | 4.42 (3) | 4.42 (3) | 4.64 (3) | ||||
| Indoor index connection | Min. | 140 | 200 | 200 | |||
| Max. | 200 | 250 | 300 | ||||
| Dimensions | Unit | Height | mm | 1,430 | 1,615 | 1,615 | |
| Width | mm | 940 | 940 | 940 | |||
| Depth | mm | 320 | 460 | 460 | |||
| Weight | Unit | kg | 134 | 163 | 163 | ||
| Fan | External static pressure | Max. | Pa | 35 | 35 | 35 | |
| Compressor | Type | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | |||
| Operation range | Cooling | Min. | °CDB | -5 | -5 | -5 | |
| Max. | °CDB | 52 | 52 | 52 | |||
| Heating | Min. | °CWB | -20 | -20 | -20 | ||
| Max. | °CWB | 15.5 | 15.5 | 15.5 | |||
| Sound power level | Cooling | Nom. | dBA | 73.2 (4) | 74 | 76.1 (4) | |
| Sound pressure level | Cooling | Nom. | dBA | 58.1 (5) | 57 | 60 | |
| Refrigerant | Type | R-32 | R-32 | R-32 | |||
| GWP | 675 | 675 | 675 | ||||
| Charge | tCO2Eq | 3.51 | 4.73 | 4.79 | |||
| Charge | kg | 5.2 | 7 | 7.1 | |||
| Piping connections | Liquid | Type | Braze connection | Braze connection | Braze connection | ||
| OD | mm | 9.52 | 9.52 | 12.7 | |||
| Gas | Type | Braze connection | Braze connection | Braze connection | |||
| OD | mm | 19.1 | 19.1 | 22.2 | |||
| Total piping length | System | Actual | m | 50 (6) | 50 (6) | 50 (6) | |
| Standard Accessories | Connection pipes | 1 | 2 | 1 | |||
| Installation and operation manual | 1 | 1 | 1 | ||||
| Power supply | Name | Y1 | Y1 | Y1 | |||
| Phase | 3N~ | 3N~ | 3N~ | ||||
| Frequency | Hz | 50/60 | 50/60 | 50/60 | |||
| Voltage | V | 380-415/400 | 380-415/400 | 380-415/400 | |||
| Notes | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | ||||
| (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | |||||
| (3) - Defined for a system capacity ratio of 100% ± 5%, configured for complete air recirculation applications. | (3) - Defined for a system capacity ratio of 100% ± 5%, configured for complete air recirculation applications. | (3) - Defined for a system capacity ratio of 100% ± 5%, configured for complete air recirculation applications. | |||||
| (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | |||||
| (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | |||||
| (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | |||||
| (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | |||||
| (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | |||||
| (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | |||||
| (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | |||||
| (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | |||||
| (12) - Maximum allowable voltage range variation between phases is 2%. | (12) - Maximum allowable voltage range variation between phases is 2%. | (12) - Maximum allowable voltage range variation between phases is 2%. | |||||
| (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | |||||
| (14) - Sound values are measured in a semi-anechoic room. | (14) - Sound values are measured in a semi-anechoic room. | (14) - Sound values are measured in a semi-anechoic room. | |||||
| (15) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (15) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (15) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | |||||
| (16) - Ssc: Short-circuit power | (16) - Ssc: Short-circuit power | (16) - Ssc: Short-circuit power | |||||
| (17) - For detailed contents of standard accessories, see installation/operation manual | (17) - For detailed contents of standard accessories, see installation/operation manual | (17) - For detailed contents of standard accessories, see installation/operation manual | |||||
| (18) - For AHU HEX volume limitations, refer to the engineering data book or installation manual | (18) - For AHU HEX volume limitations, refer to the engineering data book or installation manual | (18) - For AHU HEX volume limitations, refer to the engineering data book or installation manual | |||||