Specifications Table for ERA-AYF

ERA200AMYFB ERA250AMYFB ERA300AMYFB
Cooling capacity Nom. 35°CDB kW 22.4 (1) 28 33.5 (1)
Heating capacity Nom. 6°CWB kW 22.4 (2) 28 33.5 (2)
SEER 6.36 (3) 6.93 (3) 6.47 (3)
SCOP 4.42 (3) 4.42 (3) 4.64 (3)
Indoor index connection Min.   140 200 200
  Max.   200 250 300
Dimensions Unit Height mm 1,430 1,615 1,615
    Width mm 940 940 940
    Depth mm 320 460 460
Weight Unit kg 134 163 163
Fan External static pressure Max. Pa 35 35 35
Compressor Type   Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor
Operation range Cooling Min. °CDB -5 -5 -5
    Max. °CDB 52 52 52
  Heating Min. °CWB -20 -20 -20
    Max. °CWB 15.5 15.5 15.5
Sound power level Cooling Nom. dBA 73.2 (4) 74 76.1 (4)
Sound pressure level Cooling Nom. dBA 58.1 (5) 57 60
Refrigerant Type   R-32 R-32 R-32
  GWP   675 675 675
  Charge tCO2Eq 3.51 4.73 4.79
  Charge kg 5.2 7 7.1
Piping connections Liquid Type   Braze connection Braze connection Braze connection
    OD mm 9.52 9.52 12.7
  Gas Type   Braze connection Braze connection Braze connection
    OD mm 19.1 19.1 22.2
  Total piping length System Actual m 50 (6) 50 (6) 50 (6)
Standard Accessories Connection pipes 1 2 1
  Installation and operation manual 1 1 1
Power supply Name   Y1 Y1 Y1
  Phase   3N~ 3N~ 3N~
  Frequency Hz 50/60 50/60 50/60
  Voltage V 380-415/400 380-415/400 380-415/400
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - Defined for a system capacity ratio of 100% ± 5%, configured for complete air recirculation applications. (3) - Defined for a system capacity ratio of 100% ± 5%, configured for complete air recirculation applications. (3) - Defined for a system capacity ratio of 100% ± 5%, configured for complete air recirculation applications.
  (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates.
  (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
  (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual
  (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
  (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
  (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
  (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%.
  (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (14) - Sound values are measured in a semi-anechoic room. (14) - Sound values are measured in a semi-anechoic room. (14) - Sound values are measured in a semi-anechoic room.
  (15) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (15) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (15) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
  (16) - Ssc: Short-circuit power (16) - Ssc: Short-circuit power (16) - Ssc: Short-circuit power
  (17) - For detailed contents of standard accessories, see installation/operation manual (17) - For detailed contents of standard accessories, see installation/operation manual (17) - For detailed contents of standard accessories, see installation/operation manual
  (18) - For AHU HEX volume limitations, refer to the engineering data book or installation manual (18) - For AHU HEX volume limitations, refer to the engineering data book or installation manual (18) - For AHU HEX volume limitations, refer to the engineering data book or installation manual