|
ERQ125A7W1B |
ERQ200A7W1B |
ERQ250A7W1B |
Sound pressure level
|
Nom.
|
dBA
|
54
|
57
|
58
|
Standard Accessories
|
Installation manual
|
1
|
1
|
1
|
|
Operation manual
|
1
|
1
|
1
|
|
Connection pipes
|
4
|
4
|
4
|
Refrigerant
|
Charge
|
TCO2Eq
|
12.9
|
16.1
|
17.5
|
|
GWP
|
|
2,087.5
|
2,087.5
|
2,087.5
|
|
Charge
|
kg
|
6.2
|
7.7
|
8.4
|
|
Type
|
|
R-410A
|
R-410A
|
R-410A
|
Operation range
|
Cooling
|
Max.
|
°CDB
|
43
|
43
|
43
|
|
|
Min.
|
°CDB
|
-5
|
-5
|
-5
|
|
Heating
|
Max.
|
°CWB
|
15
|
15
|
15
|
|
|
Min.
|
°CWB
|
-20
|
-20
|
-20
|
Cooling capacity
|
Nom.
|
kW
|
14.0 (1)
|
22.4 (1)
|
28.0 (1)
|
Piping connections
|
Liquid
|
OD
|
mm
|
9.52
|
9.52
|
9.52
|
|
|
Type
|
|
Braze connection
|
Braze connection
|
Braze connection
|
|
Gas
|
OD
|
mm
|
15.9
|
19.1
|
22.2
|
|
|
Type
|
|
Braze connection
|
Braze connection
|
Braze connection
|
Power input
|
Cooling
|
Nom.
|
kW
|
3.52 (1)
|
5.22 (1)
|
7.42 (1)
|
Sound power level
|
Nom.
|
dBA
|
72
|
78
|
78
|
COP
|
4.00 (2)
|
4.50 (2)
|
4.09 (2)
|
Dimensions
|
Unit
|
Width
|
mm
|
635
|
930
|
930
|
|
|
Depth
|
mm
|
765
|
765
|
765
|
|
|
Height
|
mm
|
1,680
|
1,680
|
1,680
|
Weight
|
Unit
|
kg
|
159
|
187
|
240
|
Fan
|
Air flow rate
|
Heating
|
Nom.
|
m³/min
|
95
|
171
|
185
|
|
|
Cooling
|
Nom.
|
m³/min
|
95
|
171
|
185
|
EER
|
3.98 (1)
|
4.29 (1)
|
3.77 (1)
|
Heating capacity
|
Nom.
|
kW
|
16.0 (2)
|
25.0 (2)
|
31.5 (2)
|
Power supply
|
Phase
|
|
3N~
|
3N~
|
3N~
|
|
Name
|
|
W1
|
W1
|
W1
|
|
Frequency
|
Hz
|
50
|
50
|
50
|
|
Voltage
|
V
|
400
|
400
|
400
|
Notes
|
(1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m
|
(1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m
|
(1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m
|
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m
|
|
(3) - Sound values are measured in a semi-anechoic room.
|
(3) - Sound values are measured in a semi-anechoic room.
|
(3) - Sound values are measured in a semi-anechoic room.
|
|
(4) - Sound power level is an absolute value that a sound source generates.
|
(4) - Sound power level is an absolute value that a sound source generates.
|
(4) - Sound power level is an absolute value that a sound source generates.
|
|
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
|
(6) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
|
(6) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
|
(6) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
|
|
(7) - Maximum allowable voltage range variation between phases is 2%.
|
(7) - Maximum allowable voltage range variation between phases is 2%.
|
(7) - Maximum allowable voltage range variation between phases is 2%.
|
|
(8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
|
(8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
|
(8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
|
|
(9) - Select wire size based on the value of MCA
|
(9) - Select wire size based on the value of MCA
|
(9) - Select wire size based on the value of MCA
|
|
(10) - TOCA means the total value of each OC set.
|
(10) - TOCA means the total value of each OC set.
|
(10) - TOCA means the total value of each OC set.
|
|
(11) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
(11) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
(11) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
|
(12) - FLA means the full load amps of the fan motor.
|
(12) - FLA means the full load amps of the fan motor.
|
(12) - FLA means the full load amps of the fan motor.
|
|
(13) - In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value.
|
(13) - In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value.
|
(13) - In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value.
|
|
(14) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A
|
(14) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A
|
(14) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A
|
|
(15) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
|
(15) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
|
(15) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
|
|
(16) - Short-circuit power
|
(16) - Short-circuit power
|
(16) - Short-circuit power
|
|
(17) - Contains fluorinated greenhouse gases
|
(17) - system impedance
|
(17) - system impedance
|
|
(18) - system impedance
|
(18) - Contains fluorinated greenhouse gases
|
(18) - Contains fluorinated greenhouse gases
|
|
(19) - MSC means the maximum current during start up of the compressor
|
(19) - MSC means the maximum current during start up of the compressor
|
(19) - MSC means the maximum current during start up of the compressor
|