| ETSXB16P30EF / EPRA14DAV3 | ETSXB16P50EF / EPRA14DAV3 | ETSXB16P30EF / EPRA16DAV3 | ETSXB16P50EF / EPRA16DAV3 | ETSXB16P30EF / EPRA18DAV3 | ETSXB16P50EF / EPRA18DAV3 | |||||
|---|---|---|---|---|---|---|---|---|---|---|
| Domestic hot water heating | General | Declared load profile | L | XL | L | XL | L | XL | ||
| Average climate | Water heating energy efficiency class | A+ | A+ | A+ | A+ | A+ | A+ | |||
| COP | 4.67 (2) | 4.67 (2) | 5.00 (2) | 5.00 (2) | 5.00 (2) | 5.00 (2) | ||||
| Indoor unit | ETSXB16P30EF | ETSXB16P50EF | ETSXB16P30EF | ETSXB16P50EF | ETSXB16P30EF | ETSXB16P50EF | ||||
| Space heating | Average climate water outlet 35°C | General | ηs (Seasonal space heating efficiency) | % | 180 | 180 | 180 | 180 | 180 | 180 |
| Seasonal space heating eff. class | A+++ | A+++ | A+++ | A+++ | A+++ | A+++ | ||||
| SCOP | 4.57 | 4.57 | 4.57 | 4.57 | 4.57 | 4.57 | ||||
| Average climate water outlet 55°C | General | Seasonal space heating eff. class | A++ | A++ | A++ | A++ | A++ | A++ | ||
| ηs (Seasonal space heating efficiency) | % | 142 | 142 | 142 | 142 | 142 | 142 | |||
| SCOP | 3.62 | 3.62 | 3.62 | 3.62 | 3.62 | 3.62 | ||||
| Cooling capacity | Nom. | kW | 10.6 (3), 6.90 (4) | 10.6 (3), 6.90 (4) | 11.5 (3), 7.88 (4) | 11.5 (3), 7.88 (4) | 12.5 (3), 8.86 (4) | 12.5 (3), 8.86 (4) | ||
| EER | 4.13 (3), 2.70 (4) | 4.13 (3), 2.70 (4) | 4.11 (3), 2.69 (4) | 4.11 (3), 2.69 (4) | 4.09 (3), 2.68 (4) | 4.09 (3), 2.68 (4) | ||||
| Heating capacity | Nom. | kW | 5.69 (2) | 5.69 (2) | 9.00 (2) | 9.00 (2) | 9.00 (2) | 9.00 (2) | ||
| Min. | kW | 3.70 (1) | 3.70 (1) | 3.96 (1) | 3.96 (1) | 4.40 (1) | 4.40 (1) | |||
| Max. | kW | 10.18 (1) | 10.18 (1) | 10.91 (1) | 10.91 (1) | 12.12 (1) | 12.12 (1) | |||
| Power input | Heating | Max. | kW | 2.09 (5) | 2.09 (5) | 2.24 (5) | 2.24 (5) | 2.49 (5) | 2.49 (5) | |
| Min. | kW | 0.88 (5) | 0.88 (5) | 0.95 (5) | 0.95 (5) | 1.05 (5) | 1.05 (5) | |||
| Nom. | kW | 1.22 (2) | 1.22 (2) | 1.80 (2) | 1.80 (2) | 1.80 (2) | 1.80 (2) | |||
| Cooling | Nom. | kW | 2.55 (3), 2.56 (4) | 2.55 (3), 2.56 (4) | 2.80 (3), 2.93 (4) | 2.80 (3), 2.93 (4) | 3.05 (3), 3.31 (4) | 3.05 (3), 3.31 (4) | ||
| Notes | (1) - Capacity according to standard EN14511 and valid for heated water range dT = 3~8°C at Ta 7°C | (1) - Capacity according to standard EN14511 and valid for heated water range dT = 3~8°C at Ta 7°C | (1) - Capacity according to standard EN14511 and valid for heated water range dT = 3~8°C at Ta 7°C | (1) - Capacity according to standard EN14511 and valid for heated water range dT = 3~8°C at Ta 7°C | (1) - Capacity according to standard EN14511 and valid for heated water range dT = 3~8°C at Ta 7°C | (1) - Capacity according to standard EN14511 and valid for heated water range dT = 3~8°C at Ta 7°C | ||||
| (2) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) | (2) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) | (2) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) | (2) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) | (2) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) | (2) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) | |||||
| (3) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB | (3) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB | (3) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB | (3) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB | (3) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB | (3) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB | |||||
| (4) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB | (4) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB | (4) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB | (4) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB | (4) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB | (4) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB | |||||
| (5) - Power input is total input of indoor and outdoor units, including the circulation pump; according to EN14511 | (5) - Power input is total input of indoor and outdoor units, including the circulation pump; according to EN14511 | (5) - Power input is total input of indoor and outdoor units, including the circulation pump; according to EN14511 | (5) - Power input is total input of indoor and outdoor units, including the circulation pump; according to EN14511 | (5) - Power input is total input of indoor and outdoor units, including the circulation pump; according to EN14511 | (5) - Power input is total input of indoor and outdoor units, including the circulation pump; according to EN14511 | |||||