EWWQ014KBW1N |
EWWQ025KBW1N |
EWWQ033KBW1N |
EWWQ049KBW1N |
EWWQ064KBW1N |
EWWQ098KBW1N |
EWWQ113KBW1N |
EWWQ128KBW1N |
EWWQ147KBW1N |
EWWQ162KBW1N |
EWWQ177KBW1N |
EWWQ192KBW1N |
Sound pressure level
|
Cooling
|
Nom.
|
dBA
|
50
|
50
|
57
|
53
|
60
|
55.71
|
59.71
|
61.71
|
56.9
|
60.9
|
61.9
|
62.9
|
Refrigerant
|
Circuits
|
Quantity
|
|
1
|
1
|
1
|
2
|
2
|
4
|
4
|
4
|
6
|
6
|
6
|
6
|
|
Charge
|
kg
|
1.2
|
2
|
3.1
|
4.6
|
5.6
|
9.4
|
10.2
|
11.2
|
13.8
|
14.8
|
15.8
|
16.8
|
|
Type
|
|
R-410A
|
R-410A
|
R-410A
|
R-410A
|
R-410A
|
R-410A
|
R-410A
|
R-410A
|
R-410A
|
R-410A
|
R-410A
|
R-410A
|
Cooling capacity
|
Nom.
|
kW
|
13.25
|
23.9
|
30.4
|
47.15
|
60.98
|
94
|
108
|
122
|
142
|
155
|
169
|
183
|
Power input
|
Cooling
|
Nom.
|
kW
|
3.15
|
5.72
|
7.3
|
11.42
|
14.58
|
22.7
|
25.8
|
28.9
|
33.9
|
37
|
40.1
|
43.2
|
Sound power level
|
Cooling
|
Nom.
|
dBA
|
64
|
64
|
71
|
67
|
74
|
71
|
75
|
77
|
73
|
77
|
78
|
79
|
Dimensions
|
Unit
|
Width
|
mm
|
600
|
600
|
600
|
600
|
600
|
600
|
600
|
600
|
600
|
600
|
600
|
600
|
|
|
Depth
|
mm
|
600
|
600
|
600
|
1,200
|
1,200
|
1,200
|
1,200
|
1,200
|
1,200
|
1,200
|
1,200
|
1,200
|
|
|
Height
|
mm
|
600
|
600
|
600
|
600
|
600
|
1,200
|
1,200
|
1,200
|
1,800
|
1,800
|
1,800
|
1,800
|
Compressor
|
Type
|
|
Scroll compressor
|
Scroll compressor
|
Scroll compressor
|
Scroll compressor
|
|
Scroll compressor
|
Scroll compressor
|
Scroll compressor
|
Scroll compressor
|
Scroll compressor
|
Scroll compressor
|
Scroll compressor
|
|
Quantity
|
|
1
|
1
|
1
|
2
|
|
4
|
4
|
4
|
6
|
6
|
6
|
6
|
Water heat exchanger - condenser
|
Type
|
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
|
Water flow rate
|
Nom.
|
l/s
|
0.78
|
1.41
|
1.83
|
2.78
|
3.61
|
5.57
|
6.39
|
7.21
|
8.35
|
9.17
|
10
|
10.8
|
Capacity control
|
Minimum capacity
|
%
|
100
|
100
|
100
|
50
|
50
|
25
|
25
|
25
|
16
|
16
|
16
|
16
|
|
Method
|
|
Fixed
|
Fixed
|
Fixed
|
Fixed
|
Fixed
|
Weight
|
Operation weight
|
kg
|
123
|
175
|
182
|
320
|
353
|
640
|
673
|
707
|
960
|
993
|
1,026
|
1,060
|
|
Unit
|
kg
|
120
|
170
|
175
|
310
|
340
|
620
|
650
|
680
|
930
|
960
|
990
|
1,020
|
Water heat exchanger - evaporator
|
Water flow rate
|
Nom.
|
l/s
|
0.64
|
1.15
|
1.46
|
2.26
|
2.92
|
4.5
|
5.2
|
5.8
|
6.8
|
7.4
|
8.1
|
8.8
|
|
Type
|
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
Brazed plate
|
|
Water volume
|
l
|
1.23
|
1.93
|
2.68
|
4.5
|
5.93
|
9
|
10
|
12
|
14
|
15
|
16
|
18
|
EER
|
4.209
|
4.177
|
4.164
|
4.127
|
4.182
|
4.17
|
4.19
|
4.22
|
4.18
|
4.2
|
4.22
|
4.24
|
ESEER
|
4.52
|
4.58
|
4.72
|
4.56
|
4.71
|
4.65
|
4.64
|
4.66
|
4.7
|
4.69
|
4.70
|
4.71
|
Power supply
|
Phase
|
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
|
Name
|
|
W1
|
W1
|
W1
|
W1
|
W1
|
|
Frequency
|
Hz
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
|
Voltage
|
V
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
Notes
|
(1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C
|
(1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C
|
(1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C
|
(1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C
|
(1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C
|
(1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C
|
(1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C
|
(1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C
|
(1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C
|
(1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C
|
(1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C
|
(1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C
|
|
(2) - The nominal sound power level is measured according to ISO9614
|
(2) - The nominal sound power level is measured according to ISO9614
|
(2) - The nominal sound power level is measured according to ISO9614
|
(2) - The nominal sound power level is measured according to ISO9614
|
(2) - The nominal sound power level is measured according to ISO9614
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
|
(3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
|
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
|
(5) - Electrical data referred to standard unit without options, refer to name plate data.
|
(5) - Electrical data referred to standard unit without options, refer to name plate data.
|
(5) - Electrical data referred to standard unit without options, refer to name plate data.
|
(5) - Electrical data referred to standard unit without options, refer to name plate data.
|
(5) - Electrical data referred to standard unit without options, refer to name plate data.
|
(5) - Electrical data referred to standard unit without options, refer to name plate data.
|
(5) - Electrical data referred to standard unit without options, refer to name plate data.
|
(5) - Electrical data referred to standard unit without options, refer to name plate data.
|
(5) - Electrical data referred to standard unit without options, refer to name plate data.
|
(5) - Electrical data referred to standard unit without options, refer to name plate data.
|
(5) - Electrical data referred to standard unit without options, refer to name plate data.
|
(5) - Electrical data referred to standard unit without options, refer to name plate data.
|
Compressor
|
Type
|
|
|
|
|
|
Scroll compressor
|
|
Quantity
|
|
|
|
|
|
2
|
Space heating
|
Average climate water outlet 35°C
|
General
|
Seasonal space heating eff. class
|
|
|
|
|
|
A+++
|