| EWYT085B-XRA1 | EWYT115B-XRA1 | EWYT135B-XRA1 | EWYT175B-XRA1 | EWYT215B-XRA1 | EWYT215B-XRA2 | EWYT235B-XRA2 | EWYT265B-XRA2 | EWYT310B-XRA2 | EWYT350B-XRA2 | EWYT400B-XRA2 | EWYT440B-XRA2 | EWYT500B-XRA2 | EWYT560B-XRA2 | EWYT600B-XRA2 | EWYT630B-XRA2 | EWYT650B-XRA2 | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Cooling capacity | Nom. | kW | 79 | 103 | 124 | 164 | 203 | 204 | 227 | 247 | 282 | 321 | 364 | 398 | 458 | 507 | 548 | 583 | 600 | ||
| Capacity control | Method | Step | Step | Step | Step | Step | Step | Step | Step | Step | Step | Step | Step | Step | Step | Step | Step | Step | |||
| Minimum capacity | % | 50 | 38 | 50 | 38 | 50 | 19 | 17 | 25 | 22 | 19 | 17 | 25 | 22 | 19 | 18 | 17 | 17 | |||
| Power input | Cooling | Nom. | kW | 26.6 | 35.4 | 42.6 | 57.4 | 72.9 | 68.8 | 75.7 | 84.4 | 95.2 | 109 | 124 | 136 | 160 | 180 | 196 | 208 | 203 | |
| EER | 2.98 | 2.9 | 2.92 | 2.86 | 2.79 | 2.97 | 3 | 2.93 | 2.96 | 2.95 | 2.93 | 2.91 | 2.85 | 2.81 | 2.8 | 2.8 | 2.94 | ||||
| IPLV | 4.73 | 4.73 | 4.67 | 4.65 | 4.67 | 4.86 | 4.82 | 4.62 | 4.92 | 5.12 | 5.26 | 5.12 | 5.34 | 5.32 | 5.22 | 5.23 | 5.19 | ||||
| SEER | 4.21 | 4.37 | 4.21 | 4.41 | 4.16 | 4.42 | 4.43 | 4.13 | 4.74 | 4.8 | 4.82 | 4.63 | 4.92 | 4.89 | 4.83 | 4.79 | 4.72 | ||||
| Dimensions | Unit | Depth | mm | 2825 | 3425 | 3425 | 4025 | 4625 | 5550 | 6150 | 6150 | 4125 | 4125 | 5025 | 5025 | 5925 | 5925 | 6825 | 6825 | 6825 | |
| Height | mm | 1800 | 1800 | 1800 | 1800 | 1800 | 1800 | 1800 | 1800 | 2514 | 2514 | 2514 | 2514 | 2514 | 2514 | 2514 | 2514 | 2514 | |||
| Width | mm | 1195 | 1195 | 1195 | 1195 | 1195 | 1195 | 1195 | 1195 | 2282 | 2282 | 2282 | 2282 | 2282 | 2282 | 2282 | 2282 | 2282 | |||
| Weight | Operation weight | kg | 1121 | 1181 | 1261 | 1446 | 1626 | 2065 | 2365 | 2415 | 3175 | 3275 | 3845 | 3972 | 4428 | 4526 | 4990 | 5090 | 5090 | ||
| Unit | kg | 1110 | 1170 | 1250 | 1430 | 1610 | 2030 | 2330 | 2380 | 3140 | 3240 | 3810 | 3910 | 4366 | 4456 | 4920 | 5020 | 5020 | |||
| Casing | Colour | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | |||
| Material | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | ||||
| Air heat exchanger | Type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | |||
| Fan | Quantity | 6 | 8 | 8 | 10 | 12 | 14 | 16 | 16 | 7 | 8 | 10 | 10 | 12 | 12 | 14 | 14 | 14 | |||
| Type | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | ||||
| Fan motor | Drive | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | |||
| Compressor | Quantity | 2 | 2 | 2 | 2 | 2 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 5 | 6 | 6 | 6 | 6 | |||
| Type | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | ||||
| Starting method | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | ||||
| Sound power level | Cooling | Nom. | dBA | 77 | 81 | 83 | 85 | 87 | 84 | 85 | 86 | 84 | 84 | 85.2 | 85.5 | 86.2 | 86.3 | 86.9 | 87.1 | 91.6 | |
| Sound pressure level | Cooling | Nom. | dBA | 59 | 63 | 65 | 67 | 68 | 65 | 65 | 66 | 64 | 64 | 64.8 | 65.1 | 65.4 | 65.5 | 65.8 | 66 | 70.5 | |
| Refrigerant | Type | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | |||
| Charge | kg | 17.7 | 18.3 | 22 | 33.7 | 42.4 | 51.6 | 48.6 | 46 | 52.4 | 60.4 | 70.5 | 78 | 87.5 | 92 | 108 | 104 | 113 | |||
| Circuits | Quantity | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |||
| Piping connections | Evaporator water inlet/outlet (OD) | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 114.3 | 114.3 | 114.3 | 114.3 | 114.3 | 114.3 | |||
| Energy Efficiency Range | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | ||||
| Power supply | Phase | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | |||
| Frequency | Hz | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | |||
| Voltage | V | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | |||
| Voltage range | Min. | % | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | ||
| Max. | % | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | |||
| Unit | Starting current | Max | A | 213.0 | 329.0 | 343.0 | 465.0 | 497.0 | 412.0 | 429.0 | 443.0 | 572.0 | 606.0 | 644.0 | 674.0 | 728.0 | 773.0 | 811.0 | 841.0 | 841.0 | |
| Running current | Cooling | Nom. | A | 53.0 | 65.0 | 75.0 | 100.0 | 124.0 | 123.0 | 133.0 | 145.0 | 169.0 | 192.0 | 214.0 | 237.0 | 276.0 | 315.0 | 339.0 | 360.0 | 353.0 | |
| Max | A | 70.0 | 87.0 | 101.0 | 133.0 | 165.0 | 170.0 | 186.0 | 201.0 | 240.0 | 274.0 | 312.0 | 342.0 | 395.0 | 441.0 | 479.0 | 509.0 | 509.0 | |||
| Max unit current for wires sizing | A | 77.0 | 96.0 | 111.0 | 146.0 | 182.0 | 187.0 | 205.0 | 221.0 | 264.0 | 301.0 | 343.0 | 376.0 | 435.0 | 485.0 | 527.0 | 560.0 | 560.0 | |||
| Notes | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | ||||
| (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | |||||
| (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | |||||
| (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | |||||
| (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | |||||
| (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | |||||
| (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | |||||
| (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | |||||
| (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | |||||
| (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | |||||
| (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | |||||
| (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | |||||
| (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | |||||
| (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | |||||
| (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | |||||
| (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | |||||
| (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | |||||
| (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | |||||