Specifications Table for FBQ-D

FBQ35D2VEB FBQ50D2VEB FBQ60D2VEB FBQ71D2VEB FBQ100D2VEB FBQ125D2VEB FBQ140D2VEB
Sound pressure level Heating High dBA 37 37 31 31.0 36.0 38.0 38
    Medium dBA 34 34 28 28.0 33.0 35.0 35
    Low dBA 29 29 25 25.0 30.0 32.0 32
  Cooling Medium dBA 32 32 28 28.0 32.0 35.0 35
    Low dBA 29 29 25 25.0 30.0 32.0 32
    High dBA 35 35 30 30.0 34.0 37.0 37
Standard Accessories Operation manual 1 1 1 1 1 1 1
  Installation manual 1 1 1 1 1 1 1
  Drain hose 1 1 1 1 1 1 1
  Metal clamp for drain hose 1 1 1 1 1 1 1
  Washer for hanger bracket 8 8 8 8 8 8 8
  Screws 40 40 40 40 40 40 40
  Insulation for fitting 2 2 2 2 2 2 2
  Sealing pad 5 5 5 5 5 5 5
  Sealing pads       5 5 5 5
  Clamps 4 4 4 4 4 4 4
Refrigerant GWP   2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5
Control systems Wired remote control         BRC1E52A/B, BRC1D528 BRC1E52A/B, BRC1D528 BRC1E52A/B, BRC1D528 BRC1E52A/B, BRC1D528
  Infrared remote control         BRC4C65 BRC4C65 BRC4C65 BRC4C65
Piping connections Liquid OD mm 6.35 6.35 6.35 9.52 9.52 9.52 9.52
  Gas OD mm 9.52 12.7 12.7 15.9 15.9 15.9 15.9
  Drain   VP20 (I.D. 20/O.D. 26), drain height 625 mm VP20 (I.D. 20/O.D. 26), drain height 625 mm VP20 (I.D. 20/O.D. 26), drain height 625 mm VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26)
Sound power level Cooling dBA 60 60 56 56 58 62 62
Dimensions Unit Width mm 700 700 1,000 1,000 1,400 1,400 1,400
    Depth mm 800 800 800 800 800 800 800
    Height mm 245 245 245 245 245 245 245
Casing Material   Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate
  Colour   Not painted (galvanised) Not painted (galvanised) Not painted (galvanised) Not painted (galvanised) Not painted (galvanised) Not painted (galvanised) Not painted (galvanised)
Weight Unit kg 28.0 28.0 35.0 35.0 46.0 46.0 46.0
Fan External static pressure High Pa 150 150 150 150 150 150 150
    Nom. Pa 30 30 30 30 40 50 50
  Air flow rate Heating High m³/min         29.0 34.0 34.0
      Medium m³/min         26.0 29.0 29.0
      Low m³/min         23.0 23.5 23.5
    Cooling Low m³/min         23.0 23.5 23.5
      Medium m³/min         26.0 29.0 29.0
      High m³/min         29.0 34.0 34.0
Drain-up height mm 625 625 625 625 625 625 625
Power supply Phase   1~ 1~ 1~ 1~ 1~ 1~ 1~
  Name   VE VE VE VE VE VE VE
  Frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60 50/60
  Voltage V 220-240 220-240 220-240 220-240/220 220-240/220 220-240/220 220-240/220
Notes (1) - The sound power level is an absolute value indicating the power which a sound source generates. (1) - The sound power level is an absolute value indicating the power which a sound source generates. (1) - The sound power level is an absolute value indicating the power which a sound source generates. (1) - The sound power level is an absolute value indicating the power which a sound source generates. (1) - The sound power level is an absolute value indicating the power which a sound source generates. (1) - The sound power level is an absolute value indicating the power which a sound source generates. (1) - The sound power level is an absolute value indicating the power which a sound source generates.