Specifications Table for FTXF-F / RXF-D9

FTXF60F2V1B / RXF60D5V1B9 FTXF71F2V1B / RXF71D5V1B9
Cooling capacity Min. kW 1.70 2.30
  Nom. kW 6 7.10
  Max. kW 7 7.30
Heating capacity Min. kW 1.70 2.30
  Nom. kW 6.40 8.20
  Max. kW 8 9
Nominal efficiency EER   3.25 2.56
  COP   3.93 3.15
  Annual energy consumption kWh 923 1,387
  Energy labeling Directive Cooling   A E
    Heating   A A
Space cooling Energy efficiency class   A++ A
  Capacity Pdesign kW 6 7.10
  SEER   6.15 5.15
  Annual energy consumption kWh/a 342 483
Space heating (Average climate) Energy efficiency class   A+ A
  Capacity Pdesign kW 4.80 6.20
  SCOP/A   4.06 3.81
  Pdh Heating capacity at -10° kW 4.24 5.02
  Annual energy consumption kWh/a 1,654 2,275
Notes (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
  (3) - See separate drawing for operation range (3) - See separate drawing for operation range
  (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data