Specifications Table for FTXM-R / 4MXM-A8

FTXM35R2V1B / FTXM35R2V1B / 4MXM68A2V1B8 FTXM35R5V1B / FTXM35R5V1B / 4MXM68A2V1B8 FTXM20R2V1B / FTXM20R2V1B / FTXM25R2V1B / 4MXM68A2V1B8 FTXM20R5V1B / FTXM20R5V1B / FTXM25R5V1B / 4MXM68A2V1B8 FTXM20R2V1B / FTXM25R2V1B / FTXM25R2V1B / 4MXM68A2V1B8 FTXM20R5V1B / FTXM25R5V1B / FTXM25R5V1B / 4MXM68A2V1B8 FTXM20R2V1B / FTXM50R2V1B / 4MXM68A2V1B8 FTXM20R5V1B / FTXM50R2V1B / 4MXM68A2V1B8 FTXM25R2V1B / FTXM42R2V1B / 4MXM68A2V1B8 FTXM25R5V1B / FTXM42R5V1B / 4MXM68A2V1B8 FTXM20R2V1B / FTXM20R2V1B / FTXM20R2V1B / FTXM20R2V1B / 4MXM80A2V1B8 FTXM20R5V1B / FTXM20R5V1B / FTXM20R5V1B / FTXM20R5V1B / 4MXM80A2V1B8 FTXM20R2V1B / FTXM60R2V1B / 4MXM80A2V1B8 FTXM20R5V1B / FTXM60R2V1B / 4MXM80A2V1B8 FTXM35R2V1B / FTXM42R2V1B / 4MXM80A2V1B8 FTXM35R5V1B / FTXM42R5V1B / 4MXM80A2V1B8 FTXM20R2V1B / FTXM20R2V1B / FTXM42R2V1B / 4MXM80A2V1B8 FTXM20R5V1B / FTXM20R5V1B / FTXM42R5V1B / 4MXM80A2V1B8 FTXM20R2V1B / FTXM25R2V1B / FTXM35R2V1B / 4MXM80A2V1B8 FTXM20R5V1B / FTXM25R5V1B / FTXM35R5V1B / 4MXM80A2V1B8
Cooling capacity Nom. kW 6.8 6.8 6.5 6.5 6.8 6.8 6.8 6.8 6.7 6.7 7.40 7.40 7.40 7.40 7.70 7.70 8.00 8.00 7.40 7.40
Heating capacity Nom. kW 8.60 8.60 8.20 8.20 8.60 8.60 8.60 8.60 8.30 8.30 9.60 9.60 9.30 9.30 9.00 9.00 9.40 9.40 9.30 9.30
Nominal efficiency EER   3.94 3.94 4.01 4.01 3.85 3.85 3.59 3.59 3.74 3.74 4.17 4.17 3.43 3.43 3.11 3.11 3.56 3.56 3.79 3.79
  COP   3.81 3.81 4.49 4.49 4.38 4.38 3.82 3.82 3.95 3.95 4.58 4.58 3.73 3.73 3.56 3.56 4.08 4.08 4.02 4.02
  Annual energy consumption kWh 863 863 810 810 883 883 947 947 896 896 887 887 1,079 1,079 1,236 1,236 1,125 1,125 977 977
  Energy labeling Directive Cooling   A A A A A A A A A A A A A A B B A A A A
    Heating   A A A A A A A A A A A A A A B B A A A A
Space cooling Energy efficiency class   A++ A++ A++ A++ A++ A++ A++ A++ A++ A++ A++ A++ A++ A++ A++ A++ A++ A++ A++ A++
  Capacity Pdesign kW 6.80 6.80 6.50 6.50 6.80 6.80 6.80 6.80 6.70 6.70 7.40 7.40 7.40 7.40 7.70 7.70 8.00 8.00 7.40 7.40
  SEER   6.97 6.97 7.76 7.76 7.71 7.71 6.75 6.75 6.94 6.94 7.40 7.40 6.73 6.73 6.52 6.52 6.93 6.93 7.07 7.07
  Annual energy consumption kWh/a 342 342 294 294 309 309 352 352 338 338 351 351 387 387 417 417 405 405 370 370
Space heating (Average climate) Energy efficiency class   A+ A+ A+ A+ A+ A+ A A A A A+ A+ A+ A+ A+ A+ A+ A+ A+ A+
  Capacity Pdesign kW 4.80 4.80 5.30 5.30 5.30 5.30 4.50 4.50 4.30 4.30 6.23 6.23 4.27 4.27 4.27 4.27 5.37 5.37 5.37 5.37
  SCOP/A   4.00 4.00 4.09 4.09 4.10 4.10 3.90 3.90 3.86 3.86 4.56 4.56 4.33 4.33 4.23 4.23 4.34 4.34 4.31 4.31
  Pdh Heating capacity at -10° kW 3.73 3.73 4.21 4.21 4.22 4.22 3.55 3.55 3.41 3.41 4.73 4.73 3.71 3.71 3.68 3.68 4.34 4.34 4.37 4.37
  Annual energy consumption kWh/a 1,679 1,679 1,814 1,814 1,807 1,807 1,612 1,612 1,559 1,559 1,913 1,913 1,382 1,382 1,413 1,413 1,732 1,732 1,744 1,744
Notes (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
  (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range
  (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data