| FWF02DATN5V3-- | FWF02DAFN5V3-- | FWF03DATN5V3-- | FWF03DAFN5V3-- | FWF04DATN5V3-- | FWF04DAFN5V3-- | FWF05DATN5V3-- | FWF05DAFN5V3-- | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Cooling capacity (standard conditions) | Sensible capacity 2-pipe | Low | kW | 1.09 | 1.75 | 1.91 | 2.11 | |||||
| High | kW | 1.76 | 2.31 | 3.01 | 3.88 | |||||||
| Sensible capacity 4-pipe | Low | kW | 1.20 | 1.61 | 1.78 | 1.85 | ||||||
| High | kW | 1.76 | 2.19 | 2.88 | 3.67 | |||||||
| Total capacity 2-pipe | Low | kW | 1.30 | 2.37 | 2.65 | 2.93 | ||||||
| High | kW | 2.00 | 3.00 | 4.07 | 5.10 | |||||||
| Total capacity 4-pipe | Low | kW | 1.44 | 2.30 | 2.58 | 2.64 | ||||||
| High | kW | 2.00 | 3.00 | 4.00 | 5.02 | |||||||
| Heating capacity (standard conditions) | Capacity 2-pipe | Low | kW | 1.56 | 2.44 | 2.69 | 2.95 | |||||
| High | kW | 2.54 | 3.30 | 4.26 | 5.74 | |||||||
| Capacity 4-pipe | Low | kW | 2.23 | 2.78 | 2.90 | 2.99 | ||||||
| High | kW | 3.31 | 4.15 | 4.59 | 5.64 | |||||||
| Power input | Low | kW | 0.01 | 0.01 | 0.01 | 0.02 | 0.01 | 0.02 | 0.02 | 0.02 | ||
| High | kW | 0.018 | 0.017 | 0.019 | 0.019 | 0.024 | 0.024 | 0.045 | 0.047 | |||
| Dimensions | Unit | Height | mm | 260 | 260 | 260 | 260 | 260 | 260 | 260 | 260 | |
| Width | mm | 642 | 642 | 642 | 642 | 642 | 642 | 642 | 642 | |||
| Depth | mm | 575 | 575 | 575 | 575 | 575 | 575 | 575 | 575 | |||
| Weight | Unit | kg | 14.5 | 16.0 | 15.5 | 17.0 | 15.5 | 17.0 | 15.5 | 17.0 | ||
| Fan | Air flow rate | Low | m³/h | 278 | 301 | 363 | 356 | 369 | 361 | 408 | 367 | |
| High | m³/h | 498 | 477 | 516 | 534 | 623 | 612 | 860 | 847 | |||
| Total sound power level | Low | dBA | 33.0 | 34.0 | 36.0 | 36.0 | 36.0 | 38.0 | 39.0 | 40.0 | ||
| High | dBA | 41.0 | 41.0 | 42.0 | 44.0 | 47.0 | 48.0 | 54.0 | 56.0 | |||
| Sound pressure level | Low | dBA | 19.0 | 20.0 | 22.0 | 22.0 | 22.0 | 24.0 | 25.0 | 26.0 | ||
| High | dBA | 27.0 | 27.0 | 28.0 | 30.0 | 33.0 | 34.0 | 40.0 | 42.0 | |||
| Water flow | Cooling | Low | l/h | 224 | 248 | 407 | 396 | 455 | 444 | 504 | 455 | |
| High | l/h | 344 | 345 | 515 | 516 | 699 | 687 | 878 | 864 | |||
| Heating | High | l/h | 437 | 285 | 568 | 357 | 733 | 395 | 987 | 485 | ||
| Low | l/h | 269 | 192 | 419 | 239 | 463 | 249 | 507 | 257 | |||
| Water pressure drop | Cooling | Low | kPa | 6 | 7 | 18 | 17 | 16 | 15 | 18 | 16 | |
| High | kPa | 8 | 8 | 25 | 25 | 29 | 28 | 41 | 41 | |||
| Heating | Low | kPa | 6 | 7 | 21 | 5 | 15 | 5 | 18 | 6 | ||
| High | kPa | 11 | 10 | 32 | 8 | 30 | 9 | 50 | 12 | |||
| Allowed water temperature | Cooling | Min. | °C | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | |
| Max. | °C | 75.0 | 75.0 | 75.0 | 75.0 | 75.0 | 75.0 | 75.0 | 75.0 | |||
| Heating | Min. | °C | 5.00 | 5.00 | 5.00 | 5.00 | 5.00 | 5.00 | 5.00 | 5.00 | ||
| Max. | °C | 75.000 | 75.000 | 75.000 | 75.000 | 75.000 | 75.000 | 75.000 | 75.000 | |||
| Piping connections | Water | Inlet | 3/4" BSP (female thread) | 3/4" BSP (female thread) | 3/4" BSP (female thread) | 3/4" BSP (female thread) | 3/4" BSP (female thread) | 3/4" BSP (female thread) | 3/4" BSP (female thread) | 3/4" BSP (female thread) | ||
| Outlet | 3/4" BSP (female thread) | 3/4" BSP (female thread) | 3/4" BSP (female thread) | 3/4" BSP (female thread) | 3/4" BSP (female thread) | 3/4" BSP (female thread) | 3/4" BSP (female thread) | 3/4" BSP (female thread) | ||||
| Drain | OD | mm | VP20 (External dia.26, Internal dia. 20) | VP20 (External dia.26, Internal dia. 20) | VP20 (External dia.26, Internal dia. 20) | VP20 (External dia.26, Internal dia. 20) | VP20 (External dia.26, Internal dia. 20) | VP20 (External dia.26, Internal dia. 20) | VP20 (External dia.26, Internal dia. 20) | VP20 (External dia.26, Internal dia. 20) | ||
| Power supply | Type | 230 / 1 / 50 | 230 / 1 / 50 | 230 / 1 / 50 | 230 / 1 / 50 | 230 / 1 / 50 | 230 / 1 / 50 | 230 / 1 / 50 | 230 / 1 / 50 | |||
| Phase | 1~ | 1~ | 1~ | 1~ | 1~ | 1~ | 1~ | 1~ | ||||
| Frequency | Hz | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | |||
| Voltage | V | 230 | 230 | 230 | 230 | 230 | 230 | 230 | 230 | |||
| Notes | (1) - Cooling: air 27°CDB, 19°CWB; entering water 7°C; leaving water 12°C | (1) - Cooling: air 27°CDB, 19°CWB; entering water 7°C; leaving water 12°C | (1) - Cooling: air 27°CDB, 19°CWB; entering water 7°C; leaving water 12°C | (1) - Cooling: air 27°CDB, 19°CWB; entering water 7°C; leaving water 12°C | (1) - Cooling: air 27°CDB, 19°CWB; entering water 7°C; leaving water 12°C | (1) - Cooling: air 27°CDB, 19°CWB; entering water 7°C; leaving water 12°C | (1) - Cooling: air 27°CDB, 19°CWB; entering water 7°C; leaving water 12°C | (1) - Cooling: air 27°CDB, 19°CWB; entering water 7°C; leaving water 12°C | ||||
| (2) - Heating: 2 pipe: air 20°CDB, 15°CWB; entering water 45°C; leaving water 40°C | (2) - Heating: 2 pipe: air 20°CDB, 15°CWB; entering water 45°C; leaving water 40°C | (2) - Heating: 2 pipe: air 20°CDB, 15°CWB; entering water 45°C; leaving water 40°C | (2) - Heating: 2 pipe: air 20°CDB, 15°CWB; entering water 45°C; leaving water 40°C | (2) - Heating: 2 pipe: air 20°CDB, 15°CWB; entering water 45°C; leaving water 40°C | (2) - Heating: 2 pipe: air 20°CDB, 15°CWB; entering water 45°C; leaving water 40°C | (2) - Heating: 2 pipe: air 20°CDB, 15°CWB; entering water 45°C; leaving water 40°C | (2) - Heating: 2 pipe: air 20°CDB, 15°CWB; entering water 45°C; leaving water 40°C | |||||
| (3) - Heating: 4 pipe: air 20°CDB, 15°CWB; entering water 65°C; leaving water 55°C | (3) - Heating: 4 pipe: air 20°CDB, 15°CWB; entering water 65°C; leaving water 55°C | (3) - Heating: 4 pipe: air 20°CDB, 15°CWB; entering water 65°C; leaving water 55°C | (3) - Heating: 4 pipe: air 20°CDB, 15°CWB; entering water 65°C; leaving water 55°C | (3) - Heating: 4 pipe: air 20°CDB, 15°CWB; entering water 65°C; leaving water 55°C | (3) - Heating: 4 pipe: air 20°CDB, 15°CWB; entering water 65°C; leaving water 55°C | (3) - Heating: 4 pipe: air 20°CDB, 15°CWB; entering water 65°C; leaving water 55°C | (3) - Heating: 4 pipe: air 20°CDB, 15°CWB; entering water 65°C; leaving water 55°C | |||||
| (4) - The unit is not pre-charged. A minimal rest charge is present related to factory quality inspection | (4) - The unit is not pre-charged. A minimal rest charge is present related to factory quality inspection | (4) - The unit is not pre-charged. A minimal rest charge is present related to factory quality inspection | (4) - The unit is not pre-charged. A minimal rest charge is present related to factory quality inspection | (4) - The unit is not pre-charged. A minimal rest charge is present related to factory quality inspection | (4) - The unit is not pre-charged. A minimal rest charge is present related to factory quality inspection | (4) - The unit is not pre-charged. A minimal rest charge is present related to factory quality inspection | (4) - The unit is not pre-charged. A minimal rest charge is present related to factory quality inspection | |||||
| (5) - Airflow value measurements are performed at 20C (DB) /15 C(WB) condition. | (5) - Airflow value measurements are performed at 20C (DB) /15 C(WB) condition. | (5) - Airflow value measurements are performed at 20C (DB) /15 C(WB) condition. | (5) - Airflow value measurements are performed at 20C (DB) /15 C(WB) condition. | (5) - Airflow value measurements are performed at 20C (DB) /15 C(WB) condition. | (5) - Airflow value measurements are performed at 20C (DB) /15 C(WB) condition. | (5) - Airflow value measurements are performed at 20C (DB) /15 C(WB) condition. | (5) - Airflow value measurements are performed at 20C (DB) /15 C(WB) condition. | |||||