| FXAQ15AUV1B | FXAQ20AUV1B | FXAQ25AUV1B | FXAQ32AUV1B | FXAQ40AUV1B | FXAQ50AUV1B | FXAQ63AUV1B | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Sound pressure level | Heating | At high fan speed | dBA | 33.0 | 34.0 | 36.0 | 38.5 | 38.0 | 42.0 | 47.0 | |
| At low fan speed | dBA | 28.5 | 28.5 | 28.5 | 28.5 | 33.5 | 35.5 | 38.5 | |||
| Cooling | At low fan speed | dBA | 28.5 | 28.5 | 28.5 | 28.5 | 33.5 | 35.5 | 38.5 | ||
| At high fan speed | dBA | 32.0 | 33.0 | 35.0 | 37.5 | 37.0 | 41.0 | 46.5 | |||
| Standard Accessories | Installation and operation manual | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |||
| Installation panel | 1 | 1 | 1 | 1 | 1 | 1 | 1 | ||||
| Paper pattern for installation | 1 | 1 | 1 | 1 | 1 | 1 | 1 | ||||
| Insulation tape | 1 | 1 | 1 | 1 | 1 | 1 | 1 | ||||
| Clamps | 1 | 1 | 1 | 1 | 1 | 1 | 1 | ||||
| Screws | 1 | 1 | 1 | 1 | 1 | 1 | 1 | ||||
| Refrigerant | GWP | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | |||
| Type | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | ||||
| Power input - 50Hz | Cooling | At high fan speed | kW | 0.02 | 0.02 | 0.03 | 0.03 | 0.02 | 0.03 | 0.05 | |
| Heating | At high fan speed | kW | 0.03 | 0.03 | 0.03 | 0.04 | 0.02 | 0.04 | 0.06 | ||
| Cooling capacity | Total capacity | At high fan speed | kW | 1.7 (1) | 2.2 (1) | 2.8 (1) | 3.6 (1) | 4.5 (1) | 5.6 (1) | 7.1 (1) | |
| Piping connections | Liquid | OD | mm | 6.35 | 6.35 | 6.35 | 6.35 | 6.35 | 6.35 | 9.52 | |
| Type | Flare connection | Flare connection | Flare connection | Flare connection | Flare connection | Flare connection | Flare connection | ||||
| Gas | OD | mm | 12.7 | 12.7 | 12.7 | 12.7 | 12.7 | 12.7 | 15.9 | ||
| Type | Flare connection | Flare connection | Flare connection | Flare connection | Flare connection | Flare connection | Flare connection | ||||
| Drain | VP13 (I.D. 15/O.D. 18) | VP13 (I.D. 15/O.D. 18) | VP13 (I.D. 15/O.D. 18) | VP13 (I.D. 15/O.D. 18) | VP13 (I.D. 15/O.D. 18) | VP13 (I.D. 15/O.D. 18) | VP13 (I.D. 15/O.D. 18) | ||||
| Sound power level | Cooling | At high fan speed | dBA | 51.0 | 52.0 | 53.0 | 55.0 | 55.0 | 58.0 | 63.0 | |
| Air filter | Type | Washable resin net | Washable resin net | Washable resin net | Washable resin net | Washable resin net | Washable resin net | Washable resin net | |||
| Dimensions | Unit | Width | mm | 795 | 795 | 795 | 795 | 1,050 | 1,050 | 1,050 | |
| Depth | mm | 266 | 266 | 266 | 266 | 269 | 269 | 269 | |||
| Height | mm | 290 | 290 | 290 | 290 | 290 | 290 | 290 | |||
| Casing | Colour | White | White | White | White | White | White | White | |||
| Weight | Unit | kg | 12 | 12 | 12 | 12 | 15 | 15 | 15 | ||
| Fan | Air flow rate - 50Hz | Cooling | At high fan speed | m³/min | 8.4 | 9.1 | 9.4 | 9.8 | 12.2 | 14.4 | 18.3 |
| At low fan speed | m³/min | 7.0 | 7.0 | 7.0 | 7.0 | 9.7 | 11.5 | 13.5 | |||
| Heating capacity | Total capacity | At high fan speed | kW | 1.9 (2) | 2.5 (2) | 3.2 (2) | 4.0 (2) | 5.0 (2) | 6.3 (2) | 8.0 (2) | |
| Current - 50Hz | Maximum fuse amps (MFA) | A | 16 | 16 | 16 | 16 | 16 | 16 | 16 | ||
| Power supply | Phase | 1~ | 1~ | 1~ | 1~ | 1~ | 1~ | 1~ | |||
| Name | V1 | V1 | V1 | V1 | V1 | V1 | V1 | ||||
| Frequency | Hz | 50 | 50 | 50 | 50 | 50 | 50 | 50 | |||
| Voltage | V | 220-240 | 220-240 | 220-240 | 220-240 | 220-240 | 220-240 | 220-240 | |||
| Notes | (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m (horizontal) | (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m (horizontal) | (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m (horizontal) | (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m (horizontal) | (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m (horizontal) | (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m (horizontal) | (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m (horizontal) | ||||
| (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m (horizontal) | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m (horizontal) | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m (horizontal) | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m (horizontal) | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m (horizontal) | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m (horizontal) | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m (horizontal) | |||||
| (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. | (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. | (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. | (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. | (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. | (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. | (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. | |||||
| (4) - Sound levels are measured in an anechoic room. | (4) - Sound levels are measured in an anechoic room. | (4) - Sound levels are measured in an anechoic room. | (4) - Sound levels are measured in an anechoic room. | (4) - Sound levels are measured in an anechoic room. | (4) - Sound levels are measured in an anechoic room. | (4) - Sound levels are measured in an anechoic room. | |||||
| (5) - Operation sound differs with operation and ambient conditions | (5) - Operation sound differs with operation and ambient conditions | (5) - Operation sound differs with operation and ambient conditions | (5) - Operation sound differs with operation and ambient conditions | (5) - Operation sound differs with operation and ambient conditions | (5) - Operation sound differs with operation and ambient conditions | (5) - Operation sound differs with operation and ambient conditions | |||||
| (6) - The sound pressure level is measured via a microphone at 1m distance of the unit. | (6) - The sound pressure level is measured via a microphone at 1m distance of the unit. | (6) - The sound pressure level is measured via a microphone at 1m distance of the unit. | (6) - The sound pressure level is measured via a microphone at 1m distance of the unit. | (6) - The sound pressure level is measured via a microphone at 1m distance of the unit. | (6) - The sound pressure level is measured via a microphone at 1m distance of the unit. | (6) - The sound pressure level is measured via a microphone at 1m distance of the unit. | |||||
| (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | |||||
| (8) - Maximum allowable voltage range variation between phases is 2%. | (8) - Maximum allowable voltage range variation between phases is 2%. | (8) - Maximum allowable voltage range variation between phases is 2%. | (8) - Maximum allowable voltage range variation between phases is 2%. | (8) - Maximum allowable voltage range variation between phases is 2%. | (8) - Maximum allowable voltage range variation between phases is 2%. | (8) - Maximum allowable voltage range variation between phases is 2%. | |||||
| (9) - MCA/MFA: MCA = 1.25 x FLA | (9) - MCA/MFA: MCA = 1.25 x FLA | (9) - MCA/MFA: MCA = 1.25 x FLA | (9) - MCA/MFA: MCA = 1.25 x FLA | (9) - MCA/MFA: MCA = 1.25 x FLA | (9) - MCA/MFA: MCA = 1.25 x FLA | (9) - MCA/MFA: MCA = 1.25 x FLA | |||||
| (10) - Contains fluorinated greenhouse gases | (10) - Contains fluorinated greenhouse gases | (10) - Contains fluorinated greenhouse gases | (10) - Contains fluorinated greenhouse gases | (10) - Contains fluorinated greenhouse gases | (10) - Contains fluorinated greenhouse gases | (10) - Contains fluorinated greenhouse gases | |||||
| (11) - Instead of a fuse, use a circuit breaker | (11) - Instead of a fuse, use a circuit breaker | (11) - Instead of a fuse, use a circuit breaker | (11) - Instead of a fuse, use a circuit breaker | (11) - Instead of a fuse, use a circuit breaker | (11) - Instead of a fuse, use a circuit breaker | (11) - Instead of a fuse, use a circuit breaker | |||||
| (12) - Select wire size based on the value of MCA | (12) - Select wire size based on the value of MCA | (12) - Select wire size based on the value of MCA | (12) - Select wire size based on the value of MCA | (12) - Select wire size based on the value of MCA | (12) - Select wire size based on the value of MCA | (12) - Select wire size based on the value of MCA | |||||
| (13) - Next lower standard fuse rating minimum 16A | (13) - Next lower standard fuse rating minimum 16A | (13) - Next lower standard fuse rating minimum 16A | (13) - Next lower standard fuse rating minimum 16A | (13) - Next lower standard fuse rating minimum 16A | (13) - Next lower standard fuse rating minimum 16A | (13) - Next lower standard fuse rating minimum 16A | |||||
| (14) - MFA ≤ 4 x FLA | (14) - MFA ≤ 4 x FLA | (14) - MFA ≤ 4 x FLA | (14) - MFA ≤ 4 x FLA | (14) - MFA ≤ 4 x FLA | (14) - MFA ≤ 4 x FLA | (14) - MFA ≤ 4 x FLA | |||||