Specifications Table for FXKA-A

FXKA20AMVEB FXKA25AMVEB FXKA32AMVEB FXKA40AMVEB FXKA50AMVEB FXKA63AMVEB
Cooling capacity Total capacity At high fan speed kW 2.2 2.8 3.6 4.5 5.6 7.1
Heating capacity Total capacity At high fan speed kW 2.5 3.2 4 5 6.3 8
Power input - 50Hz Cooling At high fan speed kW 0.026 0.026 0.039 0.047 0.073 0.118
  Heating At high fan speed kW 0.034 0.034 0.039 0.047 0.073 0.118
Dimensions Unit Height mm 200 200 200 200 200 200
    Width mm 840 840 840 1240 1240 1240
    Depth mm 470 470 470 470 470 470
Weight Unit kg 18 18 19 24 24 24
Casing Colour   Not painted (galvanised) Not painted (galvanised) Not painted (galvanised) Not painted (galvanised) Not painted (galvanised) Not painted (galvanised)
  Material   Galvanised steel Galvanised steel Galvanised steel Galvanised steel Galvanised steel Galvanised steel
Fan Air flow rate - 50Hz Cooling At high fan speed m³/min 7.5 7.5 9.4 14.4 17.6 21.5
      At low fan speed m³/min 5 5 7.6 11.1 12.6 14.4
Refrigerant Type   R-32 R-32 R-32 R-32 R-32 R-32
  GWP   675 675 675 675 675 675
Sound power level Cooling At high fan speed dBA 46 46 50.5 52.5 57 61.5
Sound pressure level Cooling At high fan speed dBA 32 32 37 38.5 42 48.5
    At medium fan speed dBA 27.5 27.5 34 34.5 38 43.5
    At low fan speed dBA 22.5 22.5 31.5 31.5 34.5 38.5
  Heating At high fan speed dBA 36 36 39 39.5 44 49
    At medium fan speed dBA 31 31 35.5 36 39.5 44
    At low fan speed dBA 25.5 25.5 32.5 32.5 36 39.5
Piping connections Liquid Type   Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection
    OD mm 6.4 6.4 6.4 6.4 6.4 6.4
  Gas Type   Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection
    OD mm 9.5 9.5 9.5 12.7 12.7 12.7
  Drain   I.D. 20/O.D. 26 I.D. 20/O.D. 26 I.D. 20/O.D. 26 I.D. 20/O.D. 26 I.D. 20/O.D. 26 I.D. 20/O.D. 26
Decoration panel Model   BYK32GJW1 BYK32GJW1 BYK32GJW1 BYK63GJW1 BYK63GJW1 BYK63GJW1
  Colour   Fresh White Fresh White Fresh White Fresh White Fresh White Fresh White
  Dimensions Height mm 80 80 80 80 80 80
    Width mm 950 950 950 1350 1350 1350
    Depth mm 550 550 550 550 550 550
  Weight kg 8 8 8 10 10 10
Air filter Type   Removable / washable Removable / washable Removable / washable Removable / washable Removable / washable Removable / washable
Power supply Name   VE VE VE VE VE VE
  Phase   1~ 1~ 1~ 1~ 1~ 1~
  Power supply-=-Frequency Frequency   50/60 50/60 50/60 50/60 50/60 50/60
  Power supply-=-Voltage Voltage   220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220
Current - 50Hz Current - 50Hz-=-Maximum fuse amps (MFA) Maximum fuse amps (MFA)   6 6 6 6 6 6
Required ceiling void > mm 260 260 260 260 260 260
Standard Accessories General safety precautions 1 1 1 1 1 1
  Sealing material (drain hose) 1 1 1 1 1 1
  Clamp for drain hose 1 1 1 1 1 1
  Drain hose 1 1 1 1 1 1
  Installation and operation manual 1 1 1 1 1 1
  Paper pattern for installation 1 1 1 1 1 1
Notes (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
  (3) - The sound power level is an absolute value indicating the power which a sound source generates. (3) - The sound power level is an absolute value indicating the power which a sound source generates. (3) - The sound power level is an absolute value indicating the power which a sound source generates. (3) - The sound power level is an absolute value indicating the power which a sound source generates. (3) - The sound power level is an absolute value indicating the power which a sound source generates. (3) - The sound power level is an absolute value indicating the power which a sound source generates.
  (4) - Instead of a fuse, use a circuit breaker (4) - Instead of a fuse, use a circuit breaker (4) - Instead of a fuse, use a circuit breaker (4) - Instead of a fuse, use a circuit breaker (4) - Instead of a fuse, use a circuit breaker (4) - Instead of a fuse, use a circuit breaker
  (5) - Select wire size based on the value of MCA (5) - Select wire size based on the value of MCA (5) - Select wire size based on the value of MCA (5) - Select wire size based on the value of MCA (5) - Select wire size based on the value of MCA (5) - Select wire size based on the value of MCA