| FXNQ20A2VEB | FXNQ25A2VEB | FXNQ32A2VEB | FXNQ40A2VEB | FXNQ50A2VEB | FXNQ63A2VEB | |||||
|---|---|---|---|---|---|---|---|---|---|---|
| Cooling capacity | Total capacity | At high fan speed | kW | 2.20 | 2.80 | 3.60 | 4.50 | 5.60 | 7.10 | |
| Heating capacity | Total capacity | At high fan speed | kW | 2.50 | 3.20 | 4.00 | 5.00 | 6.30 | 8.00 | |
| Power input - 50Hz | Cooling | At high fan speed | kW | 0.071 | 0.071 | 0.071 | 0.078 | 0.099 | 0.110 | |
| Heating | At high fan speed | kW | 0.068 | 0.068 | 0.068 | 0.075 | 0.096 | 0.107 | ||
| Dimensions | Unit | Height | mm | 620, 720 (1) | 620, 720 (1) | 620, 720 (1) | 620, 720 (1) | 620, 720 (1) | 620, 720 (1) | |
| Width | mm | 790 | 790 | 790 | 990 | 990 | 1,190 | |||
| Depth | mm | 200 | 200 | 200 | 200 | 200 | 200 | |||
| Weight | Unit | kg | 23.5 | 23.5 | 23.5 | 27.5 | 27.5 | 32.0 | ||
| Casing | Colour | Unpainted | Unpainted | Unpainted | Unpainted | Unpainted | Unpainted | |||
| Material | Galvanised steel plate | Galvanised steel plate | Galvanised steel plate | Galvanised steel plate | Galvanised steel plate | Galvanised steel plate | ||||
| Fan | Air flow rate - 50Hz | Cooling | At high fan speed | m³/min | 8.0 | 8.0 | 8.0 | 10.5 | 12.5 | 16.5 |
| At low fan speed | m³/min | 6.4 | 6.4 | 6.4 | 8.5 | 10.0 | 13.0 | |||
| External static pressure - 50Hz | High | Pa | 41.0 | 41.0 | 42.0 | 52.0 | 59.0 | 55.0 | ||
| Refrigerant | Type | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | |||
| GWP | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | ||||
| Sound power level | Cooling | At high fan speed | dBA | 51 | 51 | 51 | 52 | 53 | 54 | |
| Sound pressure level | Cooling | At high fan speed | dBA | 30.0 | 30.0 | 30.0 | 32.0 | 33.0 | 35.0 | |
| At medium fan speed | dBA | 28.5 | 28.5 | 28.5 | 30.0 | 31.0 | 33.0 | |||
| At low fan speed | dBA | 27.0 | 27.0 | 27.0 | 28.0 | 29.0 | 32.0 | |||
| Heating | At high fan speed | dBA | 30.0 | 30.0 | 30.0 | 32.0 | 33.0 | 35.0 | ||
| At medium fan speed | dBA | 28.5 | 28.5 | 28.5 | 30.0 | 31.0 | 33.0 | |||
| At low fan speed | dBA | 27.0 | 27.0 | 27.0 | 28.0 | 29.0 | 32.0 | |||
| Piping connections | Liquid | Type | Flare connection | Flare connection | Flare connection | Flare connection | Flare connection | Flare connection | ||
| OD | mm | 6.35 | 6.35 | 6.35 | 6.35 | 6.35 | 9.52 | |||
| Gas | Type | Flare connection | Flare connection | Flare connection | Flare connection | Flare connection | Flare connection | |||
| OD | mm | 12.7 | 12.7 | 12.7 | 12.7 | 12.7 | 15.9 | |||
| Drain | VP20 (I.D. 20/O.D. 26) | VP20 (I.D. 20/O.D. 26) | VP20 (I.D. 20/O.D. 26) | VP20 (I.D. 20/O.D. 26) | VP20 (I.D. 20/O.D. 26) | VP20 (I.D. 20/O.D. 26) | ||||
| Air filter | Type | Resin net | Resin net | Resin net | Resin net | Resin net | Resin net | |||
| Power supply | Name | VE | VE | VE | VE | VE | VE | |||
| Phase | 1~ | 1~ | 1~ | 1~ | 1~ | 1~ | ||||
| Frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | |||
| Voltage | V | 220-240/220 | 220-240/220 | 220-240/220 | 220-240/220 | 220-240/220 | 220-240/220 | |||
| Current - 50Hz | Maximum fuse amps (MFA) | A | 16 | 16 | 16 | 16 | 16 | 16 | ||
| Notes | (1) - Including installation legs | (1) - Including installation legs | (1) - Including installation legs | (1) - Including installation legs | (1) - Including installation legs | (1) - Including installation legs | ||||
| (2) - The sound power level is an absolute value indicating the power which a sound source generates. | (2) - The sound power level is an absolute value indicating the power which a sound source generates. | (2) - The sound power level is an absolute value indicating the power which a sound source generates. | (2) - The sound power level is an absolute value indicating the power which a sound source generates. | (2) - The sound power level is an absolute value indicating the power which a sound source generates. | (2) - The sound power level is an absolute value indicating the power which a sound source generates. | |||||
| (3) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (3) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (3) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (3) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (3) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (3) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | |||||
| (4) - Select wire size based on the value of MCA | (4) - Select wire size based on the value of MCA | (4) - Select wire size based on the value of MCA | (4) - Select wire size based on the value of MCA | (4) - Select wire size based on the value of MCA | (4) - Select wire size based on the value of MCA | |||||
| (5) - Maximum allowable voltage range variation between phases is 2%. | (5) - Maximum allowable voltage range variation between phases is 2%. | (5) - Maximum allowable voltage range variation between phases is 2%. | (5) - Maximum allowable voltage range variation between phases is 2%. | (5) - Maximum allowable voltage range variation between phases is 2%. | (5) - Maximum allowable voltage range variation between phases is 2%. | |||||
| (6) - Use a circuit breaker instead of a fuse. | (6) - Use a circuit breaker instead of a fuse. | (6) - Use a circuit breaker instead of a fuse. | (6) - Use a circuit breaker instead of a fuse. | (6) - Use a circuit breaker instead of a fuse. | (6) - Use a circuit breaker instead of a fuse. | |||||
| (7) - MCA/MFA; MCA= 1,25 x FLA; MFA=< 4 x FLA; The next lower standard fuse rating is minimum 16 ampere. | (7) - MCA/MFA; MCA= 1,25 x FLA; MFA=< 4 x FLA; The next lower standard fuse rating is minimum 16 ampere. | (7) - MCA/MFA; MCA= 1,25 x FLA; MFA=< 4 x FLA; The next lower standard fuse rating is minimum 16 ampere. | (7) - MCA/MFA; MCA= 1,25 x FLA; MFA=< 4 x FLA; The next lower standard fuse rating is minimum 16 ampere. | (7) - MCA/MFA; MCA= 1,25 x FLA; MFA=< 4 x FLA; The next lower standard fuse rating is minimum 16 ampere. | (7) - MCA/MFA; MCA= 1,25 x FLA; MFA=< 4 x FLA; The next lower standard fuse rating is minimum 16 ampere. | |||||
| (8) - Contains fluorinated greenhouse gases | (8) - Contains fluorinated greenhouse gases | (8) - Contains fluorinated greenhouse gases | (8) - Contains fluorinated greenhouse gases | (8) - Contains fluorinated greenhouse gases | (8) - Contains fluorinated greenhouse gases | |||||
| (9) - Next lower standard fuse rating minimum 16A | (9) - Next lower standard fuse rating minimum 16A | (9) - Next lower standard fuse rating minimum 16A | (9) - Next lower standard fuse rating minimum 16A | (9) - Next lower standard fuse rating minimum 16A | (9) - Next lower standard fuse rating minimum 16A | |||||