Specifications Table for REYQ-U

REYQ8U7Y1B REYQ10U7Y1B REYQ10U7Y1B. REYQ12U7Y1B REYQ13U7Y1B REYQ14U7Y1B REYQ16U7Y1B REYQ16U7Y1B. REYQ18U7Y1B REYQ18U7Y1B. REYQ20U7Y1B. REYQ20U7Y1B REYQ22U7Y1B REYQ24U7Y1B REYQ26U7Y1B REYQ28U7Y1B REYQ30U7Y1B REYQ32U7Y1B REYQ34U7Y1B REYQ36U7Y1B REYQ38U7Y1B REYQ40U7Y1B REYQ42U7Y1B REYQ44U7Y1B REYQ46U7Y1B REYQ48U7Y1B REYQ50U7Y1B REYQ52U7Y1B REYQ54U7Y1B
Sound pressure level Cooling Nom. dBA         60.0 (5)       62.0 (5) 60.0 (5) 62.5 (5) 65.0 (5) 62.5 (5) 64.0 (5) 63.5 (5) 65.1 (5) 64.5 (5) 66.0 (5) 65.5 (5) 67.1 (5) 65.2 (5) 65.2 (5) 66.5 (5) 67.2 (5) 67.0 (5) 67.8 (5) 67.5 (5) 67.1 (5) 66.8 (5)
Standard Accessories Installation and operation manual 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
  Connection pipes 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
SEER recommended combination 2 6.8 6.8 7.1 6.2 7.5 6.6 6.2 7.3 6.4 6.8 6.4 6.3 6.5 6.4 6.4 6.3 6.6 6.2 6.6 6.5 6.6 6.6 6.4 6.3 6.3 6.2 6.5 6.7 7.0
SEER recommended combination 3 7.2 6.7 6.9 6.6 7.4 6.6 6.1 7.1 6.4 6.9 6.8 6.3 6.6 6.5 6.6 6.4 6.8 6.1 6.6 6.5 6.9 6.7 6.3 6.3 6.2 6.1 6.4 6.7 7.0
Capacity range HP 8 10 10 12 13 14 16 16 18 18 20 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54
ηs,c recommended combination 2         296.3       251.9 269.4 252.4 249.6 256.8 253.7 254.1 247.9 262.9 244.5 260.6 257.6 263.0 259.5 252.5 247.1 248.8 244.5 255.9 267.0 276.7
Operation range Cooling Max. °CDB                 43.0     43.0
    Min. °CDB                 -5.0     -5.0
  Heating Min. °CWB                 -20.0     -20.0
    Max. °CWB                 15.5     15.5
ηs,c %         301.3       250.6 272.9 266.0 246.7 260.4 257.7 257.5 251.9 266.8 243.1 259.2 255.3 269.2 259.6 250.2 249.3 246.8 243.1 254.4 265.7 275.2
ηs,c recommended combination 3         291.7       252.0 274.2 269.0 248.9 262.7 256.6 260.5 252.2 269.3 241.7 259.8 255.8 271.4 263.1 249.6 249.0 246.9 241.7 254.5 266.8 276.7
Maximum number of connectable indoor units 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3)
Space cooling B Condition (30°C - 27/19) Pdc kW         26.8       37.1 37.1 41.2 38.3 45.3 49.7 54.2 57.9 61.8 66.3 70.3 71.5 78.3 82.5 86.9 91.0 95.8 99.5 103.5 107.4 111.4
    EERd           5.5       4.5 5.2 4.9 4.4 4.9 4.8 4.7 4.6 4.8 4.6 4.8 4.7 4.9 4.9 4.7 4.6 4.6 4.6 4.7 4.8 5.0
  D Condition (20°C - 27/19) Pdc kW         10.0       11.6 17.8 11.8 13.6 18.2 17.3 17.6 17.7 21.3 18.9 21.0 23.1 30.8 23.6 24.8 26.0 27.4 28.4 29.6 30.7 34.7
    EERd           14.8       15.0 13.6 12.5 14.6 14.6 12.4 13.2 13.3 15.9 11.2 13.7 13.6 14.9 12.6 12.3 12.7 11.2 11.2 13.0 15.0 16.7
  A Condition (35°C - 27/19) EERd           3.3       2.2 2.9 2.7 2.2 2.6 2.5 2.7 2.4 2.4 2.2 2.3 2.3 2.5 2.5 2.3 2.3 2.4 2.2 2.3 2.3 2.4
    Pdc kW         36.4       50.4 50.4 55.9 52.0 61.5 67.4 73.5 78.5 83.9 90.0 95.4 97.0 106.3 111.9 118.0 123.5 130.0 135.0 140.4 145.8 151.2
  C Condition (25°C - 27/19) EERd           9.8       7.8 8.5 8.3 7.7 7.6 8.5 7.9 7.8 8.2 8.1 8.4 8.2 8.4 8.0 8.0 7.9 8.1 8.1 8.3 8.4 8.6
    Pdc kW         17.2       23.9 23.9 26.5 24.6 29.1 31.9 34.8 37.2 39.7 42.6 45.2 45.9 50.4 53.0 55.9 58.5 61.6 64.0 66.5 69.1 71.6
SCOP 4.2 4.3 4 4.7 4.1 4.3 4.3 4.3 4.4 4.3 4.5 4.1 4.5 4.3 4.5 4.4 4.6 4.3 4.4 4.2 4.5 4.5 4.3 4.4 4.3 4.3 4.3 4.4 4.4
Compressor Type                   Hermetically sealed scroll compressor     Hermetically sealed scroll compressor
Weight Unit kg                 317     317
Refrigerant Charge TCO2Eq                 24.6     24.6
  GWP           2,087.5       2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5
  Charge kg                 11.8     11.8
  Type           R-410A       R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
Space cooling recommended combination 3 B Condition (30°C - 27/19) Pdc kW         26.8       37.1 37.1 41.2 38.3 45.3 49.7 54.2 57.8 61.8 66.3 70.3 71.5 78.3 82.5 87.0 91.0 95.8 99.5 103.5 107.4 111.4
    EERd           5.6       4.4 5.2 4.9 4.4 4.9 4.7 4.7 4.6 4.8 4.5 4.7 4.6 4.9 4.9 4.6 4.5 4.6 4.5 4.6 4.8 4.9
  D Condition (20°C - 27/19) Pdc kW         9.9       11.8 18.0 11.8 13.6 18.4 17.5 18.0 17.9 21.7 19.0 21.3 23.0 31.2 23.6 24.8 26.0 27.4 28.4 29.6 31.7 35.4
    EERd           14.5       15.2 13.5 12.7 15.0 14.6 12.4 13.4 13.4 16.0 11.3 13.9 13.8 14.9 12.9 12.4 12.8 11.4 11.3 13.2 15.2 16.8
  A Condition (35°C - 27/19) EERd           3.3       2.2 2.9 2.7 2.2 2.6 2.5 2.7 2.4 2.4 2.2 2.3 2.3 2.5 2.5 2.3 2.3 2.4 2.2 2.3 2.3 2.4
    Pdc kW         36.4       50.4 50.4 55.9 52.0 61.5 67.4 73.5 78.5 83.9 90.0 95.4 97.0 106.3 111.9 118.0 123.5 130.0 135.0 140.4 145.8 151.2
  C Condition (25°C - 27/19) EERd           9.0       8.0 8.6 8.4 7.9 7.8 8.5 8.2 7.9 8.4 8.0 8.5 8.3 8.6 8.3 8.0 8.0 8.2 8.0 8.3 8.6 8.8
    Pdc kW         18.8       23.9 23.9 26.5 24.6 29.1 31.9 34.8 37.2 39.7 42.6 45.2 45.9 50.4 53.0 55.9 58.5 61.6 63.9 66.5 69.1 71.6
SCOP recommended combination 3 4.2 4.2 4.1 4.5 4.2 4.1 4.1 4.1 4.2 4.2 4.4 4.0 4.4 4.1 4.3 4.3 4.4 4.1 4.2 4.1 4.3 4.3 4.1 4.2 4.1 4.1 4.2 4.2 4.2
ηs,h recommended combination 2         157.6       170.0 166.0 173.3 161.4 176.4 164.3 172.5 171.3 176.1 166.1 169.3 164.2 172.4 173.4 165.4 168.7 165.9 165.3 167.5 169.3 170.8
ηs,h recommended combination 3         166.5       164.7 165.0 171.9 157.3 174.1 162.1 168.6 168.4 172.6 162.2 164.4 160.0 170.3 170.1 161.9 165.4 161.5 161.5 163.0 164.3 165.5
Space cooling recommended combination 2 C Condition (25°C - 27/19) Pdc kW         17.2       23.9 23.9 26.5 24.6 29.1 31.9 34.8 37.2 39.7 42.6 45.2 45.9 50.3 53.0 55.9 58.5 61.6 63.9 66.5 69.1 71.6
    EERd           9.5       7.9 8.5 7.8 7.9 7.5 8.5 7.8 7.7 8.0 8.2 8.5 8.4 8.2 8.0 8.2 7.9 8.3 8.2 8.4 8.6 8.8
  A Condition (35°C - 27/19) EERd           3.2       2.2 2.8 2.7 2.2 2.6 2.4 2.7 2.4 2.4 2.2 2.3 2.3 2.5 2.5 2.4 2.3 2.4 2.2 2.3 2.3 2.4
    Pdc kW         36.4       50.4 50.4 55.9 52.0 61.5 67.4 73.5 78.5 83.9 90.0 95.4 97.0 106.3 111.9 118.0 123.5 130.0 135.0 140.4 145.8 151.2
  D Condition (20°C - 27/19) EERd           14.7       15.0 13.3 11.7 14.9 14.4 12.1 13.0 13.0 15.6 11.3 13.8 13.8 14.5 12.9 12.4 12.5 11.4 11.3 13.1 15.0 16.7
    Pdc kW         10.0       11.6 17.7 11.8 13.6 18.1 17.2 17.5 17.6 21.2 18.9 21.1 23.1 30.5 23.6 24.8 26.0 27.4 28.4 29.6 31.2 34.9
  B Condition (30°C - 27/19) EERd           5.5       4.4 5.0 4.7 4.4 4.7 4.7 4.7 4.5 4.7 4.5 4.7 4.7 4.8 4.8 4.7 4.5 4.6 4.5 4.7 4.8 4.9
    Pdc kW         26.8       37.1 37.1 41.2 38.3 45.3 49.7 54.2 57.8 61.8 66.3 70.3 71.5 78.3 82.5 86.9 91.0 95.8 99.5 103.4 107.4 111.4
System Outdoor unit module 2           REYQ8U         REYQ10U REYQ12U   REYQ12U REYQ16U REYQ14U REYQ16U REYQ18U REYQ16U REYQ18U REYQ20U REYQ12U REYQ12U REYQ16U REYQ16U REYQ16U REYQ16U REYQ16U REYQ18U REYQ18U
  Outdoor unit module 3                                           REYQ18U REYQ18U REYQ16U REYQ16U REYQ16U REYQ16U REYQ18U REYQ18U REYQ18U
  Outdoor unit module 1           REMQ5U         REYQ8U REYQ8U   REYQ10U REYQ8U REYQ12U REYQ12U REYQ12U REYQ16U REYQ16U REYQ16U REYQ8U REYQ10U REYQ10U REYQ12U REYQ14U REYQ16U REYQ16U REYQ16U REYQ18U
Recommended combination 3 4 x FXMQ50P7VEB 4 x FXMQ63P7VEB 4 x FXMQ63P7VEB 6 x FXMQ50P7VEB 3 x FXMQ50P7VEB + 3 x FXMQ63P7VEB 1 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 3 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 4 x FXMQ50P7VEB + 4 x FXMQ63P7VEB 10 x FXMQ50P7VEB 2 x FXMQ50P7VEB + 6 x FXMQ63P7VEB 6 x FXMQ50P7VEB + 4 x FXMQ63P7VEB 4 x FXMQ50P7VEB + 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 7 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 6 x FXMQ50P7VEB + 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 9 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 8 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 3 x FXMQ50P7VEB + 9 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 2 x FXMQ50P7VEB + 10 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 6 x FXMQ50P7VEB + 10 x FXMQ63P7VEB 9 x FXMQ50P7VEB + 9 x FXMQ63P7VEB 12 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 6 x FXMQ50P7VEB + 8 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 1 x FXMQ50P7VEB + 13 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 12 x FXMQ63P7VEB + 6 x FXMQ80P7VEB 3 x FXMQ50P7VEB + 13 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 6 x FXMQ50P7VEB + 14 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 9 x FXMQ50P7VEB + 15 x FXMQ63P7VEB
Recommended combination 2 4 x FXSQ50A2VEB 4 x FXSQ63A2VEB 4 x FXSQ63A2VEB 6 x FXSQ50A2VEB 3 x FXSQ50A2VEB + 3 x FXSQ63A2VEB 1 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 3 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 4 x FXSQ50A2VEB + 4 x FXSQ63A2VEB 10 x FXSQ50A2VEB 2 x FXSQ50A2VEB + 6 x FXSQ63A2VEB 6 x FXSQ50A2VEB + 4 x FXSQ63A2VEB 4 x FXSQ50A2VEB + 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 7 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 6 x FXSQ50A2VEB + 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 9 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 8 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 3 x FXSQ50A2VEB + 9 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 2 x FXSQ50A2VEB + 10 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 6 x FXSQ50A2VEB + 10 x FXSQ63A2VEB 9 x FXSQ50A2VEB + 9 x FXSQ63A2VEB 12 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 6 x FXSQ50A2VEB + 8 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 1 x FXSQ50A2VEB + 13 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 12 x FXSQ63A2VEB + 6 x FXSQ80A2VEB 3 x FXSQ50A2VEB + 13 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 6 x FXSQ50A2VEB + 14 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 9 x FXSQ50A2VEB + 15 x FXSQ63A2VEB
SCOP recommended combination 2 4.1 4.3 4.1 4.6 4.0 4.2 4.2 4.2 4.3 4.2 4.4 4.1 4.5 4.2 4.4 4.4 4.5 4.2 4.3 4.2 4.4 4.4 4.2 4.3 4.2 4.2 4.3 4.3 4.3
Power input - 50Hz Heating Nom. 6°CWB kW         9.67 (2)       14.22 (2) 12.98 (2) 15.05 (2) 17.47 (2) 17.23 (2) 17.94 (2) 20.33 (2) 22.19 (2) 23.87 (2) 25.08 (2) 26.76 (2) 30.02 (2) 29.27 (2) 31.45 (2) 32.66 (2) 34.73 (2) 35.77 (2) 37.62 (2) 39.30 (2) 40.98 (2) 42.66 (2)
Indoor index connection Min.           163.0       225.0 225.0 250.0 250.0 275.0 300.0 325.0 350.0 375.0 400.0 425.0 450.0 475.0 500.0 525.0 550.0 575.0 600.0 625.0 650.0 675.0
  Max.           423.0       585.0 585.0 650.0 650.0 715.0 780.0 845.0 910.0 975.0 1,040.0 1,105.0 1,170.0 1,235.0 1,300.0 1,365.0 1,430.0 1,495.0 1,560.0 1,625.0 1,690.0 1,755.0
Cooling capacity Prated,c kW         36.4 (1)       50.4 (1) 50.4 (1) 55.9 (1) 52.0 (1) 61.5 (1) 67.4 (1) 73.5 (1) 78.5 (1) 83.9 (1) 90.0 (1) 95.4 (1) 97.0 (1) 106.3 (1) 111.9 (1) 118.0 (1) 123.5 (1) 130.0 (1) 135.0 (1) 140.4 (1) 145.8 (1) 151.2 (1)
COP at nom. capacity 6°CWB kW/kW         3.76 (2)       3.54 (2) 3.88 (2) 3.71 (2) 3.20 (2) 3.57 (2) 3.76 (2) 3.61 (2) 3.54 (2) 3.51 (2) 3.59 (2) 3.56 (2) 3.36 (2) 3.63 (2) 3.56 (2) 3.61 (2) 3.56 (2) 3.63 (2) 3.59 (2) 3.57 (2) 3.56 (2) 3.54 (2)
Recommended combination 4 x FXFQ50AVEB 4 x FXFQ63AVEB 4 x FXFQ63AVEB 6 x FXFQ50AVEB 3 x FXFQ50AVEB + 3 x FXFQ63AVEB 1 x FXFQ50AVEB + 5 x FXFQ63AVEB 4 x FXFQ63AVEB + 2 x FXFQ80AVEB 4 x FXFQ63AVEB + 2 x FXFQ80AVEB 3 x FXFQ50AVEB + 5 x FXFQ63AVEB 4 x FXFQ50AVEB + 4 x FXFQ63AVEB 10 x FXFQ50AVEB 2 x FXFQ50AVEB + 6 x FXFQ63AVEB 6 x FXFQ50AVEB + 4 x FXFQ63AVEB 4 x FXFQ50AVEB + 4 x FXFQ63AVEB + 2 x FXFQ80AVEB 7 x FXFQ50AVEB + 5 x FXFQ63AVEB 6 x FXFQ50AVEB + 4 x FXFQ63AVEB + 2 x FXFQ80AVEB 9 x FXFQ50AVEB + 5 x FXFQ63AVEB 8 x FXFQ63AVEB + 4 x FXFQ80AVEB 3 x FXFQ50AVEB + 9 x FXFQ63AVEB + 2 x FXFQ80AVEB 2 x FXFQ50AVEB + 10 x FXFQ63AVEB + 2 x FXFQ80AVEB 6 x FXFQ50AVEB + 10 x FXFQ63AVEB 9 x FXFQ50AVEB + 9 x FXFQ63AVEB 12 x FXFQ63AVEB + 4 x FXFQ80AVEB 6 x FXFQ50AVEB + 8 x FXFQ63AVEB + 4 x FXFQ80AVEB 1 x FXFQ50AVEB + 13 x FXFQ63AVEB + 4 x FXFQ80AVEB 12 x FXFQ63AVEB + 6 x FXFQ80AVEB 3 x FXFQ50AVEB + 13 x FXFQ63AVEB + 4 x FXFQ80AVEB 6 x FXFQ50AVEB + 14 x FXFQ63AVEB + 2 x FXFQ80AVEB 9 x FXFQ50AVEB + 15 x FXFQ63AVEB
Space heating (Average climate) TOL COPd (declared COP)           2.3       2.6 2.3 2.3 2.4 2.3 2.2 2.2 2.2 2.5 2.1 2.3 2.3 2.4 2.4 2.1 2.2 2.1 2.1 2.3 2.4 2.6
    Pdh (declared heating cap) kW         21.7       27.9 27.9 31.0 31.0 34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.0 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    Tol (temperature operating limit) °C         -10       -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
  D Condition (12°C) Pdh (declared heating cap) kW         9.1       8.2 7.0 7.7 8.2 7.0 5.7 6.0 6.4 7.7 7.1 8.2 8.3 9.2 9.6 11.0 11.0 11.0 11.0 13.7 13.7 16.3
    COPd (declared COP)           10.6       8.0 10.3 9.4 8.1 10.3 7.0 7.0 7.2 9.4 7.4 8.0 8.0 8.7 8.6 6.9 6.9 6.9 6.9 7.6 7.6 8.0
  B Condition (2°C) COPd (declared COP)           3.6       4.1 4.0 4.1 3.7 4.1 3.9 4.1 4.1 4.1 3.9 4.0 3.8 4.1 4.1 4.0 4.0 4.0 3.9 4.0 4.0 4.1
    Pdh (declared heating cap) kW         11.7       15.0 15.0 16.7 16.7 18.5 19.9 21.0 22.4 24.9 25.0 27.5 29.2 32.3 33.5 33.6 34.9 36.1 37.5 40.0 42.6 45.1
  C Condition (7°C) COPd (declared COP)           6.2       6.2 6.0 6.6 6.1 6.7 6.3 6.7 6.8 6.5 6.5 6.3 6.3 6.4 6.4 6.4 6.7 6.4 6.5 6.4 6.3 6.2
    Pdh (declared heating cap) kW         7.5       9.7 11.3 12.2 10.7 12.3 12.8 13.7 14.6 16.2 16.1 17.7 18.8 21.9 21.9 21.8 22.6 23.2 24.1 25.7 27.3 29.0
  A Condition (-7°C) COPd (declared COP)           2.6       2.9 2.6 2.8 2.7 2.7 2.7 2.8 2.8 2.9 2.7 2.8 2.7 2.8 2.8 2.6 2.7 2.7 2.7 2.8 2.8 2.9
    Pdh (declared heating cap) kW         19.2       24.7 24.7 27.4 27.4 30.4 32.6 34.5 36.8 40.9 41.0 45.2 47.9 53.0 55.1 55.2 57.3 59.3 61.5 65.7 69.9 74.0
  TBivalent Pdh (declared heating cap) kW         21.7       27.9 27.9 31.0 31.0 34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.0 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    Tbiv (bivalent temperature) °C         -10       -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
    COPd (declared COP)           2.3       2.6 2.3 2.3 2.4 2.3 2.2 2.2 2.2 2.5 2.1 2.3 2.3 2.4 2.4 2.1 2.2 2.1 2.1 2.3 2.4 2.6
Piping connections HP/LP gas OD mm         19.1       22.2 22.2 28.6 28.6 28.6 28.6 28.6 28.6 28.6 28.6 28.6 28.6 34.9 34.9 34.9 34.9 34.9 34.9 34.9 34.9 34.9
  Liquid OD mm         12.7       15.9 15.9 15.9 15.9 15.9 15.9 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1
    Type           Braze connection       Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
  Total piping length System Actual m         500 (6)       1,000 (6) 500 (6) 500 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6)
  Gas OD mm         28.6       28.6 28.6 28.6 28.6 28.6 34.9 34.9 34.9 34.9 34.9 34.9 41.3 41.3 41.3 41.3 41.3 41.3 41.3 41.3 41.3 41.3
    Type           Braze connection       Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
SEER 7.2 6.7 7 6.5 7.6 6.5 6.2 7.3 6.3 6.9 6.7 6.2 6.6 6.5 6.5 6.4 6.7 6.2 6.6 6.5 6.8 6.6 6.3 6.3 6.2 6.2 6.4 6.7 7.0
Space heating (Average climate) recommended combination 2 B Condition (2°C) Pdh (declared heating cap) kW         11.7       15.0 15.0 16.7 16.7 18.5 19.9 21.0 22.4 24.9 25.0 27.5 29.2 32.3 33.5 33.6 34.9 36.1 37.5 40.0 42.5 45.1
    COPd (declared COP)           3.6       4.0 3.9 4.1 3.7 4.1 3.9 4.1 4.0 4.1 3.9 3.9 3.8 4.0 4.0 3.9 3.9 3.9 3.9 3.9 4.0 4.0
  C Condition (7°C) Pdh (declared heating cap) kW         7.5       9.7 11.2 12.3 10.7 12.1 12.8 13.6 14.5 16.2 16.1 17.7 18.8 21.8 21.8 21.7 22.6 23.2 24.1 25.7 27.3 29.0
    COPd (declared COP)           6.1       6.0 5.9 6.5 6.1 6.6 6.2 6.5 6.7 6.4 6.4 6.2 6.2 6.2 6.3 6.3 6.5 6.3 6.4 6.2 6.1 6.0
  A Condition (-7°C) COPd (declared COP)           2.5       2.9 2.6 2.8 2.7 2.7 2.6 2.8 2.7 2.9 2.6 2.8 2.7 2.8 2.8 2.6 2.7 2.7 2.6 2.7 2.8 2.9
    Pdh (declared heating cap) kW         19.2       24.7 24.7 27.4 27.4 30.4 32.6 34.5 36.8 40.9 41.0 45.2 47.9 53.0 55.1 55.2 57.3 59.3 61.6 65.7 69.9 74.0
  TOL Pdh (declared heating cap) kW         21.7       27.9 27.9 31.0 31.0 34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.0 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    COPd (declared COP)           2.2       2.5 2.2 2.3 2.4 2.2 2.1 2.2 2.2 2.4 2.1 2.3 2.2 2.4 2.4 2.1 2.1 2.1 2.1 2.2 2.4 2.5
    Tol (temperature operating limit) °C         -10       -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
  D Condition (12°C) Pdh (declared heating cap) kW         9.0       8.0 6.9 7.6 8.0 6.9 5.7 6.0 6.4 7.6 7.1 8.0 8.3 9.2 9.6 10.6 10.6 10.6 10.7 13.3 13.3 16.0
    COPd (declared COP)           10.4       7.9 10.3 9.1 7.9 10.3 6.8 6.9 7.1 9.1 7.2 7.9 7.8 8.4 8.3 6.7 6.7 6.7 6.7 7.3 7.3 7.9
  TBivalent Pdh (declared heating cap) kW         21.7       27.9 27.9 31.0 31.0 34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.0 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    COPd (declared COP)           2.2       2.5 2.2 2.3 2.4 2.2 2.1 2.2 2.2 2.4 2.1 2.3 2.2 2.4 2.4 2.1 2.1 2.1 2.1 2.2 2.4 2.5
    Tbiv (bivalent temperature) °C         -10       -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
Space heating (Average climate) recommended combination 3 B Condition (2°C) Pdh (declared heating cap) kW         11.7       15.0 15.0 16.7 16.7 18.5 19.9 21.0 22.4 24.9 25.0 27.5 29.2 32.3 33.5 33.6 34.9 36.1 37.5 40.0 42.5 45.1
    COPd (declared COP)           3.7       3.9 3.9 4.0 3.6 4.0 3.8 4.0 3.9 4.0 3.8 3.8 3.7 4.0 4.0 3.8 3.9 3.8 3.8 3.8 3.9 3.9
  C Condition (7°C) COPd (declared COP)           6.1       5.8 5.9 6.4 5.9 6.4 6.0 6.4 6.5 6.2 6.2 6.0 6.0 6.1 6.1 6.2 6.4 6.1 6.2 6.1 5.9 5.8
    Pdh (declared heating cap) kW         7.5       9.7 11.1 11.9 10.7 11.9 12.8 13.5 14.4 16.0 16.1 17.7 18.8 20.8 21.6 21.7 22.4 23.2 24.1 25.7 27.3 29.0
  A Condition (-7°C) Pdh (declared heating cap) kW         19.2       24.7 24.7 27.4 27.4 30.4 32.6 34.5 36.8 40.9 41.0 45.2 47.9 53.1 55.1 55.2 57.3 59.3 61.6 65.7 69.9 74.0
    COPd (declared COP)           2.5       2.8 2.6 2.8 2.7 2.7 2.6 2.7 2.7 2.8 2.6 2.7 2.6 2.8 2.7 2.6 2.6 2.6 2.6 2.7 2.7 2.8
  TOL Pdh (declared heating cap) kW         21.7       27.9 27.9 31.0 31.0 34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.0 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    Tol (temperature operating limit) °C         -10       -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
    COPd (declared COP)           2.2       2.5 2.2 2.3 2.3 2.2 2.1 2.2 2.2 2.4 2.1 2.3 2.2 2.4 2.3 2.1 2.1 2.1 2.1 2.2 2.3 2.5
  D Condition (12°C) COPd (declared COP)           16.8       7.4 10.1 9.1 7.6 10.1 6.7 6.6 6.9 9.1 7.0 7.4 7.4 8.4 8.3 6.5 6.5 6.5 6.6 7.0 7.0 7.4
    Pdh (declared heating cap) kW         5.1       7.6 6.9 7.4 7.7 6.9 5.7 6.0 6.4 7.4 7.1 7.9 8.3 9.2 9.6 10.2 10.2 10.2 10.7 12.7 12.7 15.2
  TBivalent Pdh (declared heating cap) kW         21.7       27.9 27.9 31.0 31.0 34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.0 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    COPd (declared COP)           2.2       2.5 2.2 2.3 2.3 2.2 2.1 2.2 2.2 2.4 2.1 2.3 2.2 2.4 2.3 2.1 2.1 2.1 2.1 2.2 2.3 2.5
    Tbiv (bivalent temperature) °C         -10       -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
Sound power level Cooling Nom. dBA         81.0 (4)       83.8 (4) 81.6 (4) 84.5 (4) 87.9 (4) 84.8 (4) 86.3 (4) 85.3 (4) 87.6 (4) 86.6 (4) 88.6 (4) 87.8 (4) 89.9 (4) 87.2 (4) 87.3 (4) 89.1 (4) 89.8 (4) 89.3 (4) 90.4 (4) 89.8 (4) 89.3 (4) 88.6 (4)
Dimensions Unit Width mm                 1,240     1,240
    Depth mm                 765     765
    Height mm                 1,685     1,685
ηs,h %         160.6       172.5 167.9 175.7 162.7 178.5 167.6 175.5 174.8 179.4 169.1 172.0 166.3 176.0 176.1 167.8 171.9 168.8 168.5 170.3 171.7 173.3
Continuous heating     Yes   Yes     Yes   Yes Yes   Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Fan External static pressure Max. Pa                 78     78
Heating capacity Prated,h kW         36.4 (2)       50.4 (2) 50.4 (2) 55.9 (2) 56.0 (2) 61.5 (2) 67.4 (2) 73.5 (2) 78.5 (2) 83.9 (2) 90.0 (2) 95.4 (2) 101.0 (2) 106.4 (2) 111.9 (2) 118.0 (2) 123.5 (2) 130.0 (2) 135.0 (2) 140.4 (2) 145.8 (2) 151.2 (2)
  Nom. 6°CWB kW         36.4 (2)       50.4 (2) 50.4 (2) 55.9 (2) 56.0 (2) 61.5 (2) 67.4 (2) 73.5 (2) 78.5 (2) 83.9 (2) 90.0 (2) 95.4 (2) 101.0 (2) 106.3 (2) 111.9 (2) 118.0 (2) 123.5 (2) 130.0 (2) 135.0 (2) 140.4 (2) 145.8 (2) 151.2 (2)
Power supply Phase           3N~       3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~
  Name           Y1       Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1
  Frequency Hz         50       50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Voltage V         380-415       380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%)
  (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates.
  (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
  (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual
  (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
  (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
  (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
  (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan   (11) - FLA means the nominal running current of the fan (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan   (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
          (12) - FLA means the nominal running current of the fan       (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan
          (13) - Maximum allowable voltage range variation between phases is 2%.       (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%.
          (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.       (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
          (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation )       (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation )
          (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality       (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality
          (17) - Sound values are measured in a semi-anechoic room.       (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room.
          (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA       (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
          (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase       (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
          (20) - Ssc: Short-circuit power       (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power
          (21) - For detailed contents of standard accessories, see installation/operation manual       (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual
          (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination       (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination
Cooling capacity Prated,c kW 22.4 (1) 28 28 33.5 (1)   40 45 44.8 (1)
Heating capacity Prated,h kW 22.4 (2) 28 28 33.5 (2)   40 45 44.8 (2)
  Nom. 6°CWB kW 22.4 (2) 28 28 33.5 (2)   40 45 44.8 (2)
COP at nom. capacity 6°CWB KW/KW 4.15 (2) 3.69 (2) 3.71 (2) 3.47 (2)   3.74 (2) 3.59 (2) 3.57 (2)
Space cooling A Condition (35°C - 27/19) EERd   3.2 2.7 3.5 2.5   2.8 2.2 3
    Pdc kW 22.4 28.0 28 33.5   40.0 45.0 44.8
  B Condition (30°C - 27/19) EERd   5.3 5.1 5.8 4.7   4.8 4.6 5
    Pdc kW 16.5 20.6 20.6 24.7   29.5 33.2 33
  C Condition (25°C - 27/19) EERd   9.6 7.7 8.4 7.5   8.3 8.1 9.1
    Pdc kW 10.6 13.3 16.8 15.9   18.9 21.3 21.2
  D Condition (20°C - 27/19) EERd   13.1 14.1 13.5 15.1   11.3 11.2 15
    Pdc kW 9.4 8.4 9.6 9.8   8.4 9.5 10
Space cooling recommended combination 2 A Condition (35°C - 27/19) EERd   2.9 2.8 3.6 2.5   2.8 2.2 3
    Pdc kW 22.4 28 28 33.5   40 45 44.8
  B Condition (30°C - 27/19) EERd   4.9 5.1 5.9 4.5   4.8 4.5 5.1
    Pdc kW 16.5 20.6 20.6 24.7   29.5 33.2 33
  C Condition (25°C - 27/19) EERd   9.1 8 8.5 7.1   8.5 8.2 9.2
    Pdc kW 10.6 13.3 17 15.9   18.9 21.3 21.2
  D Condition (20°C - 27/19) EERd   12.6 14.3 13.9 14.4   11.4 11.3 15.1
    Pdc kW 9.2 8.5 9.8 9.6   8.4 9.5 10.1
Space cooling recommended combination 3 A Condition (35°C - 27/19) EERd   3.1 2.7 3.5 2.5   2.8 2.2 3.0
    Pdc kW 22.4 28.0 28.0 33.5   40.0 45.0 44.8
  B Condition (30°C - 27/19) EERd   5.4 5.1 5.7 4.7   4.8 4.5 4.9
    Pdc kW 16.5 20.6 20.6 24.7   29.5 33.2 33.0
  C Condition (25°C - 27/19) EERd   9.6 7.9 8.3 7.8   8.5 8.0 8.9
    Pdc kW 10.6 13.3 16.8 15.9   18.9 21.3 21.2
  D Condition (20°C - 27/19) EERd   13.0 14.1 13.0 15.1   11.6 11.3 14.9
    Pdc kW 9.4 8.5 9.4 9.9   8.4 9.5 10.1
Space heating (Average climate) TBivalent COPd (declared COP)   2.3 2.2 1.8 2.3   2.2 2.1 2.4
    Pdh (declared heating cap) kW 13.7 16.0 16 18.4   20.6 23.2 23.2
    Tbiv (bivalent temperature) °C -10 -10 -10 -10   -10 -10 -10
  Space heating (Average climate)-=-E condition (-10°C) Space heating (Average climate)-=-E condition (-10°C)-=-COPd (declared COP)   2.3 2.2 1.8 2.3   2.2 2.1 2.4
    Space heating (Average climate)-=-E condition (-10°C)-=-Pdh (declared heating cap)-=-kW kW 13.7 16.0 16 18.4   20.6 23.2 23.2
  TOL Tol (temperature operating limit) °C -10 -10 -10 -10   -10 -10 -10
  A Condition (-7°C) COPd (declared COP)   2.7 2.6 1.9 2.9   2.7 2.7 2.7
    Pdh (declared heating cap) kW 12.1 14.2 14.2 16.3   18.2 20.5 20.5
  B Condition (2°C) COPd (declared COP)   4.0 4.0 4 4.2   4.0 3.9 3.8
    Pdh (declared heating cap) kW 7.4 8.6 8.6 9.9   11.1 12.5 12.5
  C Condition (7°C) COPd (declared COP)   6.0 6.1 6.1 7.2   6.3 6.5 6.3
    Pdh (declared heating cap) kW 5.7 5.7 5.7 6.6   7.1 8.0 8
  D Condition (12°C) COPd (declared COP)   9.3 10.3 9.6 9.4   6.8 6.9 11.1
    Pdh (declared heating cap) kW 8.8 7.0 8.9 7.7   5.4 5.5 9.2
Space heating (Average climate) recommended combination 2 TBivalent COPd (declared COP)   2.2 2.2 2.3 2.3   2.1 2.1 2.3
    Pdh (declared heating cap) kW 13.7 16 16 18.4   20.6 23.2 23.2
    Tbiv (bivalent temperature) °C -10 -10 -10 -10   -10 -10 -10
  TOL COPd (declared COP)   2.2 2.2 2.3 2.3   2.1 2.1 2.3
    Pdh (declared heating cap) kW 13.7 16 16 18.4   20.6 23.2 23.2
    Tol (temperature operating limit) °C -10 -10 -10 -10   -10 -10 -10
  A Condition (-7°C) COPd (declared COP)   2.6 2.6 2.5 2.8   2.7 2.6 2.7
    Pdh (declared heating cap) kW 12.1 14.2 14.2 16.2   18.2 20.5 20.5
  B Condition (2°C) COPd (declared COP)   3.9 4 3.9 4.1   4 3.9 3.7
    Pdh (declared heating cap) kW 7.4 8.6 8.6 9.9   11.1 12.5 12.5
  C Condition (7°C) COPd (declared COP)   5.8 6.1 5.8 7   6.2 6.4 6.1
    Pdh (declared heating cap) kW 5.6 5.6 5.5 6.5   7.1 8 8
  D Condition (12°C) COPd (declared COP)   9 10.3 9.1 9.1   6.6 6.7 10.8
    Pdh (declared heating cap) kW 8.7 6.9 8.7 7.6   5.2 5.3 9
Space heating (Average climate) recommended combination 3 TBivalent COPd (declared COP)   2.3 2.1 2.2 2.3   2.1 2.1 2.3
    Pdh (declared heating cap) kW 13.7 16.0 16.0 18.4   20.6 23.2 23.2
    Tbiv (bivalent temperature) °C -10 -10 -10 -10   -10 -10 -10
  TOL COPd (declared COP)   2.3 2.1 2.2 2.3   2.1 2.1 2.3
    Pdh (declared heating cap) kW 13.7 16.0 16.0 18.4   20.6 23.2 23.2
    Tol (temperature operating limit) °C -10 -10 -10 -10   -10 -10 -10
  A Condition (-7°C) COPd (declared COP)   2.6 2.5 2.4 2.8   2.7 2.6 2.6
    Pdh (declared heating cap) kW 12.1 14.2 14.2 16.3   18.2 20.5 20.5
  B Condition (2°C) COPd (declared COP)   3.9 3.9 3.9 4.1   3.8 3.8 3.7
    Pdh (declared heating cap) kW 7.4 8.6 8.6 9.9   11.1 12.5 12.5
  C Condition (7°C) COPd (declared COP)   5.8 6.0 5.8 6.9   5.9 6.2 5.9
    Pdh (declared heating cap) kW 5.5 5.6 5.5 6.4   7.1 8.0 8.0
  D Condition (12°C) COPd (declared COP)   9.2 10.1 9.2 9.1   6.2 6.5 10.5
    Pdh (declared heating cap) kW 8.7 6.9 8.7 7.4   4.9 5.1 8.9
Indoor index connection Min.   100 125 125 150   175 200 200
  Max.   260 325 325 390   455 520 520
Dimensions Unit Height mm 1,685 1,685   1,685   1,685 1,685
    Width mm 930 930   930   1,240 1,240
    Depth mm 765 765   765   765 765
Weight Unit kg 230 230   230   314 314
Fan External static pressure Max. Pa 78 78   78   78 78
Compressor Type   Hermetically sealed scroll compressor Hermetically sealed scroll compressor   Hermetically sealed scroll compressor   Hermetically sealed scroll compressor Hermetically sealed scroll compressor
Operation range Cooling Min. °CDB -5 -5   -5   -5 -5
    Max. °CDB 43 43   43   43 43
  Heating Min. °CWB -20 -20   -20   -20 -20
    Max. °CWB 15.5 15.5   15.5   15.5 15.5
Sound power level Cooling Nom. dBA 78.0 (4) 79.1 (4) 81 83.4 (4)   80.9 (4) 85.6 (4) 81
Sound pressure level Cooling Nom. dBA 57 57 60 61   60 63 60
Refrigerant Type   R-410A R-410A R-410A R-410A   R-410A R-410A R-410A
  GWP   2,087.5 2,087.5 2,087.5 2,087.5   2,087.5 2,087.5 2,087.5
  Charge tCO2Eq 20.2 20.5   20.7   24.6 24.6
  Charge kg 9.7 9.8   9.9   11.8 11.8
Piping connections Liquid Type   Braze connection Braze connection Braze connection Braze connection   Braze connection Braze connection Braze connection
    OD mm 9.5 9.5 9.5 12.7   12.7 12.7 12.7
  Gas Type   Braze connection Braze connection Braze connection Braze connection   Braze connection Braze connection Braze connection
    OD mm 19.1 22.2 22.2 28.6   28.6 28.6 28.6
  HP/LP gas OD mm 15.9 19.1 19.1 19.1   22.2 22.2 22.2
  Total piping length System Actual m 1,000 (6) 1,000 (6) 500 (6) 1,000 (6)   1,000 (6) 1,000 (6) 500 (6)
Power supply Name   Y1 Y1 Y1 Y1   Y1 Y1 Y1
  Phase   3N~ 3N~ 3N~ 3N~   3N~ 3N~ 3N~
  Frequency Hz 50 50 50 50   50 50 50
  Voltage V 380-415 380-415 380-415 380-415   380-415 380-415 380-415
System Outdoor unit module 1       REMQ5U         REYQ8U
  Outdoor unit module 2       REMQ5U         REYQ8U