| REYQ8U7Y1B | REYQ10U7Y1B | REYQ10U7Y1B. | REYQ12U7Y1B | REYQ13U7Y1B | REYQ14U7Y1B | REYQ16U7Y1B | REYQ16U7Y1B. | REYQ18U7Y1B. | REYQ18U7Y1B | REYQ20U7Y1B. | REYQ20U7Y1B | REYQ22U7Y1B | REYQ24U7Y1B | REYQ26U7Y1B | REYQ28U7Y1B | REYQ30U7Y1B | REYQ32U7Y1B | REYQ34U7Y1B | REYQ36U7Y1B | REYQ38U7Y1B | REYQ40U7Y1B | REYQ42U7Y1B | REYQ44U7Y1B | REYQ46U7Y1B | REYQ48U7Y1B | REYQ50U7Y1B | REYQ52U7Y1B | REYQ54U7Y1B | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Sound pressure level | Cooling | Nom. | dBA | 60.0 (5) | 60.0 (5) | 62.5 (5) | 62.5 (5) | 64.0 (5) | 63.5 (5) | 65.1 (5) | 64.5 (5) | 66.0 (5) | 65.5 (5) | 67.1 (5) | 65.2 (5) | 65.2 (5) | 66.5 (5) | 67.2 (5) | 67.0 (5) | 67.8 (5) | 67.5 (5) | 67.1 (5) | 66.8 (5) | ||||||||||
| Standard Accessories | Installation and operation manual | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |||||
| Connection pipes | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | ||||||
| SEER recommended combination 2 | 6.8 | 6.8 | 7.1 | 6.2 | 7.5 | 6.6 | 6.2 | 7.3 | 6.8 | 6.4 | 6.4 | 6.3 | 6.5 | 6.4 | 6.4 | 6.3 | 6.6 | 6.2 | 6.6 | 6.5 | 6.6 | 6.6 | 6.4 | 6.3 | 6.3 | 6.2 | 6.5 | 6.7 | 7.0 | ||||
| SEER recommended combination 3 | 7.2 | 6.7 | 6.9 | 6.6 | 7.4 | 6.6 | 6.1 | 7.1 | 6.9 | 6.8 | 6.6 | 6.5 | 6.6 | 6.4 | 6.8 | 6.1 | 6.6 | 6.5 | 6.9 | 6.7 | 6.3 | 6.3 | 6.2 | 6.1 | 6.4 | 6.7 | 7.0 | ||||||
| Capacity range | HP | 8 | 10 | 10 | 12 | 13 | 14 | 16 | 16 | 18 | 18 | 20 | 20 | 22 | 24 | 26 | 28 | 30 | 32 | 34 | 36 | 38 | 40 | 42 | 44 | 46 | 48 | 50 | 52 | 54 | |||
| ηs,c recommended combination 2 | 296.3 | 269.4 | 252.4 | 256.8 | 253.7 | 254.1 | 247.9 | 262.9 | 244.5 | 260.6 | 257.6 | 263.0 | 259.5 | 252.5 | 247.1 | 248.8 | 244.5 | 255.9 | 267.0 | 276.7 | |||||||||||||
| ηs,c | % | 301.3 | 272.9 | 266.0 | 260.4 | 257.7 | 257.5 | 251.9 | 266.8 | 243.1 | 259.2 | 255.3 | 269.2 | 259.6 | 250.2 | 249.3 | 246.8 | 243.1 | 254.4 | 265.7 | 275.2 | ||||||||||||
| ηs,c recommended combination 3 | 291.7 | 274.2 | 269.0 | 262.7 | 256.6 | 260.5 | 252.2 | 269.3 | 241.7 | 259.8 | 255.8 | 271.4 | 263.1 | 249.6 | 249.0 | 246.9 | 241.7 | 254.5 | 266.8 | 276.7 | |||||||||||||
| Maximum number of connectable indoor units | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | 64 (3) | ||||||
| Space cooling | B Condition (30°C - 27/19) | Pdc | kW | 26.8 | 37.1 | 41.2 | 45.3 | 49.7 | 54.2 | 57.9 | 61.8 | 66.3 | 70.3 | 71.5 | 78.3 | 82.5 | 86.9 | 91.0 | 95.8 | 99.5 | 103.5 | 107.4 | 111.4 | ||||||||||
| EERd | 5.5 | 5.2 | 4.9 | 4.9 | 4.8 | 4.7 | 4.6 | 4.8 | 4.6 | 4.8 | 4.7 | 4.9 | 4.9 | 4.7 | 4.6 | 4.6 | 4.6 | 4.7 | 4.8 | 5.0 | |||||||||||||
| D Condition (20°C - 27/19) | Pdc | kW | 10.0 | 17.8 | 11.8 | 18.2 | 17.3 | 17.6 | 17.7 | 21.3 | 18.9 | 21.0 | 23.1 | 30.8 | 23.6 | 24.8 | 26.0 | 27.4 | 28.4 | 29.6 | 30.7 | 34.7 | |||||||||||
| EERd | 14.8 | 13.6 | 12.5 | 14.6 | 12.4 | 13.2 | 13.3 | 15.9 | 11.2 | 13.7 | 13.6 | 14.9 | 12.6 | 12.3 | 12.7 | 11.2 | 11.2 | 13.0 | 15.0 | 16.7 | |||||||||||||
| A Condition (35°C - 27/19) | EERd | 3.3 | 2.9 | 2.7 | 2.6 | 2.5 | 2.7 | 2.4 | 2.4 | 2.2 | 2.3 | 2.3 | 2.5 | 2.5 | 2.3 | 2.3 | 2.4 | 2.2 | 2.3 | 2.3 | 2.4 | ||||||||||||
| Pdc | kW | 36.4 | 50.4 | 55.9 | 61.5 | 67.4 | 73.5 | 78.5 | 83.9 | 90.0 | 95.4 | 97.0 | 106.3 | 111.9 | 118.0 | 123.5 | 130.0 | 135.0 | 140.4 | 145.8 | 151.2 | ||||||||||||
| C Condition (25°C - 27/19) | EERd | 9.8 | 8.5 | 8.3 | 7.6 | 8.5 | 7.9 | 7.8 | 8.2 | 8.1 | 8.4 | 8.2 | 8.4 | 8.0 | 8.0 | 7.9 | 8.1 | 8.1 | 8.3 | 8.4 | 8.6 | ||||||||||||
| Pdc | kW | 17.2 | 23.9 | 26.5 | 29.1 | 31.9 | 34.8 | 37.2 | 39.7 | 42.6 | 45.2 | 45.9 | 50.4 | 53.0 | 55.9 | 58.5 | 61.6 | 64.0 | 66.5 | 69.1 | 71.6 | ||||||||||||
| SCOP | 4.2 | 4.3 | 4 | 4.7 | 4.1 | 4.3 | 4.3 | 4.3 | 4.3 | 4.5 | 4.5 | 4.3 | 4.5 | 4.4 | 4.6 | 4.3 | 4.4 | 4.2 | 4.5 | 4.5 | 4.3 | 4.4 | 4.3 | 4.3 | 4.3 | 4.4 | 4.4 | ||||||
| Refrigerant | GWP | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | ||||||||||||
| Type | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | |||||||||||||
| Space cooling recommended combination 3 | B Condition (30°C - 27/19) | Pdc | kW | 26.8 | 37.1 | 41.2 | 45.3 | 49.7 | 54.2 | 57.8 | 61.8 | 66.3 | 70.3 | 71.5 | 78.3 | 82.5 | 87.0 | 91.0 | 95.8 | 99.5 | 103.5 | 107.4 | 111.4 | ||||||||||
| EERd | 5.6 | 5.2 | 4.9 | 4.9 | 4.7 | 4.7 | 4.6 | 4.8 | 4.5 | 4.7 | 4.6 | 4.9 | 4.9 | 4.6 | 4.5 | 4.6 | 4.5 | 4.6 | 4.8 | 4.9 | |||||||||||||
| D Condition (20°C - 27/19) | Pdc | kW | 9.9 | 18.0 | 11.8 | 18.4 | 17.5 | 18.0 | 17.9 | 21.7 | 19.0 | 21.3 | 23.0 | 31.2 | 23.6 | 24.8 | 26.0 | 27.4 | 28.4 | 29.6 | 31.7 | 35.4 | |||||||||||
| EERd | 14.5 | 13.5 | 12.7 | 14.6 | 12.4 | 13.4 | 13.4 | 16.0 | 11.3 | 13.9 | 13.8 | 14.9 | 12.9 | 12.4 | 12.8 | 11.4 | 11.3 | 13.2 | 15.2 | 16.8 | |||||||||||||
| A Condition (35°C - 27/19) | EERd | 3.3 | 2.9 | 2.7 | 2.6 | 2.5 | 2.7 | 2.4 | 2.4 | 2.2 | 2.3 | 2.3 | 2.5 | 2.5 | 2.3 | 2.3 | 2.4 | 2.2 | 2.3 | 2.3 | 2.4 | ||||||||||||
| Pdc | kW | 36.4 | 50.4 | 55.9 | 61.5 | 67.4 | 73.5 | 78.5 | 83.9 | 90.0 | 95.4 | 97.0 | 106.3 | 111.9 | 118.0 | 123.5 | 130.0 | 135.0 | 140.4 | 145.8 | 151.2 | ||||||||||||
| C Condition (25°C - 27/19) | EERd | 9.0 | 8.6 | 8.4 | 7.8 | 8.5 | 8.2 | 7.9 | 8.4 | 8.0 | 8.5 | 8.3 | 8.6 | 8.3 | 8.0 | 8.0 | 8.2 | 8.0 | 8.3 | 8.6 | 8.8 | ||||||||||||
| Pdc | kW | 18.8 | 23.9 | 26.5 | 29.1 | 31.9 | 34.8 | 37.2 | 39.7 | 42.6 | 45.2 | 45.9 | 50.4 | 53.0 | 55.9 | 58.5 | 61.6 | 63.9 | 66.5 | 69.1 | 71.6 | ||||||||||||
| SCOP recommended combination 3 | 4.2 | 4.2 | 4.1 | 4.5 | 4.2 | 4.1 | 4.1 | 4.1 | 4.2 | 4.4 | 4.4 | 4.1 | 4.3 | 4.3 | 4.4 | 4.1 | 4.2 | 4.1 | 4.3 | 4.3 | 4.1 | 4.2 | 4.1 | 4.1 | 4.2 | 4.2 | 4.2 | ||||||
| ηs,h recommended combination 2 | 157.6 | 166.0 | 173.3 | 176.4 | 164.3 | 172.5 | 171.3 | 176.1 | 166.1 | 169.3 | 164.2 | 172.4 | 173.4 | 165.4 | 168.7 | 165.9 | 165.3 | 167.5 | 169.3 | 170.8 | |||||||||||||
| ηs,h recommended combination 3 | 166.5 | 165.0 | 171.9 | 174.1 | 162.1 | 168.6 | 168.4 | 172.6 | 162.2 | 164.4 | 160.0 | 170.3 | 170.1 | 161.9 | 165.4 | 161.5 | 161.5 | 163.0 | 164.3 | 165.5 | |||||||||||||
| Space cooling recommended combination 2 | C Condition (25°C - 27/19) | Pdc | kW | 17.2 | 23.9 | 26.5 | 29.1 | 31.9 | 34.8 | 37.2 | 39.7 | 42.6 | 45.2 | 45.9 | 50.3 | 53.0 | 55.9 | 58.5 | 61.6 | 63.9 | 66.5 | 69.1 | 71.6 | ||||||||||
| EERd | 9.5 | 8.5 | 7.8 | 7.5 | 8.5 | 7.8 | 7.7 | 8.0 | 8.2 | 8.5 | 8.4 | 8.2 | 8.0 | 8.2 | 7.9 | 8.3 | 8.2 | 8.4 | 8.6 | 8.8 | |||||||||||||
| A Condition (35°C - 27/19) | EERd | 3.2 | 2.8 | 2.7 | 2.6 | 2.4 | 2.7 | 2.4 | 2.4 | 2.2 | 2.3 | 2.3 | 2.5 | 2.5 | 2.4 | 2.3 | 2.4 | 2.2 | 2.3 | 2.3 | 2.4 | ||||||||||||
| Pdc | kW | 36.4 | 50.4 | 55.9 | 61.5 | 67.4 | 73.5 | 78.5 | 83.9 | 90.0 | 95.4 | 97.0 | 106.3 | 111.9 | 118.0 | 123.5 | 130.0 | 135.0 | 140.4 | 145.8 | 151.2 | ||||||||||||
| D Condition (20°C - 27/19) | EERd | 14.7 | 13.3 | 11.7 | 14.4 | 12.1 | 13.0 | 13.0 | 15.6 | 11.3 | 13.8 | 13.8 | 14.5 | 12.9 | 12.4 | 12.5 | 11.4 | 11.3 | 13.1 | 15.0 | 16.7 | ||||||||||||
| Pdc | kW | 10.0 | 17.7 | 11.8 | 18.1 | 17.2 | 17.5 | 17.6 | 21.2 | 18.9 | 21.1 | 23.1 | 30.5 | 23.6 | 24.8 | 26.0 | 27.4 | 28.4 | 29.6 | 31.2 | 34.9 | ||||||||||||
| B Condition (30°C - 27/19) | EERd | 5.5 | 5.0 | 4.7 | 4.7 | 4.7 | 4.7 | 4.5 | 4.7 | 4.5 | 4.7 | 4.7 | 4.8 | 4.8 | 4.7 | 4.5 | 4.6 | 4.5 | 4.7 | 4.8 | 4.9 | ||||||||||||
| Pdc | kW | 26.8 | 37.1 | 41.2 | 45.3 | 49.7 | 54.2 | 57.8 | 61.8 | 66.3 | 70.3 | 71.5 | 78.3 | 82.5 | 86.9 | 91.0 | 95.8 | 99.5 | 103.4 | 107.4 | 111.4 | ||||||||||||
| System | Outdoor unit module 2 | REYQ8U | REYQ10U | REYQ12U | REYQ12U | REYQ16U | REYQ14U | REYQ16U | REYQ18U | REYQ16U | REYQ18U | REYQ20U | REYQ12U | REYQ12U | REYQ16U | REYQ16U | REYQ16U | REYQ16U | REYQ16U | REYQ18U | REYQ18U | ||||||||||||
| Outdoor unit module 3 | REYQ18U | REYQ18U | REYQ16U | REYQ16U | REYQ16U | REYQ16U | REYQ18U | REYQ18U | REYQ18U | ||||||||||||||||||||||||
| Outdoor unit module 1 | REMQ5U | REYQ8U | REYQ8U | REYQ10U | REYQ8U | REYQ12U | REYQ12U | REYQ12U | REYQ16U | REYQ16U | REYQ16U | REYQ8U | REYQ10U | REYQ10U | REYQ12U | REYQ14U | REYQ16U | REYQ16U | REYQ16U | REYQ18U | |||||||||||||
| Recommended combination 3 | 4 x FXMQ50P7VEB | 4 x FXMQ63P7VEB | 4 x FXMQ63P7VEB | 6 x FXMQ50P7VEB | 3 x FXMQ50P7VEB + 3 x FXMQ63P7VEB | 1 x FXMQ50P7VEB + 5 x FXMQ63P7VEB | 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB | 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB | 4 x FXMQ50P7VEB + 4 x FXMQ63P7VEB | 10 x FXMQ50P7VEB | 6 x FXMQ50P7VEB + 4 x FXMQ63P7VEB | 4 x FXMQ50P7VEB + 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB | 7 x FXMQ50P7VEB + 5 x FXMQ63P7VEB | 6 x FXMQ50P7VEB + 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB | 9 x FXMQ50P7VEB + 5 x FXMQ63P7VEB | 8 x FXMQ63P7VEB + 4 x FXMQ80P7VEB | 3 x FXMQ50P7VEB + 9 x FXMQ63P7VEB + 2 x FXMQ80P7VEB | 2 x FXMQ50P7VEB + 10 x FXMQ63P7VEB + 2 x FXMQ80P7VEB | 6 x FXMQ50P7VEB + 10 x FXMQ63P7VEB | 9 x FXMQ50P7VEB + 9 x FXMQ63P7VEB | 12 x FXMQ63P7VEB + 4 x FXMQ80P7VEB | 6 x FXMQ50P7VEB + 8 x FXMQ63P7VEB + 4 x FXMQ80P7VEB | 1 x FXMQ50P7VEB + 13 x FXMQ63P7VEB + 4 x FXMQ80P7VEB | 12 x FXMQ63P7VEB + 6 x FXMQ80P7VEB | 3 x FXMQ50P7VEB + 13 x FXMQ63P7VEB + 4 x FXMQ80P7VEB | 6 x FXMQ50P7VEB + 14 x FXMQ63P7VEB + 2 x FXMQ80P7VEB | 9 x FXMQ50P7VEB + 15 x FXMQ63P7VEB | ||||||
| Recommended combination 2 | 4 x FXSQ50A2VEB | 4 x FXSQ63A2VEB | 4 x FXSQ63A2VEB | 6 x FXSQ50A2VEB | 3 x FXSQ50A2VEB + 3 x FXSQ63A2VEB | 1 x FXSQ50A2VEB + 5 x FXSQ63A2VEB | 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB | 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB | 4 x FXSQ50A2VEB + 4 x FXSQ63A2VEB | 3 x FXSQ50A2VEB + 5 x FXSQ63A2VEB | 10 x FXSQ50A2VEB | 2 x FXSQ50A2VEB + 6 x FXSQ63A2VEB | 6 x FXSQ50A2VEB + 4 x FXSQ63A2VEB | 4 x FXSQ50A2VEB + 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB | 7 x FXSQ50A2VEB + 5 x FXSQ63A2VEB | 6 x FXSQ50A2VEB + 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB | 9 x FXSQ50A2VEB + 5 x FXSQ63A2VEB | 8 x FXSQ63A2VEB + 4 x FXSQ80A2VEB | 3 x FXSQ50A2VEB + 9 x FXSQ63A2VEB + 2 x FXSQ80A2VEB | 2 x FXSQ50A2VEB + 10 x FXSQ63A2VEB + 2 x FXSQ80A2VEB | 6 x FXSQ50A2VEB + 10 x FXSQ63A2VEB | 9 x FXSQ50A2VEB + 9 x FXSQ63A2VEB | 12 x FXSQ63A2VEB + 4 x FXSQ80A2VEB | 6 x FXSQ50A2VEB + 8 x FXSQ63A2VEB + 4 x FXSQ80A2VEB | 1 x FXSQ50A2VEB + 13 x FXSQ63A2VEB + 4 x FXSQ80A2VEB | 12 x FXSQ63A2VEB + 6 x FXSQ80A2VEB | 3 x FXSQ50A2VEB + 13 x FXSQ63A2VEB + 4 x FXSQ80A2VEB | 6 x FXSQ50A2VEB + 14 x FXSQ63A2VEB + 2 x FXSQ80A2VEB | 9 x FXSQ50A2VEB + 15 x FXSQ63A2VEB | ||||
| SCOP recommended combination 2 | 4.1 | 4.3 | 4.1 | 4.6 | 4.0 | 4.2 | 4.2 | 4.2 | 4.2 | 4.3 | 4.4 | 4.1 | 4.5 | 4.2 | 4.4 | 4.4 | 4.5 | 4.2 | 4.3 | 4.2 | 4.4 | 4.4 | 4.2 | 4.3 | 4.2 | 4.2 | 4.3 | 4.3 | 4.3 | ||||
| Power input - 50Hz | Heating | Nom. | 6°CWB | kW | 9.67 (2) | 12.98 (2) | 15.05 (2) | 17.23 (2) | 17.94 (2) | 20.33 (2) | 22.19 (2) | 23.87 (2) | 25.08 (2) | 26.76 (2) | 30.02 (2) | 29.27 (2) | 31.45 (2) | 32.66 (2) | 34.73 (2) | 35.77 (2) | 37.62 (2) | 39.30 (2) | 40.98 (2) | 42.66 (2) | |||||||||
| Indoor index connection | Min. | 163.0 | 225.0 | 250.0 | 275.0 | 300.0 | 325.0 | 350.0 | 375.0 | 400.0 | 425.0 | 450.0 | 475.0 | 500.0 | 525.0 | 550.0 | 575.0 | 600.0 | 625.0 | 650.0 | 675.0 | ||||||||||||
| Max. | 423.0 | 585.0 | 650.0 | 715.0 | 780.0 | 845.0 | 910.0 | 975.0 | 1,040.0 | 1,105.0 | 1,170.0 | 1,235.0 | 1,300.0 | 1,365.0 | 1,430.0 | 1,495.0 | 1,560.0 | 1,625.0 | 1,690.0 | 1,755.0 | |||||||||||||
| Cooling capacity | Prated,c | kW | 36.4 (1) | 50.4 (1) | 55.9 (1) | 61.5 (1) | 67.4 (1) | 73.5 (1) | 78.5 (1) | 83.9 (1) | 90.0 (1) | 95.4 (1) | 97.0 (1) | 106.3 (1) | 111.9 (1) | 118.0 (1) | 123.5 (1) | 130.0 (1) | 135.0 (1) | 140.4 (1) | 145.8 (1) | 151.2 (1) | |||||||||||
| COP at nom. capacity | 6°CWB | kW/kW | 3.76 (2) | 3.88 (2) | 3.71 (2) | 3.57 (2) | 3.76 (2) | 3.61 (2) | 3.54 (2) | 3.51 (2) | 3.59 (2) | 3.56 (2) | 3.36 (2) | 3.63 (2) | 3.56 (2) | 3.61 (2) | 3.56 (2) | 3.63 (2) | 3.59 (2) | 3.57 (2) | 3.56 (2) | 3.54 (2) | |||||||||||
| Recommended combination | 4 x FXFQ50AVEB | 4 x FXFQ63AVEB | 4 x FXFQ63AVEB | 6 x FXFQ50AVEB | 3 x FXFQ50AVEB + 3 x FXFQ63AVEB | 1 x FXFQ50AVEB + 5 x FXFQ63AVEB | 4 x FXFQ63AVEB + 2 x FXFQ80AVEB | 4 x FXFQ63AVEB + 2 x FXFQ80AVEB | 4 x FXFQ50AVEB + 4 x FXFQ63AVEB | 3 x FXFQ50AVEB + 5 x FXFQ63AVEB | 10 x FXFQ50AVEB | 2 x FXFQ50AVEB + 6 x FXFQ63AVEB | 6 x FXFQ50AVEB + 4 x FXFQ63AVEB | 4 x FXFQ50AVEB + 4 x FXFQ63AVEB + 2 x FXFQ80AVEB | 7 x FXFQ50AVEB + 5 x FXFQ63AVEB | 6 x FXFQ50AVEB + 4 x FXFQ63AVEB + 2 x FXFQ80AVEB | 9 x FXFQ50AVEB + 5 x FXFQ63AVEB | 8 x FXFQ63AVEB + 4 x FXFQ80AVEB | 3 x FXFQ50AVEB + 9 x FXFQ63AVEB + 2 x FXFQ80AVEB | 2 x FXFQ50AVEB + 10 x FXFQ63AVEB + 2 x FXFQ80AVEB | 6 x FXFQ50AVEB + 10 x FXFQ63AVEB | 9 x FXFQ50AVEB + 9 x FXFQ63AVEB | 12 x FXFQ63AVEB + 4 x FXFQ80AVEB | 6 x FXFQ50AVEB + 8 x FXFQ63AVEB + 4 x FXFQ80AVEB | 1 x FXFQ50AVEB + 13 x FXFQ63AVEB + 4 x FXFQ80AVEB | 12 x FXFQ63AVEB + 6 x FXFQ80AVEB | 3 x FXFQ50AVEB + 13 x FXFQ63AVEB + 4 x FXFQ80AVEB | 6 x FXFQ50AVEB + 14 x FXFQ63AVEB + 2 x FXFQ80AVEB | 9 x FXFQ50AVEB + 15 x FXFQ63AVEB | ||||
| Space heating (Average climate) | TOL | COPd (declared COP) | 2.3 | 2.3 | 2.3 | 2.3 | 2.2 | 2.2 | 2.2 | 2.5 | 2.1 | 2.3 | 2.3 | 2.4 | 2.4 | 2.1 | 2.2 | 2.1 | 2.1 | 2.3 | 2.4 | 2.6 | |||||||||||
| Pdh (declared heating cap) | kW | 21.7 | 27.9 | 31.0 | 34.4 | 36.9 | 39.0 | 41.6 | 46.3 | 46.4 | 51.1 | 54.2 | 60.0 | 62.3 | 62.4 | 64.8 | 67.0 | 69.6 | 74.3 | 79.0 | 83.7 | ||||||||||||
| Tol (temperature operating limit) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | ||||||||||||
| D Condition (12°C) | Pdh (declared heating cap) | kW | 9.1 | 7.0 | 7.7 | 7.0 | 5.7 | 6.0 | 6.4 | 7.7 | 7.1 | 8.2 | 8.3 | 9.2 | 9.6 | 11.0 | 11.0 | 11.0 | 11.0 | 13.7 | 13.7 | 16.3 | |||||||||||
| COPd (declared COP) | 10.6 | 10.3 | 9.4 | 10.3 | 7.0 | 7.0 | 7.2 | 9.4 | 7.4 | 8.0 | 8.0 | 8.7 | 8.6 | 6.9 | 6.9 | 6.9 | 6.9 | 7.6 | 7.6 | 8.0 | |||||||||||||
| B Condition (2°C) | COPd (declared COP) | 3.6 | 4.0 | 4.1 | 4.1 | 3.9 | 4.1 | 4.1 | 4.1 | 3.9 | 4.0 | 3.8 | 4.1 | 4.1 | 4.0 | 4.0 | 4.0 | 3.9 | 4.0 | 4.0 | 4.1 | ||||||||||||
| Pdh (declared heating cap) | kW | 11.7 | 15.0 | 16.7 | 18.5 | 19.9 | 21.0 | 22.4 | 24.9 | 25.0 | 27.5 | 29.2 | 32.3 | 33.5 | 33.6 | 34.9 | 36.1 | 37.5 | 40.0 | 42.6 | 45.1 | ||||||||||||
| C Condition (7°C) | COPd (declared COP) | 6.2 | 6.0 | 6.6 | 6.7 | 6.3 | 6.7 | 6.8 | 6.5 | 6.5 | 6.3 | 6.3 | 6.4 | 6.4 | 6.4 | 6.7 | 6.4 | 6.5 | 6.4 | 6.3 | 6.2 | ||||||||||||
| Pdh (declared heating cap) | kW | 7.5 | 11.3 | 12.2 | 12.3 | 12.8 | 13.7 | 14.6 | 16.2 | 16.1 | 17.7 | 18.8 | 21.9 | 21.9 | 21.8 | 22.6 | 23.2 | 24.1 | 25.7 | 27.3 | 29.0 | ||||||||||||
| A Condition (-7°C) | COPd (declared COP) | 2.6 | 2.6 | 2.8 | 2.7 | 2.7 | 2.8 | 2.8 | 2.9 | 2.7 | 2.8 | 2.7 | 2.8 | 2.8 | 2.6 | 2.7 | 2.7 | 2.7 | 2.8 | 2.8 | 2.9 | ||||||||||||
| Pdh (declared heating cap) | kW | 19.2 | 24.7 | 27.4 | 30.4 | 32.6 | 34.5 | 36.8 | 40.9 | 41.0 | 45.2 | 47.9 | 53.0 | 55.1 | 55.2 | 57.3 | 59.3 | 61.5 | 65.7 | 69.9 | 74.0 | ||||||||||||
| TBivalent | Pdh (declared heating cap) | kW | 21.7 | 27.9 | 31.0 | 34.4 | 36.9 | 39.0 | 41.6 | 46.3 | 46.4 | 51.1 | 54.2 | 60.0 | 62.3 | 62.4 | 64.8 | 67.0 | 69.6 | 74.3 | 79.0 | 83.7 | |||||||||||
| Tbiv (bivalent temperature) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | ||||||||||||
| COPd (declared COP) | 2.3 | 2.3 | 2.3 | 2.3 | 2.2 | 2.2 | 2.2 | 2.5 | 2.1 | 2.3 | 2.3 | 2.4 | 2.4 | 2.1 | 2.2 | 2.1 | 2.1 | 2.3 | 2.4 | 2.6 | |||||||||||||
| Piping connections | HP/LP gas | OD | mm | 19.1 | 22.2 | 28.6 | 28.6 | 28.6 | 28.6 | 28.6 | 28.6 | 28.6 | 28.6 | 28.6 | 34.9 | 34.9 | 34.9 | 34.9 | 34.9 | 34.9 | 34.9 | 34.9 | 34.9 | ||||||||||
| Liquid | OD | mm | 12.7 | 15.9 | 15.9 | 15.9 | 15.9 | 19.1 | 19.1 | 19.1 | 19.1 | 19.1 | 19.1 | 19.1 | 19.1 | 19.1 | 19.1 | 19.1 | 19.1 | 19.1 | 19.1 | 19.1 | |||||||||||
| Type | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | |||||||||||||
| Total piping length | System | Actual | m | 500 (6) | 500 (6) | 500 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | ||||||||||
| Gas | OD | mm | 28.6 | 28.6 | 28.6 | 28.6 | 34.9 | 34.9 | 34.9 | 34.9 | 34.9 | 34.9 | 41.3 | 41.3 | 41.3 | 41.3 | 41.3 | 41.3 | 41.3 | 41.3 | 41.3 | 41.3 | |||||||||||
| Type | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | |||||||||||||
| SEER | 7.2 | 6.7 | 7 | 6.5 | 7.6 | 6.5 | 6.2 | 7.3 | 6.9 | 6.7 | 6.6 | 6.5 | 6.5 | 6.4 | 6.7 | 6.2 | 6.6 | 6.5 | 6.8 | 6.6 | 6.3 | 6.3 | 6.2 | 6.2 | 6.4 | 6.7 | 7.0 | ||||||
| Space heating (Average climate) recommended combination 2 | B Condition (2°C) | Pdh (declared heating cap) | kW | 11.7 | 15.0 | 16.7 | 18.5 | 19.9 | 21.0 | 22.4 | 24.9 | 25.0 | 27.5 | 29.2 | 32.3 | 33.5 | 33.6 | 34.9 | 36.1 | 37.5 | 40.0 | 42.5 | 45.1 | ||||||||||
| COPd (declared COP) | 3.6 | 3.9 | 4.1 | 4.1 | 3.9 | 4.1 | 4.0 | 4.1 | 3.9 | 3.9 | 3.8 | 4.0 | 4.0 | 3.9 | 3.9 | 3.9 | 3.9 | 3.9 | 4.0 | 4.0 | |||||||||||||
| C Condition (7°C) | Pdh (declared heating cap) | kW | 7.5 | 11.2 | 12.3 | 12.1 | 12.8 | 13.6 | 14.5 | 16.2 | 16.1 | 17.7 | 18.8 | 21.8 | 21.8 | 21.7 | 22.6 | 23.2 | 24.1 | 25.7 | 27.3 | 29.0 | |||||||||||
| COPd (declared COP) | 6.1 | 5.9 | 6.5 | 6.6 | 6.2 | 6.5 | 6.7 | 6.4 | 6.4 | 6.2 | 6.2 | 6.2 | 6.3 | 6.3 | 6.5 | 6.3 | 6.4 | 6.2 | 6.1 | 6.0 | |||||||||||||
| A Condition (-7°C) | COPd (declared COP) | 2.5 | 2.6 | 2.8 | 2.7 | 2.6 | 2.8 | 2.7 | 2.9 | 2.6 | 2.8 | 2.7 | 2.8 | 2.8 | 2.6 | 2.7 | 2.7 | 2.6 | 2.7 | 2.8 | 2.9 | ||||||||||||
| Pdh (declared heating cap) | kW | 19.2 | 24.7 | 27.4 | 30.4 | 32.6 | 34.5 | 36.8 | 40.9 | 41.0 | 45.2 | 47.9 | 53.0 | 55.1 | 55.2 | 57.3 | 59.3 | 61.6 | 65.7 | 69.9 | 74.0 | ||||||||||||
| TOL | Pdh (declared heating cap) | kW | 21.7 | 27.9 | 31.0 | 34.4 | 36.9 | 39.0 | 41.6 | 46.3 | 46.4 | 51.1 | 54.2 | 60.0 | 62.3 | 62.4 | 64.8 | 67.0 | 69.6 | 74.3 | 79.0 | 83.7 | |||||||||||
| COPd (declared COP) | 2.2 | 2.2 | 2.3 | 2.2 | 2.1 | 2.2 | 2.2 | 2.4 | 2.1 | 2.3 | 2.2 | 2.4 | 2.4 | 2.1 | 2.1 | 2.1 | 2.1 | 2.2 | 2.4 | 2.5 | |||||||||||||
| Tol (temperature operating limit) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | ||||||||||||
| D Condition (12°C) | Pdh (declared heating cap) | kW | 9.0 | 6.9 | 7.6 | 6.9 | 5.7 | 6.0 | 6.4 | 7.6 | 7.1 | 8.0 | 8.3 | 9.2 | 9.6 | 10.6 | 10.6 | 10.6 | 10.7 | 13.3 | 13.3 | 16.0 | |||||||||||
| COPd (declared COP) | 10.4 | 10.3 | 9.1 | 10.3 | 6.8 | 6.9 | 7.1 | 9.1 | 7.2 | 7.9 | 7.8 | 8.4 | 8.3 | 6.7 | 6.7 | 6.7 | 6.7 | 7.3 | 7.3 | 7.9 | |||||||||||||
| TBivalent | Pdh (declared heating cap) | kW | 21.7 | 27.9 | 31.0 | 34.4 | 36.9 | 39.0 | 41.6 | 46.3 | 46.4 | 51.1 | 54.2 | 60.0 | 62.3 | 62.4 | 64.8 | 67.0 | 69.6 | 74.3 | 79.0 | 83.7 | |||||||||||
| COPd (declared COP) | 2.2 | 2.2 | 2.3 | 2.2 | 2.1 | 2.2 | 2.2 | 2.4 | 2.1 | 2.3 | 2.2 | 2.4 | 2.4 | 2.1 | 2.1 | 2.1 | 2.1 | 2.2 | 2.4 | 2.5 | |||||||||||||
| Tbiv (bivalent temperature) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | ||||||||||||
| Space heating (Average climate) recommended combination 3 | B Condition (2°C) | Pdh (declared heating cap) | kW | 11.7 | 15.0 | 16.7 | 18.5 | 19.9 | 21.0 | 22.4 | 24.9 | 25.0 | 27.5 | 29.2 | 32.3 | 33.5 | 33.6 | 34.9 | 36.1 | 37.5 | 40.0 | 42.5 | 45.1 | ||||||||||
| COPd (declared COP) | 3.7 | 3.9 | 4.0 | 4.0 | 3.8 | 4.0 | 3.9 | 4.0 | 3.8 | 3.8 | 3.7 | 4.0 | 4.0 | 3.8 | 3.9 | 3.8 | 3.8 | 3.8 | 3.9 | 3.9 | |||||||||||||
| C Condition (7°C) | COPd (declared COP) | 6.1 | 5.9 | 6.4 | 6.4 | 6.0 | 6.4 | 6.5 | 6.2 | 6.2 | 6.0 | 6.0 | 6.1 | 6.1 | 6.2 | 6.4 | 6.1 | 6.2 | 6.1 | 5.9 | 5.8 | ||||||||||||
| Pdh (declared heating cap) | kW | 7.5 | 11.1 | 11.9 | 11.9 | 12.8 | 13.5 | 14.4 | 16.0 | 16.1 | 17.7 | 18.8 | 20.8 | 21.6 | 21.7 | 22.4 | 23.2 | 24.1 | 25.7 | 27.3 | 29.0 | ||||||||||||
| A Condition (-7°C) | Pdh (declared heating cap) | kW | 19.2 | 24.7 | 27.4 | 30.4 | 32.6 | 34.5 | 36.8 | 40.9 | 41.0 | 45.2 | 47.9 | 53.1 | 55.1 | 55.2 | 57.3 | 59.3 | 61.6 | 65.7 | 69.9 | 74.0 | |||||||||||
| COPd (declared COP) | 2.5 | 2.6 | 2.8 | 2.7 | 2.6 | 2.7 | 2.7 | 2.8 | 2.6 | 2.7 | 2.6 | 2.8 | 2.7 | 2.6 | 2.6 | 2.6 | 2.6 | 2.7 | 2.7 | 2.8 | |||||||||||||
| TOL | Pdh (declared heating cap) | kW | 21.7 | 27.9 | 31.0 | 34.4 | 36.9 | 39.0 | 41.6 | 46.3 | 46.4 | 51.1 | 54.2 | 60.0 | 62.3 | 62.4 | 64.8 | 67.0 | 69.6 | 74.3 | 79.0 | 83.7 | |||||||||||
| Tol (temperature operating limit) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | ||||||||||||
| COPd (declared COP) | 2.2 | 2.2 | 2.3 | 2.2 | 2.1 | 2.2 | 2.2 | 2.4 | 2.1 | 2.3 | 2.2 | 2.4 | 2.3 | 2.1 | 2.1 | 2.1 | 2.1 | 2.2 | 2.3 | 2.5 | |||||||||||||
| D Condition (12°C) | COPd (declared COP) | 16.8 | 10.1 | 9.1 | 10.1 | 6.7 | 6.6 | 6.9 | 9.1 | 7.0 | 7.4 | 7.4 | 8.4 | 8.3 | 6.5 | 6.5 | 6.5 | 6.6 | 7.0 | 7.0 | 7.4 | ||||||||||||
| Pdh (declared heating cap) | kW | 5.1 | 6.9 | 7.4 | 6.9 | 5.7 | 6.0 | 6.4 | 7.4 | 7.1 | 7.9 | 8.3 | 9.2 | 9.6 | 10.2 | 10.2 | 10.2 | 10.7 | 12.7 | 12.7 | 15.2 | ||||||||||||
| TBivalent | Pdh (declared heating cap) | kW | 21.7 | 27.9 | 31.0 | 34.4 | 36.9 | 39.0 | 41.6 | 46.3 | 46.4 | 51.1 | 54.2 | 60.0 | 62.3 | 62.4 | 64.8 | 67.0 | 69.6 | 74.3 | 79.0 | 83.7 | |||||||||||
| COPd (declared COP) | 2.2 | 2.2 | 2.3 | 2.2 | 2.1 | 2.2 | 2.2 | 2.4 | 2.1 | 2.3 | 2.2 | 2.4 | 2.3 | 2.1 | 2.1 | 2.1 | 2.1 | 2.2 | 2.3 | 2.5 | |||||||||||||
| Tbiv (bivalent temperature) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | ||||||||||||
| Sound power level | Cooling | Nom. | dBA | 81.0 (4) | 81.6 (4) | 84.5 (4) | 84.8 (4) | 86.3 (4) | 85.3 (4) | 87.6 (4) | 86.6 (4) | 88.6 (4) | 87.8 (4) | 89.9 (4) | 87.2 (4) | 87.3 (4) | 89.1 (4) | 89.8 (4) | 89.3 (4) | 90.4 (4) | 89.8 (4) | 89.3 (4) | 88.6 (4) | ||||||||||
| ηs,h | % | 160.6 | 167.9 | 175.7 | 178.5 | 167.6 | 175.5 | 174.8 | 179.4 | 169.1 | 172.0 | 166.3 | 176.0 | 176.1 | 167.8 | 171.9 | 168.8 | 168.5 | 170.3 | 171.7 | 173.3 | ||||||||||||
| Continuous heating | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||||||
| Heating capacity | Prated,h | kW | 36.4 (2) | 50.4 (2) | 55.9 (2) | 61.5 (2) | 67.4 (2) | 73.5 (2) | 78.5 (2) | 83.9 (2) | 90.0 (2) | 95.4 (2) | 101.0 (2) | 106.4 (2) | 111.9 (2) | 118.0 (2) | 123.5 (2) | 130.0 (2) | 135.0 (2) | 140.4 (2) | 145.8 (2) | 151.2 (2) | |||||||||||
| Nom. | 6°CWB | kW | 36.4 (2) | 50.4 (2) | 55.9 (2) | 61.5 (2) | 67.4 (2) | 73.5 (2) | 78.5 (2) | 83.9 (2) | 90.0 (2) | 95.4 (2) | 101.0 (2) | 106.3 (2) | 111.9 (2) | 118.0 (2) | 123.5 (2) | 130.0 (2) | 135.0 (2) | 140.4 (2) | 145.8 (2) | 151.2 (2) | |||||||||||
| Power supply | Phase | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | ||||||||||||
| Name | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | |||||||||||||
| Frequency | Hz | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | ||||||||||||
| Voltage | V | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | ||||||||||||
| Notes | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | ||||||
| (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | |||||||
| (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | (3) - Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) | |||||||
| (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | |||||||
| (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | |||||||
| (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | |||||||
| (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | |||||||
| (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | |||||||
| (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | |||||||
| (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | |||||||
| (11) - FLA means the nominal running current of the fan | (11) - FLA means the nominal running current of the fan | (11) - FLA means the nominal running current of the fan | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - FLA means the nominal running current of the fan | (11) - FLA means the nominal running current of the fan | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | |||||||||
| (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | ||||||||||||||
| (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | (13) - Maximum allowable voltage range variation between phases is 2%. | ||||||||||||||
| (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | ||||||||||||||
| (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Recovery operation, taking into account advanced energy saving operation functionality (variable refrigerant temperature control operation ) | ||||||||||||||
| (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Recovery operation, not taking into account advanced energy saving operation functionality | ||||||||||||||
| (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | (17) - Sound values are measured in a semi-anechoic room. | ||||||||||||||
| (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | ||||||||||||||
| (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | ||||||||||||||
| (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | ||||||||||||||
| (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | (21) - For detailed contents of standard accessories, see installation/operation manual | ||||||||||||||
| (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | (22) - Multi combination (10~54HP) data is corresponding with the standard multi combination | ||||||||||||||
| Cooling capacity | Prated,c | kW | 22.4 (1) | 28 | 28 | 33.5 (1) | 40 | 45 | 44.8 (1) | 50.4 | 52 | ||||||||||||||||||||||
| Heating capacity | Prated,h | kW | 22.4 (2) | 28 | 28 | 33.5 (2) | 40 | 45 | 44.8 (2) | 50.4 | 56 | ||||||||||||||||||||||
| Nom. | 6°CWB | kW | 22.4 (2) | 28 | 28 | 33.5 (2) | 40 | 45 | 44.8 (2) | 50.4 | 56 | ||||||||||||||||||||||
| COP at nom. capacity | 6°CWB | KW/KW | 4.15 (2) | 3.69 (2) | 3.71 (2) | 3.47 (2) | 3.74 (2) | 3.59 (2) | 3.57 (2) | 3.54 | 3.2 | ||||||||||||||||||||||
| Space cooling | A Condition (35°C - 27/19) | EERd | 3.2 | 2.7 | 3.5 | 2.5 | 2.8 | 2.2 | 3 | ||||||||||||||||||||||||
| Pdc | kW | 22.4 | 28.0 | 28 | 33.5 | 40.0 | 45.0 | 44.8 | |||||||||||||||||||||||||
| B Condition (30°C - 27/19) | EERd | 5.3 | 5.1 | 5.8 | 4.7 | 4.8 | 4.6 | 5 | |||||||||||||||||||||||||
| Pdc | kW | 16.5 | 20.6 | 20.6 | 24.7 | 29.5 | 33.2 | 33 | |||||||||||||||||||||||||
| C Condition (25°C - 27/19) | EERd | 9.6 | 7.7 | 8.4 | 7.5 | 8.3 | 8.1 | 9.1 | |||||||||||||||||||||||||
| Pdc | kW | 10.6 | 13.3 | 16.8 | 15.9 | 18.9 | 21.3 | 21.2 | |||||||||||||||||||||||||
| D Condition (20°C - 27/19) | EERd | 13.1 | 14.1 | 13.5 | 15.1 | 11.3 | 11.2 | 15 | |||||||||||||||||||||||||
| Pdc | kW | 9.4 | 8.4 | 9.6 | 9.8 | 8.4 | 9.5 | 10 | |||||||||||||||||||||||||
| Space cooling recommended combination 2 | A Condition (35°C - 27/19) | EERd | 2.9 | 2.8 | 3.6 | 2.5 | 2.8 | 2.2 | 3 | 2.2 | 2.2 | ||||||||||||||||||||||
| Pdc | kW | 22.4 | 28 | 28 | 33.5 | 40 | 45 | 44.8 | 50.4 | 52 | |||||||||||||||||||||||
| B Condition (30°C - 27/19) | EERd | 4.9 | 5.1 | 5.9 | 4.5 | 4.8 | 4.5 | 5.1 | 4.4 | 4.4 | |||||||||||||||||||||||
| Pdc | kW | 16.5 | 20.6 | 20.6 | 24.7 | 29.5 | 33.2 | 33 | 37.1 | 38.3 | |||||||||||||||||||||||
| C Condition (25°C - 27/19) | EERd | 9.1 | 8 | 8.5 | 7.1 | 8.5 | 8.2 | 9.2 | 7.9 | 7.9 | |||||||||||||||||||||||
| Pdc | kW | 10.6 | 13.3 | 17 | 15.9 | 18.9 | 21.3 | 21.2 | 23.9 | 24.6 | |||||||||||||||||||||||
| D Condition (20°C - 27/19) | EERd | 12.6 | 14.3 | 13.9 | 14.4 | 11.4 | 11.3 | 15.1 | 15 | 14.9 | |||||||||||||||||||||||
| Pdc | kW | 9.2 | 8.5 | 9.8 | 9.6 | 8.4 | 9.5 | 10.1 | 11.6 | 13.6 | |||||||||||||||||||||||
| Space cooling recommended combination 3 | A Condition (35°C - 27/19) | EERd | 3.1 | 2.7 | 3.5 | 2.5 | 2.8 | 2.2 | 3.0 | ||||||||||||||||||||||||
| Pdc | kW | 22.4 | 28.0 | 28.0 | 33.5 | 40.0 | 45.0 | 44.8 | |||||||||||||||||||||||||
| B Condition (30°C - 27/19) | EERd | 5.4 | 5.1 | 5.7 | 4.7 | 4.8 | 4.5 | 4.9 | |||||||||||||||||||||||||
| Pdc | kW | 16.5 | 20.6 | 20.6 | 24.7 | 29.5 | 33.2 | 33.0 | |||||||||||||||||||||||||
| C Condition (25°C - 27/19) | EERd | 9.6 | 7.9 | 8.3 | 7.8 | 8.5 | 8.0 | 8.9 | |||||||||||||||||||||||||
| Pdc | kW | 10.6 | 13.3 | 16.8 | 15.9 | 18.9 | 21.3 | 21.2 | |||||||||||||||||||||||||
| D Condition (20°C - 27/19) | EERd | 13.0 | 14.1 | 13.0 | 15.1 | 11.6 | 11.3 | 14.9 | |||||||||||||||||||||||||
| Pdc | kW | 9.4 | 8.5 | 9.4 | 9.9 | 8.4 | 9.5 | 10.1 | |||||||||||||||||||||||||
| Space heating (Average climate) | TBivalent | COPd (declared COP) | 2.3 | 2.2 | 1.8 | 2.3 | 2.2 | 2.1 | 2.4 | ||||||||||||||||||||||||
| Pdh (declared heating cap) | kW | 13.7 | 16.0 | 16 | 18.4 | 20.6 | 23.2 | 23.2 | |||||||||||||||||||||||||
| Tbiv (bivalent temperature) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | |||||||||||||||||||||||||
| Space heating (Average climate)-=-E condition (-10°C) | Space heating (Average climate)-=-E condition (-10°C)-=-COPd (declared COP) | 2.3 | 2.2 | 1.8 | 2.3 | 2.2 | 2.1 | 2.4 | |||||||||||||||||||||||||
| Space heating (Average climate)-=-E condition (-10°C)-=-Pdh (declared heating cap)-=-kW | kW | 13.7 | 16.0 | 16 | 18.4 | 20.6 | 23.2 | 23.2 | |||||||||||||||||||||||||
| TOL | Tol (temperature operating limit) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | ||||||||||||||||||||||||
| A Condition (-7°C) | COPd (declared COP) | 2.7 | 2.6 | 1.9 | 2.9 | 2.7 | 2.7 | 2.7 | |||||||||||||||||||||||||
| Pdh (declared heating cap) | kW | 12.1 | 14.2 | 14.2 | 16.3 | 18.2 | 20.5 | 20.5 | |||||||||||||||||||||||||
| B Condition (2°C) | COPd (declared COP) | 4.0 | 4.0 | 4 | 4.2 | 4.0 | 3.9 | 3.8 | |||||||||||||||||||||||||
| Pdh (declared heating cap) | kW | 7.4 | 8.6 | 8.6 | 9.9 | 11.1 | 12.5 | 12.5 | |||||||||||||||||||||||||
| C Condition (7°C) | COPd (declared COP) | 6.0 | 6.1 | 6.1 | 7.2 | 6.3 | 6.5 | 6.3 | |||||||||||||||||||||||||
| Pdh (declared heating cap) | kW | 5.7 | 5.7 | 5.7 | 6.6 | 7.1 | 8.0 | 8 | |||||||||||||||||||||||||
| D Condition (12°C) | COPd (declared COP) | 9.3 | 10.3 | 9.6 | 9.4 | 6.8 | 6.9 | 11.1 | |||||||||||||||||||||||||
| Pdh (declared heating cap) | kW | 8.8 | 7.0 | 8.9 | 7.7 | 5.4 | 5.5 | 9.2 | |||||||||||||||||||||||||
| Space heating (Average climate) recommended combination 2 | TBivalent | COPd (declared COP) | 2.2 | 2.2 | 2.3 | 2.3 | 2.1 | 2.1 | 2.3 | 2.5 | 2.4 | ||||||||||||||||||||||
| Pdh (declared heating cap) | kW | 13.7 | 16 | 16 | 18.4 | 20.6 | 23.2 | 23.2 | 27.9 | 31 | |||||||||||||||||||||||
| Tbiv (bivalent temperature) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | |||||||||||||||||||||||
| TOL | COPd (declared COP) | 2.2 | 2.2 | 2.3 | 2.3 | 2.1 | 2.1 | 2.3 | 2.5 | 2.4 | |||||||||||||||||||||||
| Pdh (declared heating cap) | kW | 13.7 | 16 | 16 | 18.4 | 20.6 | 23.2 | 23.2 | 27.9 | 31 | |||||||||||||||||||||||
| Tol (temperature operating limit) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | |||||||||||||||||||||||
| A Condition (-7°C) | COPd (declared COP) | 2.6 | 2.6 | 2.5 | 2.8 | 2.7 | 2.6 | 2.7 | 2.9 | 2.7 | |||||||||||||||||||||||
| Pdh (declared heating cap) | kW | 12.1 | 14.2 | 14.2 | 16.2 | 18.2 | 20.5 | 20.5 | 24.7 | 27.4 | |||||||||||||||||||||||
| B Condition (2°C) | COPd (declared COP) | 3.9 | 4 | 3.9 | 4.1 | 4 | 3.9 | 3.7 | 4 | 3.7 | |||||||||||||||||||||||
| Pdh (declared heating cap) | kW | 7.4 | 8.6 | 8.6 | 9.9 | 11.1 | 12.5 | 12.5 | 15 | 16.7 | |||||||||||||||||||||||
| C Condition (7°C) | COPd (declared COP) | 5.8 | 6.1 | 5.8 | 7 | 6.2 | 6.4 | 6.1 | 6 | 6.1 | |||||||||||||||||||||||
| Pdh (declared heating cap) | kW | 5.6 | 5.6 | 5.5 | 6.5 | 7.1 | 8 | 8 | 9.7 | 10.7 | |||||||||||||||||||||||
| D Condition (12°C) | COPd (declared COP) | 9 | 10.3 | 9.1 | 9.1 | 6.6 | 6.7 | 10.8 | 7.9 | 7.9 | |||||||||||||||||||||||
| Pdh (declared heating cap) | kW | 8.7 | 6.9 | 8.7 | 7.6 | 5.2 | 5.3 | 9 | 8 | 8 | |||||||||||||||||||||||
| Space heating (Average climate) recommended combination 3 | TBivalent | COPd (declared COP) | 2.3 | 2.1 | 2.2 | 2.3 | 2.1 | 2.1 | 2.3 | ||||||||||||||||||||||||
| Pdh (declared heating cap) | kW | 13.7 | 16.0 | 16.0 | 18.4 | 20.6 | 23.2 | 23.2 | |||||||||||||||||||||||||
| Tbiv (bivalent temperature) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | |||||||||||||||||||||||||
| TOL | COPd (declared COP) | 2.3 | 2.1 | 2.2 | 2.3 | 2.1 | 2.1 | 2.3 | |||||||||||||||||||||||||
| Pdh (declared heating cap) | kW | 13.7 | 16.0 | 16.0 | 18.4 | 20.6 | 23.2 | 23.2 | |||||||||||||||||||||||||
| Tol (temperature operating limit) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | |||||||||||||||||||||||||
| A Condition (-7°C) | COPd (declared COP) | 2.6 | 2.5 | 2.4 | 2.8 | 2.7 | 2.6 | 2.6 | |||||||||||||||||||||||||
| Pdh (declared heating cap) | kW | 12.1 | 14.2 | 14.2 | 16.3 | 18.2 | 20.5 | 20.5 | |||||||||||||||||||||||||
| B Condition (2°C) | COPd (declared COP) | 3.9 | 3.9 | 3.9 | 4.1 | 3.8 | 3.8 | 3.7 | |||||||||||||||||||||||||
| Pdh (declared heating cap) | kW | 7.4 | 8.6 | 8.6 | 9.9 | 11.1 | 12.5 | 12.5 | |||||||||||||||||||||||||
| C Condition (7°C) | COPd (declared COP) | 5.8 | 6.0 | 5.8 | 6.9 | 5.9 | 6.2 | 5.9 | |||||||||||||||||||||||||
| Pdh (declared heating cap) | kW | 5.5 | 5.6 | 5.5 | 6.4 | 7.1 | 8.0 | 8.0 | |||||||||||||||||||||||||
| D Condition (12°C) | COPd (declared COP) | 9.2 | 10.1 | 9.2 | 9.1 | 6.2 | 6.5 | 10.5 | |||||||||||||||||||||||||
| Pdh (declared heating cap) | kW | 8.7 | 6.9 | 8.7 | 7.4 | 4.9 | 5.1 | 8.9 | |||||||||||||||||||||||||
| Indoor index connection | Min. | 100 | 125 | 125 | 150 | 175 | 200 | 200 | 225 | 250 | |||||||||||||||||||||||
| Max. | 260 | 325 | 325 | 390 | 455 | 520 | 520 | 585 | 650 | ||||||||||||||||||||||||
| Dimensions | Unit | Height | mm | 1,685 | 1,685 | 1,685 | 1,685 | 1,685 | 1685 | 1685 | |||||||||||||||||||||||
| Width | mm | 930 | 930 | 930 | 1240 | 1240 | 1240 | 1240 | |||||||||||||||||||||||||
| Depth | mm | 765 | 765 | 765 | 765 | 765 | 765 | 765 | |||||||||||||||||||||||||
| Weight | Unit | kg | 230 | 230 | 230 | 314 | 314 | 317 | 317 | ||||||||||||||||||||||||
| Fan | External static pressure | Max. | Pa | 78 | 78 | 78 | 78 | 78 | |||||||||||||||||||||||||
| Compressor | Type | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | |||||||||||||||||||||||||
| Operation range | Cooling | Min. | °CDB | -5 | -5 | -5 | -5 | -5 | -5 | -5 | |||||||||||||||||||||||
| Max. | °CDB | 43 | 43 | 43 | 43 | 43 | 43 | 43 | |||||||||||||||||||||||||
| Heating | Min. | °CWB | -20 | -20 | -20 | -20 | -20 | -20 | -20 | ||||||||||||||||||||||||
| Max. | °CWB | 15.5 | 15.5 | 15.5 | 15.5 | 15.5 | 15.5 | 15.5 | |||||||||||||||||||||||||
| Sound power level | Cooling | Nom. | dBA | 78.0 (4) | 79.1 (4) | 81 | 83.4 (4) | 80.9 (4) | 85.6 (4) | 81 | |||||||||||||||||||||||
| Sound pressure level | Cooling | Nom. | dBA | 57 | 57 | 60 | 61 | 60 | 63 | 60 | 62 | 65 | |||||||||||||||||||||
| Refrigerant | Type | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | R-410A | |||||||||||||||||||||||
| GWP | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | ||||||||||||||||||||||||||
| Charge | tCO2Eq | 20.2 | 20.5 | 20.7 | 24.6 | 24.6 | |||||||||||||||||||||||||||
| Charge | kg | 9.7 | 9.8 | 9.9 | 11.8 | 11.8 | 11.8 | 11.8 | |||||||||||||||||||||||||
| Piping connections | Liquid | Type | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | ||||||||||||||||||||||||
| OD | mm | 9.5 | 9.5 | 9.5 | 12.7 | 12.7 | 12.7 | 12.7 | 15.9 | 15.9 | |||||||||||||||||||||||
| Gas | Type | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | Braze connection | |||||||||||||||||||||||||
| OD | mm | 19.1 | 22.2 | 22.2 | 28.6 | 28.6 | 28.6 | 28.6 | 28.6 | 28.6 | |||||||||||||||||||||||
| HP/LP gas | OD | mm | 15.9 | 19.1 | 19.1 | 19.1 | 22.2 | 22.2 | 22.2 | ||||||||||||||||||||||||
| Total piping length | System | Actual | m | 1,000 (6) | 1,000 (6) | 500 (6) | 1,000 (6) | 1,000 (6) | 1,000 (6) | 500 (6) | 1000 | 1000 | |||||||||||||||||||||
| Power supply | Name | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | |||||||||||||||||||||||
| Phase | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | ||||||||||||||||||||||||
| Frequency | Hz | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | |||||||||||||||||||||||
| Voltage | V | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | 380-415 | |||||||||||||||||||||||
| System | Outdoor unit module 1 | REMQ5U | REYQ8U | ||||||||||||||||||||||||||||||
| Outdoor unit module 2 | REMQ5U | REYQ8U | |||||||||||||||||||||||||||||||